Electrical Control Function
112
Electrical Control System
----T3 rises to be higher than TCDE1
℃
.
----T3 keeps to be higher than TCDE2
℃
for 80 seconds.
----The machine has run for 10 minutes in defrosting mode.
Defrosting action
:
4-Way valve
Indoor fan
Outdoor fan
480P
PMV
PMV running
4 mins with 480P
Compressor
10S
30S
TimeA
10S
no longer than 10min
Cool-F9
Anti cold wind
1.3.3.5 High evaporator coil temp.T2 protection:
If T2>63
℃
, the indoor unit has no capacity demand and resume till 48
℃
.
.
1.3.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30
℃
.
In auto mode, the machine will choose cooling, heating or fan-
only mode according to ΔT (ΔT =T1-Ts).
ΔT=T1-Ts
Running mode
ΔT
>
1
℃
Cooling
-
1<ΔT≤1
℃
Fan-only
ΔT≤-1
℃
Heating
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
1.3.5 Drying mode
HKD,HND(9K,12K)
Indoor fan speed is
fixed at breeze and can’t be changed. The louver angle is the same as in cooling mode.
Summary of Contents for 7SP091170
Page 16: ...Indoor Units 14 Indoor Units Part 2 Indoor Units HKD Type 15 HND Type 28 Light Commercial 41...
Page 28: ...Exploded View and Spare Part list 26 Indoor Units 4 7 Exploded view of model AWSI HKD024 N11...
Page 33: ...Dimensions Indoor Units 31 For AWSI HND012 N11 For AWSI HND018 N11 For AWSI HND024 N11...
Page 37: ...Exploded View and Spare Part list Indoor Units 35 4 3 Exploded view of model AWSI HND012 N11...
Page 39: ...Exploded View and Spare Part list Indoor Units 37 4 5 Exploded view of model AWSI HND018 N11...
Page 41: ...Exploded View and Spare Part list Indoor Units 39 4 7 Exploded view of model AWSI HND024 N11...
Page 45: ...Features Indoor Units 43 Dimension 75mm Fresh Air...
Page 50: ...Dimensions 48 Indoor Units 2 Dimensions 2 1 Four way cassette type compact 270...
Page 52: ...Dimensions 50 Indoor Units 2 3 Console...
Page 54: ...Service Space 52 Indoor Units 3 3 Console...
Page 57: ...Wiring Diagrams Indoor Units 55 4 5 AWSI DCD012 N11...
Page 58: ...Wiring Diagrams 56 Indoor Units 4 6 Model AWSI DID012 N11...
Page 59: ...Wiring Diagrams Indoor Units 57 4 7 AWSI XAD012 N11 4 8 Model AWSI XBD012 N11...
Page 72: ...Exploded View and Spare Part list 70 Indoor Units 5 13 Exploded view of model AWSI DID012 N11...
Page 74: ...Exploded View and Spare Part list 72 Indoor Units 5 15 Exploded view of model AWSI XBD009X N11...
Page 87: ...Wiring Diagrams Outdoor Units 85 4 Wiring Diagrams 4 1 AWAU YCZ218 H11 4 2 AWAU YCZ327 H11...
Page 88: ...Wiring Diagrams 86 Outdoor Units 4 3 AWAU YCZ430 H11...
Page 89: ...Wiring Diagrams Outdoor Units 87 AWAU YCZ542 H11 7SP091173...
Page 151: ...Electrical Control System 149 SERVICE MANUAL Multi Splits Series...