Technical Data SR C0C0 Units
Waterside Pressure Drop Data
Valve Kv
M
SR09 C0C0
16.0
0.44
SR12 C0C0
25.0
0.69
SR15 C0C0
25.0
0.69
SR18 C0C0
40.0
1.11
Includes coil, 2 or 3 port valve and pipework.
To calculate 3 port valve pressure drop:
∆P valve =
2
M
Q
where ∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
36
Kv
Fluid 100% water.
8
SR09D020-C0C0 / SR09D025-C0C0
9
SR12D030-C0C0 / SR12D035-C0C0
10
SR15D040-C0C0 / SR15D045-C0C0
11
SR18D050-C0C0 / SR 18D060-C0C0
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
90.0
0.00
1.00
2.00
3.00
4.00
5.00
6.00
Pre
ss
ure
D
ro
p (
kP
a)
Flow Rate (l/s)
8
9
10
11
SmartCool™ 6 - 200kW
Precision Air Conditioning
60
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
C0
C0
Te
ch
ni
ca
l
C0
C0
SR