PERFORAMCNE DATA
Version - 1
20 HND DCI
2) Heating
ID COIL ENTERING AIR DB TEMPERATURE [C
0
]
OD COIL ENTERING
AIR DB/WB
TEMPERATURE [C
0
]
DATA
15
20
25
-15/-16
TC
2.36
2.19
2.03
PI
0.53
0.58
0.64
-10/-12
TC
2.62
2.46
2.29
PI
0.64
0.69
0.74
-7/-8
TC
2.82
2.66
2.49
PI
0.72
0.77
0.83
-1/-2
TC
2.92
2.76
2.59
PI
0.76
0.81
0.87
2/1
TC
2.99
2.82
2.66
PI
0.79
0.84
0.89
7/6
TC
3.86
3.70
3.54
PI
0.83
0.88
0.93
10/9
TC
4.08
3.91
3.75
PI
0.88
0.93
0.98
15/12
TC
4.29
4.13
3.96
PI
0.93
0.98
1.03
15-24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
Legend
TC -Total Capacity [kW]
PI - Power Input [kW]
WB -Wet Bulb Temperature
DB -Dry Bulb Temperature
ID - Indoor
OD
–
Outdoor
Summary of Contents for 7SP023034
Page 12: ...DIMENSIONS Version 1 12 HND DCI For AWSI HND009 N11 For AWSI HND012 N11...
Page 13: ...DIMENSION HND DCI 13 Version 1 For AWSI HND018 N11 For AWSI HND024 N11...
Page 16: ...DIMENSIONS Version 1 16 HND DCI For AWAU YND024 H11...
Page 28: ...WIRING DIAGRAM Version 1 28 HND DCI 7 3 Outdoor unit AWAU YND018 H11...
Page 29: ...WIRING DIAGRAM HND DCI 29 Version 1 7 4 Outdoor unit AWAU YND024 H11...
Page 66: ...EXPLODED VIEW AND SPARE PART LIST Version 1 66 HND DCI 12 2 AWSI HND012 N11...
Page 68: ...EXPLODED VIEW AND SPARE PART LIST Version 1 68 HND DCI 12 3 AWSI HND018 N11...
Page 70: ...EXPLODED VIEW AND SPARE PART LIST Version 1 70 HND DCI 12 4 AWSI HND024 N11...
Page 72: ...EXPLODED VIEW AND SPARE PART LIST Version 1 72 HND DCI 12 5 AWAU YND009 H11...
Page 74: ...EXPLODED VIEW AND SPARE PART LIST Version 1 74 HND DCI 12 6 AWAU YND012 H11...
Page 76: ...EXPLODED VIEW AND SPARE PART LIST Version 1 76 HND DCI 12 7 AWAU YND018 H11...
Page 78: ...EXPLODED VIEW AND SPARE PART LIST Version 1 78 HND DCI 12 8 AWAU YND024 H11...
Page 80: ...Version 1 80 HND DCI SERVICE MANUAL HND DCI Series...