![Airwell 7SP091170 Service Manual Download Page 104](http://html1.mh-extra.com/html/airwell/7sp091170/7sp091170_service-manual_2879972104.webp)
Installation details
102
Installation
4.1.2
For outdoor unit YCZ327/YCZ430/YCZ542
1) Completely tighten the flare nuts of the indoor and each braches of outdoor unit, confirm that both the
main valves(Gas and liquid) are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the Main valve(Gas) service port..
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Fully open the branch valves (A/B/C/D/E)
6) Operate the vacuum pump to evacuate.
7) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If
the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If the
pressure
can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump. Confirm
that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
8) Open the Main valve(Gas) about 45° counterclockwise for 6 or 7seconds after the gas
coming out, then close the valve again. Make sure the pressure display in the pressure indicator is a little
higher than the atmosphere pressure. Then remove the charge hose from the Main valve(Gas).
9) Fully open the main valve(Gas) and main valve (Liquid) and securely tighten the cap of the valves.
Lo
Hi
Manifold Valve
Vacuum pump
Handle Lo
Handle Hi
Charge Hose
Main Valve
(Gas)
Branch valve
(Gas)
Main Valve
(Liquid)
Outdoor Unit
To
indoor unit
Pressure gauge
Open
Close
Vacuum outdoor unit YCZ327/YCZ430/YCZ542
4.3. Adding the refrigerant if the pipe length exceeding the pre-charged length
Procedure:
1) Connect the charge hose to the charging cylinder R410a, make the cylinder bottom up to ensure the
liquid charge.
2) Purge the air from the charge hose and connect the hose to the service port on gas valve (Main or any
branch)
3) Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air
(be careful of the liquid refrigerant).
4) Put the charging cylinder onto the electronic scale and record the weight.
5) Operate the air conditioner at the cooling mode.
6) Open the valve (Lo) on the charge set and charge the system with liquid refrigerant.
7) When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose
from the gas valve service port immediately and turn off the air conditioner before disconnecting the
hose.
8) Mount the valve stem caps onto the service port
Summary of Contents for 7SP091170
Page 16: ...Indoor Units 14 Indoor Units Part 2 Indoor Units HKD Type 15 HND Type 28 Light Commercial 41...
Page 28: ...Exploded View and Spare Part list 26 Indoor Units 4 7 Exploded view of model AWSI HKD024 N11...
Page 33: ...Dimensions Indoor Units 31 For AWSI HND012 N11 For AWSI HND018 N11 For AWSI HND024 N11...
Page 37: ...Exploded View and Spare Part list Indoor Units 35 4 3 Exploded view of model AWSI HND012 N11...
Page 39: ...Exploded View and Spare Part list Indoor Units 37 4 5 Exploded view of model AWSI HND018 N11...
Page 41: ...Exploded View and Spare Part list Indoor Units 39 4 7 Exploded view of model AWSI HND024 N11...
Page 45: ...Features Indoor Units 43 Dimension 75mm Fresh Air...
Page 50: ...Dimensions 48 Indoor Units 2 Dimensions 2 1 Four way cassette type compact 270...
Page 52: ...Dimensions 50 Indoor Units 2 3 Console...
Page 54: ...Service Space 52 Indoor Units 3 3 Console...
Page 57: ...Wiring Diagrams Indoor Units 55 4 5 AWSI DCD012 N11...
Page 58: ...Wiring Diagrams 56 Indoor Units 4 6 Model AWSI DID012 N11...
Page 59: ...Wiring Diagrams Indoor Units 57 4 7 AWSI XAD012 N11 4 8 Model AWSI XBD012 N11...
Page 72: ...Exploded View and Spare Part list 70 Indoor Units 5 13 Exploded view of model AWSI DID012 N11...
Page 74: ...Exploded View and Spare Part list 72 Indoor Units 5 15 Exploded view of model AWSI XBD009X N11...
Page 87: ...Wiring Diagrams Outdoor Units 85 4 Wiring Diagrams 4 1 AWAU YCZ218 H11 4 2 AWAU YCZ327 H11...
Page 88: ...Wiring Diagrams 86 Outdoor Units 4 3 AWAU YCZ430 H11...
Page 89: ...Wiring Diagrams Outdoor Units 87 AWAU YCZ542 H11 7SP091173...
Page 151: ...Electrical Control System 149 SERVICE MANUAL Multi Splits Series...