Fig.8-2 Example: YNRM = MPOS with YA = 10% and YE = 80%
Fig.8-3 Example: YNRM = FLOW with YA = 10% and YE = 80%
42. SAFE
Safe position
Only when parameter 43 “BIN” is turned “ON”, the "Security Position" function is
effective. If the binary input is "0", the valve is driven to the position specified by this
value.
43.
BIN
Function Binary – Digit Input
Use this parameter to specify whether you can turn the Security Position feature “ON”
or “OFF”.
44. DO1
Digit output function1
If the positioner has detected a setting error, channel 1(DO1) from the binary output
module is "high" (contact closed).
45. SW1
DO1 – set value
If DO1 = LSET, the valve position is smaller than SW1, channel 1(DO1) of the binary
output module "high".
If DO1 = HSET, valve position is greater than SW1, channel 1(DO1) of the binary output
module "high".
46. DO2
Digit output function 2
If the positioner has detected a setting error, channel 2(DO2) from the binary output
module is "high" (contact closed).