PRODUCT SPECIFICATION
Version - 1 10 HND DCI
3.4 AWSI-HND012-N11 / AWAU-YND012-H11
Model Indoor Unit
AWSI-HND024-N11
Model Outdoor Unit
AWAU-YND024-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average Warm
Cold
Capacity
(1)
kW
7.05(2.7-7.8)
7.3(1.6-8.7)
Pdesign
kW
7.05
5.7
7.1
8.0
SEER /SCOP
(2)
W/W
7.0
4
5.1
3.3
Energy efficiency class
A++
A+
A+++
B
Annual energy consumption
kWh
353
1995
1949
5091
Tbiv
o
C
N/A
-7
2
-15
Tol
o
C
N/A
-15
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating
A
25
INDOOR
Fan type & quantity
Cross flow fan x1
Fan speeds
H/M/L/VL
RPM
1000/900/700
Air flow
(3)
H/M/L/VL
m3/hr
1050/950/700
External static pressure
Min-Max
Pa
0
Sound power level
(4)
H/M/L
dB(A)
64
Sound pressure level
(5)
H/M/L/VL
dB(A)
46/41/34/28
Moisture removal
l/hr
2.4
Condensate drain tube I.D
mm
16
Dimensions
WxHxD
mm
1186x258x343
Weight
kg
15.6
Package dimensions
LxWxH
mm
1265x340x420
Packaged weight
kg
20.6
Stacking height
units
7
OUTDOO
R
Refrigerant control
EEV
Compressor type, model
Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
810/750/600
Air flow
H/L
m3/hr
2700
Sound power level
(4)
H/L
dB(A)
69
Sound pressure level
(5)
H/L
dB(A)
59
Dimensions
WxHxD
mm
845x363x702
Weight
kg
48.4
Package dimensions
LxWxH
mm
965x395x755
Packaged weight
kg
51.6
Stacking height
Units
3
Refrigerant type
R410A
Refrigerant charge (standard connecting tubing length)
kg(5m)
2
Additional charge per 1 meter
gr / 1m
30
Connections between units
Liquid line
In.(mm)
3/8"
Suction line
In.(mm)
5/8"
Max.tubing length
m.
50
Max.height difference
m.
25
Operation control type
Remote control
Heating elements
kW
NA
Others
(1)
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
Summary of Contents for 7SP023034
Page 12: ...DIMENSIONS Version 1 12 HND DCI For AWSI HND009 N11 For AWSI HND012 N11...
Page 13: ...DIMENSION HND DCI 13 Version 1 For AWSI HND018 N11 For AWSI HND024 N11...
Page 16: ...DIMENSIONS Version 1 16 HND DCI For AWAU YND024 H11...
Page 28: ...WIRING DIAGRAM Version 1 28 HND DCI 7 3 Outdoor unit AWAU YND018 H11...
Page 29: ...WIRING DIAGRAM HND DCI 29 Version 1 7 4 Outdoor unit AWAU YND024 H11...
Page 66: ...EXPLODED VIEW AND SPARE PART LIST Version 1 66 HND DCI 12 2 AWSI HND012 N11...
Page 68: ...EXPLODED VIEW AND SPARE PART LIST Version 1 68 HND DCI 12 3 AWSI HND018 N11...
Page 70: ...EXPLODED VIEW AND SPARE PART LIST Version 1 70 HND DCI 12 4 AWSI HND024 N11...
Page 72: ...EXPLODED VIEW AND SPARE PART LIST Version 1 72 HND DCI 12 5 AWAU YND009 H11...
Page 74: ...EXPLODED VIEW AND SPARE PART LIST Version 1 74 HND DCI 12 6 AWAU YND012 H11...
Page 76: ...EXPLODED VIEW AND SPARE PART LIST Version 1 76 HND DCI 12 7 AWAU YND018 H11...
Page 78: ...EXPLODED VIEW AND SPARE PART LIST Version 1 78 HND DCI 12 8 AWAU YND024 H11...
Page 80: ...Version 1 80 HND DCI SERVICE MANUAL HND DCI Series...