48
1. Wire AirTouch 2+, gateway and AC indoor as per diagram below and leave the
dipswitches on the gateway at their default position. Make sure all wires are
connected properly.
2. Initialise the AC Unit with LG AC Wall Controller connected. The LG wall
controller can be wired to CN-REMO in parallel with the gateway.
3. If the LG wall controller is not going to be used after commissioning and the
return air sensor is used for AC temperature control: Turn off power and
disconnect the AC Wall Controller and set position 1 of S1 on the gateway to
ON (1). Then restart the AC and gateway first and then power up AirTouch 2+.
Or power them up at the same time.
4. If AirTouch 2+ sensors are used for AC temperature control:
Settings on the LG AC wall controller: Set thermostat sensor in the remote
controller (Go to Function Setting (Zone->Setting->Sensor), change it to REMO.
Remove it after the setting if the LG wall controller is not going to be used after
commissioning.
Settings on the gateway: set position 1 of S1 on the gateway to ON (1)
Settings on the AirTouch 2+ screen: Go to AC Setup and select the proper
temperature sensor for AC control.
Restart the AC and gateway first and then power up AirTouch 2+. Or power
them up at the same time.
(657219) Commissioning notes
Wiring Diagrams contd.