Electrical Control Function
Electrical Control System
105
1. Electrical Control Function
1.1 Definition
T1: Room Air Thermistor (RAT)
T2: Indoor Coil Thermistor (ICT)
T2B: Indoor Return Gas Thermistor (RGT)
T3: Outdoor Coil Thermistor (OCT)
T4: Outdoor Air Thermistor (OAT)
T5: Compressor Discharge Thermistor (CTT)
1.2 Main Protection
1.2.1 Three minutes delay at restart for compressor.
1.2.2 Temperature protection of compressor discharge
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
----If 102
℃
<T5<115
℃
, decrease the frequency to the lower level every 2 minutes till to F1.
---If T5>115
℃
for 10 seconds, the compressor will stop and restart till T5<90
℃
.
1.2.3 Sensor protection at open circuit and breaking disconnection.
1.2.4 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
1.2.5 Fan speed is out of control(Excluding AWSI-HKD009-N11)
When indoor fan speed keeps too low for certain time, the unit will stop and the LED will display the failure.
1.2.6 Zero crossing detection error protection(only for AWSI-HKD009-N11)
If AC detects time interval is not correct for continuous 240s, the unit will stop and the LED will display the
failure. The correct zero crossing signal time interval should be between 6-13ms.
1.2.7 Inverter module protection
The Inverter module has a protection function about current, voltage and temperature. If these protections
happen, the corresponding code will display on indoor unit and the unit will stop working.
1.2.8 Compressor current limit protection
If the compressor current exceeds the current limit value for 10 seconds, the compressor frequency will be
limited as below table.
Cooling mode:
Current frequency
(
Hz
)
Current limit value
(
A
)
Frequency limit
COOL_F16
ICOOLLMT12
Decrease the frequency to COOL_F4 and run at COOL_F4 for
3 minutes.
After that, the frequency will be adjusted according to the
capacity demand and rise to the upper level every 3 minutes
(When the frequency>COOL_F4 via capacity demand).
COOL_F15
ICOOLLMT11
COOL_F14
ICOOLLMT10
COOL_F13
ICOOLLMT9
COOL_F12
ICOOLLMT8
COOL_F11
ICOOLLMT7
COOL_F10
ICOOLLMT6
COOL_F9
ICOOLLMT5
COOL_F8
ICOOLLMT4
COOL_F7
ICOOLLMT3
Summary of Contents for 7SP091170
Page 16: ...Indoor Units 14 Indoor Units Part 2 Indoor Units HKD Type 15 HND Type 28 Light Commercial 41...
Page 28: ...Exploded View and Spare Part list 26 Indoor Units 4 7 Exploded view of model AWSI HKD024 N11...
Page 33: ...Dimensions Indoor Units 31 For AWSI HND012 N11 For AWSI HND018 N11 For AWSI HND024 N11...
Page 37: ...Exploded View and Spare Part list Indoor Units 35 4 3 Exploded view of model AWSI HND012 N11...
Page 39: ...Exploded View and Spare Part list Indoor Units 37 4 5 Exploded view of model AWSI HND018 N11...
Page 41: ...Exploded View and Spare Part list Indoor Units 39 4 7 Exploded view of model AWSI HND024 N11...
Page 45: ...Features Indoor Units 43 Dimension 75mm Fresh Air...
Page 50: ...Dimensions 48 Indoor Units 2 Dimensions 2 1 Four way cassette type compact 270...
Page 52: ...Dimensions 50 Indoor Units 2 3 Console...
Page 54: ...Service Space 52 Indoor Units 3 3 Console...
Page 57: ...Wiring Diagrams Indoor Units 55 4 5 AWSI DCD012 N11...
Page 58: ...Wiring Diagrams 56 Indoor Units 4 6 Model AWSI DID012 N11...
Page 59: ...Wiring Diagrams Indoor Units 57 4 7 AWSI XAD012 N11 4 8 Model AWSI XBD012 N11...
Page 72: ...Exploded View and Spare Part list 70 Indoor Units 5 13 Exploded view of model AWSI DID012 N11...
Page 74: ...Exploded View and Spare Part list 72 Indoor Units 5 15 Exploded view of model AWSI XBD009X N11...
Page 87: ...Wiring Diagrams Outdoor Units 85 4 Wiring Diagrams 4 1 AWAU YCZ218 H11 4 2 AWAU YCZ327 H11...
Page 88: ...Wiring Diagrams 86 Outdoor Units 4 3 AWAU YCZ430 H11...
Page 89: ...Wiring Diagrams Outdoor Units 87 AWAU YCZ542 H11 7SP091173...
Page 151: ...Electrical Control System 149 SERVICE MANUAL Multi Splits Series...