6
User parameter
6.1 Parameter list
No of parameter
Display
Function
Content / Scope
Default
setting
Unit
P1
01 INIA
#
INIA
Automatic initialization:
Do not start
Start
No
STRT
No
02 INIM
#
INIM
Manual initialization:
Do not start
Start
No
STRT
No
03 Reserve
04 Type
#
TYPE
.
Type of rotary actuator:
Linear actuator /rotary actuator
LINE
TURN
LINE
05 Reserve
06 DEBA
#
DEBA
Controller's dead band
Car
0,1 … 10,0
Car
%
07 DEBA1
DEBA1
Controller's dead band 1
Car
0,1 … 10,0
Car
%
08 PRST
#
PRST
Reset to factory setting
Not activated
Reset to factory setting after
pressing the button for 5s
No
STRT
No
P2
09 SDIR
#
SDIR
Setpoint direction
Rising
Falling
RISE
FALL
RISE
10 SPRA
#
SPRA
Split range start
0,0 … 100,0
0.0
%
11 SPRE
#
SPRE
Split area end
0,0 … 100,0
100.0
%
12 TSUP
#
TSUP
Setpoint ramp up
AUTO
0 … 400
0
s
13 TSDO
#
TSDO
Setpoint ramp down
AUTO
0 … 400
0
s
14 SFCT
#
SFCT
Setpoint function
Valve characteristics linear
Equal percentage
Inverse equal percentage
21 points freely adjustable
3 points freely adjustable
LINE
1:30
30:1
FREE
3-POT
LINE
15
~
35
SP00
~
SP20
#
SP00
~
#
SP20
Setpoint -turning points
0,0 … 100,0
%