TROUBLE SHOOTING
Version - 1 58 HND DCI
11.2.9 High temperature protection of compressor top diagnosis and solution (P2)
Error Code
P2
Malfunction decision
conditions
If the sampling voltage is not 5V, the LED will display the failure.
Supposed causes
●
Power supply problems.
●
System leakage or block
●
PCB faulty
Trouble shooting:
Check the air flow system
of indoor and outdoor units
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Power off, then restart the unit 10
minutes later
Check if the temperature
of compressor
No
Check refrigerant system
Yes
Check the overload
protector
Correct the connection.
No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.
No
Replace the outdoor control PCB.
Yes
Summary of Contents for 7SP023034
Page 12: ...DIMENSIONS Version 1 12 HND DCI For AWSI HND009 N11 For AWSI HND012 N11...
Page 13: ...DIMENSION HND DCI 13 Version 1 For AWSI HND018 N11 For AWSI HND024 N11...
Page 16: ...DIMENSIONS Version 1 16 HND DCI For AWAU YND024 H11...
Page 28: ...WIRING DIAGRAM Version 1 28 HND DCI 7 3 Outdoor unit AWAU YND018 H11...
Page 29: ...WIRING DIAGRAM HND DCI 29 Version 1 7 4 Outdoor unit AWAU YND024 H11...
Page 66: ...EXPLODED VIEW AND SPARE PART LIST Version 1 66 HND DCI 12 2 AWSI HND012 N11...
Page 68: ...EXPLODED VIEW AND SPARE PART LIST Version 1 68 HND DCI 12 3 AWSI HND018 N11...
Page 70: ...EXPLODED VIEW AND SPARE PART LIST Version 1 70 HND DCI 12 4 AWSI HND024 N11...
Page 72: ...EXPLODED VIEW AND SPARE PART LIST Version 1 72 HND DCI 12 5 AWAU YND009 H11...
Page 74: ...EXPLODED VIEW AND SPARE PART LIST Version 1 74 HND DCI 12 6 AWAU YND012 H11...
Page 76: ...EXPLODED VIEW AND SPARE PART LIST Version 1 76 HND DCI 12 7 AWAU YND018 H11...
Page 78: ...EXPLODED VIEW AND SPARE PART LIST Version 1 78 HND DCI 12 8 AWAU YND024 H11...
Page 80: ...Version 1 80 HND DCI SERVICE MANUAL HND DCI Series...