32
(657237) Commissioning notes
1. Initialise the AC Unit with Daikin AC Wall Controller connected to set the field
settings as required. Turn off power and disconnect the AC Wall Controller
from AC Indoor Unit.
2. Wire AirTouch, gateway and AC indoor as per diagram and leave the
dipswitches on the gateway at their default position if the Daikin wall controller
is not connected. Make sure all wires are connected properly. If the gateway
address is not 1, follow the Gateway Address Setting table to set dipswitch S1.
3. If the gateway is set to Master (default), set the Daikin wall controller to Sub.
If AirTouch sensors are used for AC temperature control:
Settings on the Daikin AC wall controller: Make sure the Daikin wall controller is
connected as Main. Go to Field Setting, find Mode 10 (20), code 2 and change
its value to 03 to set thermostat sensor to the remote controller. Remove it
after the setting if the Daikin wall controller is not going to be used. Otherwise,
set Daikin AC wall controller as sub controller.
Settings on the gateway: set position 4 of S2 on the gateway to ON (1) (default)
Settings on the AirTouch screen: Select the proper sensor or combination from
the Installer’s AC setting.
Restart the AC and gateway first and then power up AirTouch. Or power them
up at the same time.
4. If Daikin wall controller is to be used with AirTouch as Main, set the gateway to
Sub. If AirTouch sensors are used for AC temperature control:
Settings on the Daikin AC wall controller: Go to Field Setting, find Mode 10 (20),
code 2 and change its value to 03 to set thermostat sensor to the remote
controller.
Settings on the gateway: set position 4 of S2 on the gateway to Off(0)
Settings on the AirTouch screen: Select the proper sensor or combination from
the Installer’s AC setting
Restart the AC and gateway first and then power up AirTouch. Or power them
up at the same time.
Wiring Diagrams contd.