INSTALLATION DETAILS
HND DCI 31 Version - 1
8.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas
Liquid
AWSI-HND009-N11 / AWAU-YND009-H11
3/8’’
(
Ф9.52)
1/4’’
(Ф6.35)
5
10
25
15
AWSI-HND012-N11 / AWAU-YND012-H11
3/8’’
(
Ф9.52)
1/4’’
(Ф6.35)
5
10
25
15
AWSI-HND018-N11 / AWAU-YND018-H11
1/2
’’
(Ф12.7)
1/4’’
(Ф6.35)
5
20
30
15
AWSI-HND024-N11 / AWAU-YND024-H11
5
/8’’
(
Ф15.9)
3/8’’
(
Ф9.52)
5
25
50
30
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
Summary of Contents for 7SP023034
Page 12: ...DIMENSIONS Version 1 12 HND DCI For AWSI HND009 N11 For AWSI HND012 N11...
Page 13: ...DIMENSION HND DCI 13 Version 1 For AWSI HND018 N11 For AWSI HND024 N11...
Page 16: ...DIMENSIONS Version 1 16 HND DCI For AWAU YND024 H11...
Page 28: ...WIRING DIAGRAM Version 1 28 HND DCI 7 3 Outdoor unit AWAU YND018 H11...
Page 29: ...WIRING DIAGRAM HND DCI 29 Version 1 7 4 Outdoor unit AWAU YND024 H11...
Page 66: ...EXPLODED VIEW AND SPARE PART LIST Version 1 66 HND DCI 12 2 AWSI HND012 N11...
Page 68: ...EXPLODED VIEW AND SPARE PART LIST Version 1 68 HND DCI 12 3 AWSI HND018 N11...
Page 70: ...EXPLODED VIEW AND SPARE PART LIST Version 1 70 HND DCI 12 4 AWSI HND024 N11...
Page 72: ...EXPLODED VIEW AND SPARE PART LIST Version 1 72 HND DCI 12 5 AWAU YND009 H11...
Page 74: ...EXPLODED VIEW AND SPARE PART LIST Version 1 74 HND DCI 12 6 AWAU YND012 H11...
Page 76: ...EXPLODED VIEW AND SPARE PART LIST Version 1 76 HND DCI 12 7 AWAU YND018 H11...
Page 78: ...EXPLODED VIEW AND SPARE PART LIST Version 1 78 HND DCI 12 8 AWAU YND024 H11...
Page 80: ...Version 1 80 HND DCI SERVICE MANUAL HND DCI Series...