Electrical Control Function
106
Electrical Control System
COOL_F6
ICOOLLMT2
COOL_F5
ICOOLLMT1
If the current frequency is lower than COOL_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>ICOOL, the AC will display the failure for 30 seconds and stop. The AC
will restart 3 minutes later.
Heating mode:
Current frequency
(
Hz
)
Current limit value
(
A
)
Frequency limit
HEAT_F16
IHEATLMT12
Decrease the frequency to HEAT_F4 and run at HEAT_F4 for
3 minutes.
After that, the frequency will be adjusted according to the
capacity demand and rise to the upper level every 3 minutes
(When the frequency>Heat_F4 via capacity demand).
HEAT_F15
IHEATLMT11
HEAT_F14
IHEATLMT10
HEAT_F13
IHEATLMT9
HEAT_F12
IHEATLMT8
HEAT_F11
IHEATLMT7
HEAT_F10
IHEATLMT6
HEAT_F9
IHEATLMT5
HEAT_F8
IHEATLMT4
HEAT_F7
IHEATLMT3
HEAT_F6
IHEATLMT2
HEAT_F5
IHEATLMT1
If the current frequency is lower than HEAT_F4, the frequency will not be limited.
After 10s of the compressor start, if the current>IHEAT, the AC will display the failure for 30 seconds and stop. The AC
will restart 3 minutes later.
1.2.9 Indoor / outdoor units communication protection
If the indoor units cannot receive the feedback signal from the outdoor units for 2 minutes, the AC will stop
and display the failure.
1.2.10 Oil return
Running rules:
1. If the compressor frequency keeps lower than RET_OIL_FREQ1_ADD for RET_OIL_TIME1_ADD, the
AC will rise the frequency to RET_OIL_FREQ2_ADD for RET_OIL_TIME2_ADD and then resume to
former frequency.
2. The EXV will keep 300p while the indoor units will keep the current running mode.
3. If the outdoor ambient is higher than TempT4HeatLimit_ADD during the oil return, the AC quit oil return.
1.3 Operation Modes and Functions
1.3.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed.
(3) Indoor fan can be set to high/med/low/auto;
(4) The louver operates same as in cooling mode.
(5) Auto fan:
For Cassette
、
Duct
Summary of Contents for 7SP091170
Page 16: ...Indoor Units 14 Indoor Units Part 2 Indoor Units HKD Type 15 HND Type 28 Light Commercial 41...
Page 28: ...Exploded View and Spare Part list 26 Indoor Units 4 7 Exploded view of model AWSI HKD024 N11...
Page 33: ...Dimensions Indoor Units 31 For AWSI HND012 N11 For AWSI HND018 N11 For AWSI HND024 N11...
Page 37: ...Exploded View and Spare Part list Indoor Units 35 4 3 Exploded view of model AWSI HND012 N11...
Page 39: ...Exploded View and Spare Part list Indoor Units 37 4 5 Exploded view of model AWSI HND018 N11...
Page 41: ...Exploded View and Spare Part list Indoor Units 39 4 7 Exploded view of model AWSI HND024 N11...
Page 45: ...Features Indoor Units 43 Dimension 75mm Fresh Air...
Page 50: ...Dimensions 48 Indoor Units 2 Dimensions 2 1 Four way cassette type compact 270...
Page 52: ...Dimensions 50 Indoor Units 2 3 Console...
Page 54: ...Service Space 52 Indoor Units 3 3 Console...
Page 57: ...Wiring Diagrams Indoor Units 55 4 5 AWSI DCD012 N11...
Page 58: ...Wiring Diagrams 56 Indoor Units 4 6 Model AWSI DID012 N11...
Page 59: ...Wiring Diagrams Indoor Units 57 4 7 AWSI XAD012 N11 4 8 Model AWSI XBD012 N11...
Page 72: ...Exploded View and Spare Part list 70 Indoor Units 5 13 Exploded view of model AWSI DID012 N11...
Page 74: ...Exploded View and Spare Part list 72 Indoor Units 5 15 Exploded view of model AWSI XBD009X N11...
Page 87: ...Wiring Diagrams Outdoor Units 85 4 Wiring Diagrams 4 1 AWAU YCZ218 H11 4 2 AWAU YCZ327 H11...
Page 88: ...Wiring Diagrams 86 Outdoor Units 4 3 AWAU YCZ430 H11...
Page 89: ...Wiring Diagrams Outdoor Units 87 AWAU YCZ542 H11 7SP091173...
Page 151: ...Electrical Control System 149 SERVICE MANUAL Multi Splits Series...