Controls
Password Protection
The control system integrity shall be maintained by restricting access with a password PIN number.
IMPORTANT
To change the PIN , please contact Airedale at time of order with the preferred 4 digit number.
Remote On/Off
Terminals for interlocking shall be provided to enable or disable the unit remotely.
Fire Shut Down
Terminals for interlocking shall be provided to shut down the unit in the event of fire.
Evaporator Fan Hours Run Log & Reset
Shall allow the user to monitor the running times of the evaporator fans and reset after maintenance.
Hours run log or visual service indicator shall be provided.
Evaporator Fan Speed Control
Evaporator fan speed control shall be easily set via the display keypad and can be incrementally increased or decreased
to meet on site airflow and external static pressure requirements.
Filter Change Alarm
Filter change shall be managed by the software, and shall be based on fan(s) hours run with an alarm being generated
when the pre-set run time limit has been exceeded. The set-point value shall be adjusted to suit each application and is
factory set to 4000 hours.
Standard Network Features
As standard the controller shall be capable of providing a platform for the following and shall be enabled on request for 2
to 8 units, please specify at order:
Networking
A Local Area Network (pLAN ) shall be used to connect up to 8 units to offer intercommunication and Run / Standby
control. This also allows the connection of computers, printers and modems on the same communications ring.
For further details, please contact Airedale Controls.
Run / Standby Operation
The controller shall enable units to operate in run/standby mode, with up to 8 units networked together, without the need
for additional hardware or controllers. Standby units shall be configured to start when the run unit has a critical alarm.
Smart Key
A smart key shall be supplied to offer software back-up of the control strategy. The key shall feature simple plug in
operation and allow transfer of software programs from the key to the microprocessor and vice versa. The use of a
service laptop shall not be necessary.
Audible Alarm
The display keypad shall be upgraded to include audible alerts.
Water Detector
Three methods shall be available:
1.
A solid state (probe) sensor shall be supplied loose for remote mounting on site.
2.
Tape suitable for sensing water droplets shall be supplied loose for remote mounting on site. Standard tape
length 10m.
3.
Condensate drain tray level detection.
Fire Detection
Shall be supplied loose for installation in the return air stream to shut down the unit in the event of an unusually high
return air temperature.
Smoke Detector
Shall be supplied loose for remote mounting to shut down the unit and activate the alarm upon sensing the presence of
smoke.
When adding to an existing network, please consult Airedale to ensure strategy compatibility.
CAUTION
Precision Air Conditioning
SmartCool™ 6 - 200kW
31
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018