Pressure Independant Control Valve (PICV) 

Pressure Independant Control Vales (PICV) fitted to the SmartCool ensure that constant waterflow is achieved. The PICV 

valves maintain the design flowrate based upon the valve setup.

Valve

Unit

DN20

DN25

DN32

DN40

DN50

DN65

DN80

DN100

SD18D-CH00

-

-

-

-

-

SD22D-CH00

-

-

-

-

SD25D-CH00

-

-

-

SD31D-CH00

-

-

-

-

SD35D-CH00

-

-

-

-

SD18D-CL00

-

-

-

-

SD22D-CL00

-

-

-

-

SD25D-CL00

-

-

-

SD31D-CL00

-

-

-

-

SD35D-CL00

-

-

-

-

SD18D-CHCH

-

-

-

SD22D-CHCH

-

-

-

SD25D-CHCH

-

-

SD31D-CHCH

-

-

-

SD35D-CHCH

-

-

-

SD18D-CLCL

-

-

-

SD22D-CLCL

-

-

SD25D-CLCL

-

-

SD31D-CLCL

-

-

SD35D-CLCL

-

-

-

 

 Standard Features   

 Optional Features  

 Feature Not Available

Valve

DN20

DN25

DN32

DN40

SN06D-C000

SN09D-C000

SN12D-C000

SR09D-C000

SR12D-C000

SR15D-C000

SR18D-C000

 

 Standard Features   

 Optional Features  

 Feature Not Available

SD Units

SN / SR Units

SmartCool™ 6 - 200kW

Precision Air Conditioning

18

Introduction

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018

Summary of Contents for SmartCool SD Series

Page 1: ...SmartCool Downflow 6 to 200kW Technical Manual SN SR and SD SmartCool Chilled Water ...

Page 2: ...ies 44 0 113 239 1000 enquiries airedale com International Enquiries 44 0 113 239 1000 enquiries airedale com Spares Hot Line 44 0 113 238 7878 spares airedale com Airedale Service 44 0 113 239 1000 service airedale com Technical Support 44 0 113 239 1000 tech support airedale com Training Enquiries 44 0 113 239 1000 training airedale com For information visit us at our web site www airedale com A...

Page 3: ...y It is our policy to Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements Train personnel in sound environmental practices Pursue opportunities to conserve resources prevent pollution and eliminate waste Manufacture products in a responsible manner with minimum impact on the environment Reduce our use of chemicals and minimise their release ...

Page 4: ...gard to manual handling This requirement is down to the discretion of the engineer Remember do not perform a lift that exceeds your ability Pressure Equipment Directive 2014 68 EU Minimum and Maximum Operation Temperature TS and Pressure PS Waterside Allowable Temperature Range TS Min 5 C to Max 40 C Maximum Allowable Pressure PS 10 Barg Based on the waterside temperature in the unit off state in ...

Page 5: ... Services 44 Glycol 47 Water Detection Tape Installation 48 pLAN Termination 49 Technical Data SN C000 Units 50 Mechanical and Electrical Data 50 Waterside Pressure Drop Data 51 Measurement of Sound Data 52 Sound Data 53 Interconnecting Wiring 54 Technical Data SR C000 Units 55 Mechanical and Electrical Data 55 Waterside Pressure Drop Data 56 Sound Data 57 Interconnecting Wiring 58 Technical Data ...

Page 6: ...erconnecting Wiring 72 Technical Data SD CHCH Units 73 Mechanical and Electrical Data 73 Waterside Pressure Drop Data 74 Sound Data 76 Interconnecting Wiring 77 Technical Data SD CLCL Units 78 Mechanical and Electrical Data 78 Waterside Pressure Drop Data 79 Sound Data 81 Interconnecting Wiring 82 After Sales 83 Contents SmartCool 6 200kW Precision Air Conditioning 6 Introduction SmartCool 6 200kW...

Page 7: ...cities 35 C 24 RH 18 C 24 C Water Range Performance kW SN C000 1 13 36 SR C000 1 35 98 SR C0C0 1 25 70 Range Performance kW SD CH00 1 105 255 SD CHCH 1 75 184 SD CL00 2 92 215 SD CLCL 2 75 185 Moisture Content Operating Band Moisture Content kg kg Dry Air W e t B u l b T e m p e r a t u r e C Dry Bulb Temperature C 40 6 0 7 0 8 0 9 0 20 10 1 0 15 20 25 5 0 15 18 27 10 5 0 20 25 30 35 40 1 0 0 5 0 ...

Page 8: ...all reduce sound breakout and eradicate air leakage In seal type foam based door seals shall not be acceptable The control panel is mounted on hinges to allow easy removal of filters and access to several electrical components The unit design shall incorporate a series of M6 fixings to the top and bottom face to ease customer ductwork connection and reduce installation time SD Units The cabinet sh...

Page 9: ...thin unit Separate floorstand min 350mm SD CL00 CLCL Units Fans located within floorstand Floorstand integral to unit min 600mm SD CH00 CHCH Units Fans located within floorstand Floorstand integral to unit min 600mm Precision Air Conditioning SmartCool 6 200kW 9 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_2018 Introduction ...

Page 10: ...iguration SN C000 SR C000 CL00 CH00 Dual Circuit System Configuration SR C0C0 SD CLCL SD CHCH SmartCool 6 200kW Precision Air Conditioning 10 Introduction SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_2018 ...

Page 11: ...roduct Name SmartCool D Product Variant Dedicated Chilled Water 18 1800 mm 22 2200 mm 25 Case Width 2500 mm 31 3100 mm 35 3500 mm D Downflow 085 255 Nominal Cooling Capacity kW Separator C Chilled Water H Coil Streamed For High Flow L Coil Streamed For Low Flow C Chilled Water Circuit 0 No Chilled Water Circuit H Coil Streamed For High Flow L Coil Streamed For Low Flow Separator 0 400V 3Ph N 50Hz 1...

Page 12: ...er Valves Fans Humidification Hinged Control Panel Humidifier Chilled Water Pipework Floor Height Floorstand Air Filters Fixed Control Panel SmartCool 6 200kW Precision Air Conditioning 12 Introduction SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_2018 ...

Page 13: ...N SR Range SD Range Cooling Coil Chilled Water Valves Valves Pipework Connections Cooling Coil Precision Air Conditioning SmartCool 6 200kW 13 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_2018 Introduction ...

Page 14: ...ed from plain copper tubes with mechanically bonded aluminium fins Fins shall be coated with a non stick acrylic film hydrophilic to provide additional corrosion protection and efficient surface water removal for improved performance Plain aluminium shall not be acceptable The cooling coil shall be mounted over a full width stainless steel condensate tray A 22mm condensate drain hose connection sh...

Page 15: ...langed Connections For spool and unit termination two types of flange shall be available For the spool termination a bespoke flange design shall incorporate a flange profile and gasket configuration For the unit termination a PN16 round bi metallic flange shall be used The unit termination end shall require staggering by 100mm to allow fitting of the flanges as shown Nominal Diameter mm Pipe Size ...

Page 16: ...3 Port Chilled Water Valves with Bypass Standard Features Optional Features Feature Not Available Inlet Outlet 0 10V DC 3 Port Regulating Valve BI BI BI BI WTS BL DR Coil s M Inlet Outlet 0 10V DC 3 Port Regulating Valve Bypass Valve BI BI BI BI WTS BL DR Coil s M Binder Point Bleed Valve Drain Valve Water Temperature Sensor DR WTS BL BI M M 0 10V DC 3 Port Regulating Valve 0 10V DC 2 Port Regulat...

Page 17: ...ommissioning The auto commissioning shall be enabled by using a differential pressure transducer to maintain balanced water flow through the bypass The controller maintains the same pressure drop through the coil and the bypass A fixed flowrate is required for this initial commissioning to occure 2 Port Valve Inlet Outlet BI BI BI WTS BL DR Coil s M 2 Port Valve Inlet Outlet Bypass Valve BI BI WTS...

Page 18: ... CL00 SD22D CL00 SD25D CL00 SD31D CL00 SD35D CL00 SD18D CHCH SD22D CHCH SD25D CHCH SD31D CHCH SD35D CHCH SD18D CLCL SD22D CLCL SD25D CLCL SD31D CLCL SD35D CLCL Standard Features Optional Features Feature Not Available Valve DN20 DN25 DN32 DN40 SN06D C000 SN09D C000 SN12D C000 SR09D C000 SR12D C000 SR15D C000 SR18D C000 Standard Features Optional Features Feature Not Available SD Units SN SR Units ...

Page 19: ...orrosion resistance the impellers shall be composite plastic with a galvanised rotor System Configuration Range SN SR SD Number of Circuits Single Single Dual Single Dual Chilled Water EC Backward Curved Centrifugal Fans in Unit EC Backward Curved Centrifugal Fans in Floorstand G4 Air Filtration High Grade F7 Filtration Airflow Monitoring Airflow Switch Constant Air Volume Constant Pressure Contro...

Page 20: ...llustration on the right shows a comparison of the typical power input required by each method Standard Filtration Pleated disposable panel filters in a rigid frame Conform to ISO16890 2016 with filtration classes of ISO C 85 SN ISO C 75 SR and ISO C 80 SD Access and removal from unit front As standard the microprocessor provides an alarm following a pre set run time limit being exceeded High Grad...

Page 21: ...Monitoring Phase Monitoring Relay Ultra Capacitive Module Controller Power Backup Dual Power Supply Variable Humidification Electric Heating Modulating Electric Heating Standard Features Optional Features Feature Not Available Fitted as standard when dual power supply is fitted Precision Air Conditioning SmartCool 6 200kW 21 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_2018 ...

Page 22: ...ow for essential maintenance of other components within the unit SN SR Units only The electrical control panels are wired to the latest European standards and codes of practice SD Units Optional Control Panel Standard Control Panel Optional Control Panel Optional control panels are fitted dependant on which optional features are fitted Control Panel Closed Control Panel Open SmartCool 6 200kW Prec...

Page 23: ...t shall be phase balanced for increased efficiency The electric heating elements are designed to be located within the unit s fan module This enables the unit to effectively re heat the air and evenly distribute the temperature within the floor void All sizes of electric heating are configurable based upon customer requirements A bank of 7 5kW is allocated per fan and as standard each can be downs...

Page 24: ...ge enables the humidification to be configured to meet the customers design requirements and conditions Note the 30 kg hr option utilises 2 x 15 kg hr bottles SN06 SN09 SN12 SR09 SR12 SR15 SR18 SD18 SD22 SD25 SD31 SD35 3kg hr Humidification 8kg hr Humidification 15kg hr Humidification 30kg hr Humidification Standard Features Optional Features Feature Not Available Inlet and Drain Connections The h...

Page 25: ...bedded in the software determines the frequency that the bottle should be drained Example Optimised Lifetime with High Water Conductivity Supply As liquid water is boiled off into steam mineral deposits are left in solution increasing the conductivity of the water To counter this the intelligent software increases the frequency of drain meaning that the replenishing supply water keeps the concentr...

Page 26: ...accessible and adjustable via the microprocessor display keypad unit main features shall include not less than Supply water conductivity µS cm Actual steam output kg h Required steam output kg h Actual current rating A Required current rating A Status mode Start Up Running Filling Draining Water Conductivity Cylinder Type Three different cylinders shall be available which correspond to the supply ...

Page 27: ... drawn from when both power supplies are active Switch position status indicates to the end user which position the switch is currently in i e A or B and is shown via the unit s display When the dual power supply is fitted the UltraCap UPS is fitted as standard Ultracap UPS The Ultracap module is an external backup device for the controller The module guarantees temporary power to the controller i...

Page 28: ... Constant Pressure Control Temperature Control Temperature Humidity Control Supply Air Temp Control NTC Water Temperature Sensor Probe Filter Change Switch BMS and SNMP Compatibility Drip Tray Level Detection Fire Detection Smoke Detection Water Detection Standard Features Optional Features Feature Not Available Display for illustration only SmartCool 6 200kW Precision Air Conditioning 28 Introduc...

Page 29: ...r information and control Display Keypad The 4 3 touchscreen Vu display provides important unit status and allows page navigation with a swipe The default screen shows the unit status and room condition C RH Further screens offer adjustment to parameters fine tuning of setpoints via a rotating control wheel and scrollable data tables Trends of system information can be analysed and managed via the...

Page 30: ...ttings by local operator for information and control Display Keypad The display keypad features a simple array of keys to navigate through the in built menus With an 8 x 22 character 132 x 64 pixel screen size back lit in white for improved contrast the larger screen shall provide for user friendly viewing and easy status recognition by displaying a combination of text and icons The default screen...

Page 31: ...and Run Standby control This also allows the connection of computers printers and modems on the same communications ring For further details please contact Airedale Controls Run Standby Operation The controller shall enable units to operate in run standby mode with up to 8 units networked together without the need for additional hardware or controllers Standby units shall be configured to start wh...

Page 32: ...ad display The standard display keypad shall visually display operating alarms however as an optional extra a display keypad with audible alarms is available Supply Air Temperature Control Modulation of unit capacity to ensure that user defined supply air set points shall be maintained and or a high low return air temperature alarm During peak demand the standby units shall temperature assist Duty...

Page 33: ...sensor shall be be located under the false floor with the 6mm flamtronix tubing routed back into the control panel of the unit the tubing must not be obstructed damaged to ensure accurate pressure control The contant pressure system shall be commissioned by Airedale following routing of tubing from the pressure diffuser and the unit A maximum of 8m s air velocity is allowed at the diffuser so cons...

Page 34: ... the floor stand shall be specified at order Discharge Air Configuration Standard configuration shall be downflow draw through design Straight and L shaped Ceiling Duct Extension Straight and L shaped duct extensions up to a height of 1350mm shall be constructed and finished to match the unit For extensions greater than 1350mm please contact Airedale Height shall be specified at order Sterling Boa...

Page 35: ...l switch shall be incorporated into the unit drain tray for indication of a high water alarm Hot Water Full function units SN SR SD type units The cold water condensate pump has 10mm quarter turn plastic barbed connection The hot water condensate pump uses 10mm 3 8 copper tube when connecting to the discharge stub of the pump 2 4 6 8 10 12 0 5 0 9 0 7 0 13 0 15 0 11 0 Head m Flow Rate l min 0 1 2 ...

Page 36: ...890 SR12D mm 1242 1980 890 SR15D mm 1521 1980 890 SR18D mm 1800 1980 890 Depth Height Length Detail of the doors and return air ducting centres is available from the general arrangement drawings upon request SmartCool 6 200kW Precision Air Conditioning 36 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_2018 Installation ...

Page 37: ...90 SD31D mm 3100 1980 890 SD35D mm 3500 1980 890 Length Height C Depth Detail of the doors and return air ducting centres is available from the general arrangement drawings upon request Precision Air Conditioning SmartCool 6 200kW 37 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_2018 Installation ...

Page 38: ...ust not be used as they impose a point load on the unit frame which may cause damage and distortion Check the unit is as ordered Discrepancies or transit damage should be reported to Airedale immediately This small footprint unit is relatively tall and heavy Care should be taken during handling and lifting that the unit is well supported and properly balanced Observe airflow and maintenance cleara...

Page 39: ... Forward and 2 Sides All Faces SN06D mm 720 500 380 250 SN09D SR09D mm 720 500 380 250 SN12D SR12D mm 720 500 380 250 SR15D mm 740 550 440 280 SR18D mm 750 590 480 300 1 Shown with optional open floor stand 2 Shaded area indicates minimum service and maintenance requirements The unit must be installed with allowance for carpet tile clearance 3 Dimension C denotes recommended minimum maximum floor ...

Page 40: ...35D mm 750 590 480 300 1 Shown with standard open floor stand 2 Shaded area indicates minimum service and maintenance requirements The unit must be installed with allowance for carpet tile clearance 3 Dimension C denotes recommended minimum maximum floor stand height refer to Airedale for special applications please specify at order Minimum Unit Clearance SD Open and Enclosed Floorstand Option Sma...

Page 41: ...e Circuit M 2 WAY REGULATING BALL VALVE ACTUATOR DRIVEN BI BL DR WTS BINDER POINT BLEED VALVE DRAIN VALVE WATER TEMPERATURE SENSOR 3 WAY REGULATING BALL VALVE ACTUATOR DRIVEN THREADED CONNECTION BSPT MALE M 2 WAY REGULATING BALL VALVE Ensure binder points are installed on both inlet outlet pipes post unit Precision Air Conditioning SmartCool 6 200kW 41 SmartCool 6 200kW Chilled Water Technical Man...

Page 42: ... Pipework External Pipework M 2 WAY REGULATING BALL VALVE ACTUATOR DRIVEN BI BL DR WTS BINDER POINT BLEED VALVE DRAIN VALVE WATER TEMPERATURE SENSOR 3 WAY REGULATING BALL VALVE ACTUATOR DRIVEN THREADED CONNECTION BSPT MALE M 2 WAY REGULATING BALL VALVE Ensure binder points are installed on both inlet outlet pipes post unit SmartCool 6 200kW Precision Air Conditioning 42 SmartCool 6 200kW Chilled W...

Page 43: ...Dual circuit units have two single circuits duplicated BINDER POINT BLEED VALVE DRAIN VALVE WATER TEMPERATURE SENSOR 2 WAY REGULATING BALL VALVE ACTUATOR DRIVEN DIFFERENTIAL PRESSURE TRANDUCER PDZAL DR WTS BL BI M Precision Air Conditioning SmartCool 6 200kW 43 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_2018 Installation ...

Page 44: ... TEE TO CONDENSATE DRAIN J HUMIDIFIER FILL SR Single Circuit VIEW FROM ABOVE FRONT OF UNIT A B E F G J H 129 254 105 963 75 199 343 632 5 811 890 98 216 79 92 80 A DIA 35mm WATER INLET B DIA 35mm WATER OUTLET E POWER CONNECT VIA EXTERNAL CONNECTION BOX F CONTROLS CONNECT VIA CONNECTORS G CONDENSATE DRAIN TEE TO HUMIDIFIER DRAIN IF USED H HUMIDIFIER DRAIN TEE TO CONDENSATE DRAIN J HUMIDIFIER FILL S...

Page 45: ...80 408 556 98 216 75 199 A DIA 42mm CIRCUIT 1 WATER INLET B DIA 42mm CIRCUIT 1 WATER OUTLET C DIA 42mm CIRCUIT 2 WATER INLET D DIA 42mm CIRCUIT 2 WATER OUTLET E POWER CONNECT VIA EXTERNAL CONNECTION BOX F CONTROLS CONNECT VIA CONNECTORS G CONDENSATE DRAIN TEE TO HUMIDIFIER DRAIN IF USED H HUMIDIFIER DRAIN TEE TO CONDENSATE DRAIN J HUMIDIFIER FILL SN SR Electrical Power Connections Precision Air Co...

Page 46: ...BLE AND GLAND POINT WATER INLET CIRCUIT 2 WATER OUTLET CIRCUIT 2 H VARIES CLIENT SPECIFIED FLOOR VOID FLOOR LEVEL FLOOR LEVEL WATER INLET CIRCUIT 1 WATER OUTLET CIRCUIT 1 2ND GLAND POINT FOR DUAL POWER OPTION L 1980 H 115 236 170 170 115 238 368 90 108 POWER CABLE AND GLAND POINT SmartCool 6 200kW Precision Air Conditioning 46 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_201...

Page 47: ...mperature C Ethylene Glycol Volume Freezing Point C 0 0 C 10 4 C 20 9 C 30 15 C 40 23 C ρ ρ ρ ρ ρ 20 998 1013 1030 1045 1060 25 997 1012 1028 1043 1058 30 996 1010 1026 1041 1055 35 994 1008 1024 1039 1053 40 992 1006 1022 1036 1050 45 990 1003 1020 1035 1048 Pressure Drop Correction Factor Px Water Glycol Temperature C Ethylene Glycol Volume 0 10 20 30 40 Px Px Px Px Px 20 0 983 1 0125 1 054 1 09...

Page 48: ...alters the chemical composition of the tape must be avoided and any use thereof voids any warranty expressed or implied 3M Scotch Weld 77 adhesive is strongly recommended to ensure the warranty will be maintained When adhesive is used adhesive with an oily or greasy base MUST be avoided as this will affect the tape s ability to detect moisture When the use of an adhesive is not desirable or practi...

Page 49: ...ination ensures that the connections are made simultaniously Failure to attached the cables this way may cause damage to the controller CAUTION Technical C0C0 Precision Air Conditioning SmartCool 6 200kW 49 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_2018 C000 SN ...

Page 50: ...31 8 23 2 35 4 24 8 32 9 Fan Motor Quantity x Motor Size 4 kW 1 x 0 78 1 x 0 78 1 x 2 5 1 x 2 5 1 x 2 4 1 x 2 4 Speed 25Pa ESP rpm 1954 2590 2120 2474 1985 2361 Speed maximum ESP rpm 2680 2680 2970 2970 2400 2400 Maximum ESP Pa 552 87 1126 618 589 85 Nominal Airflow m s 0 70 0 95 1 20 1 55 1 75 2 10 Connections Water Inlet Outlet mm 22 0 22 0 28 0 28 0 35 0 35 0 Filtration Quantity 6 6 9 9 12 12 E...

Page 51: ...d 100 water Valve Kv M SN06 C000 10 0 0 28 SN09 C000 16 0 0 44 SN12 C000 25 0 0 69 1 SN06D010 C000 SN06D015 C000 2 SN09D020 C000 SN09D025 C000 3 SN12D030 C000 SN12D035 C000 0 20 40 60 80 100 120 140 160 180 0 00 0 50 1 00 1 50 2 00 2 50 3 00 3 50 Pressure Drop kPa Flow Rate l s 1 2 3 Precision Air Conditioning SmartCool 6 200kW 51 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10...

Page 52: ...tions IMPORTANT The sound data quoted is based on the unit having a ducted return air and standard backwards curved EC motors fitted refer to illustration below Case breakout sound data is therefore independent of the discharge air and return air sound data For non ducted return air applications the overall case breakout sound levels may increase due to the return air sound being predominant Withi...

Page 53: ...ir 76 73 72 82 75 67 63 57 40 Return Air 75 73 72 80 74 65 62 56 39 Case Breakout 77 77 77 83 74 67 63 57 43 Sound Pressure 3m 62 62 63 69 60 52 48 43 29 SN12D030 C000 Discharge Air 69 65 72 73 67 60 57 56 37 Return Air 68 65 72 71 66 58 56 55 36 Case Breakout 70 69 78 75 67 60 57 57 40 Sound Pressure 3m 55 55 63 60 52 45 42 42 26 SN12D035 C000 Discharge Air 73 64 74 78 71 64 62 58 44 Return Air 7...

Page 54: ...ction Tape Probe 810 Supply Air Temperature Sensor 811 Supply Air Temperature Sensor 560 Non Critical Alarm N O 561 Non Critical Alarm Common 563 Critical Alarm N O 564 Critical Alarm Common 565 Critical Alarm N C 881 BMS Connection 882 BMS Connection 883 BMS Connection Conn 15 Conn 16 Conn 17 Conn 14 Conn 14 CONN15 PIN 1 CONN14 PIN 1 CONN17 CONN16 PIN 1 PIN 1 Pin No Wire 1 502 2 583 or 584 3 2 4 ...

Page 55: ... 15 15 18 18 Electric Heating Rating kW 7 5 7 5 15 15 15 15 22 5 22 5 Stage of Reheat 1 1 2 2 2 2 3 3 Humidifier Capacity kg hr 8 8 8 8 15 15 15 15 Electrical Unit Data Full Function 5 Nominal Run Amps A 26 4 26 4 35 8 35 8 50 6 50 6 58 7 58 7 Recommended Mains Fuse Size A 32 32 50 50 63 63 80 80 Unit Data Cooling Only Nominal Run Amps A 4 4 5 43 5 43 7 7 9 86 9 86 Recommended Mains Fuse Size A 10...

Page 56: ... P Pressure Drop in kPa Q Water Flow Rate in l s and M 36 Kv Fluid 100 water 4 SR09D030 C000 SR09D040 C000 5 SR12D045 C000 SR09D055 C000 6 SR15D065 C000 SR15D075 C000 7 SR18D080 C000 SR18D095 C000 0 20 40 60 80 100 120 140 160 180 0 00 1 00 2 00 3 00 4 00 5 00 6 00 7 00 8 00 Pressure Drop kPa Flow Rate l s 4 5 6 7 SmartCool 6 200kW Precision Air Conditioning 56 SmartCool 6 200kW Chilled Water Tech...

Page 57: ...8 76 77 78 76 70 61 31 Return Air 78 78 76 76 77 74 69 60 30 Case Breakout 80 81 82 79 77 76 69 61 34 Sound Pressure 3m 65 67 67 65 63 61 55 47 19 SR15D075 C000 Discharge Air 82 80 79 80 80 78 72 63 34 Return Air 81 80 79 78 79 77 72 62 33 Case Breakout 82 84 84 82 80 78 72 64 37 Sound Pressure 3m 68 69 70 67 65 64 57 49 22 SR18D080 C000 Discharge Air 78 74 77 76 75 74 68 62 38 Return Air 76 74 77...

Page 58: ...lood Detection Tape Probe 610 Flood Detection Tape Probe 810 Supply Air Temperature Sensor 811 Supply Air Temperature Sensor 560 Non Critical Alarm N O 561 Non Critical Alarm Common 563 Critical Alarm N O 564 Critical Alarm Common 565 Critical Alarm N C 881 BMS Connection 882 BMS Connection 883 BMS Connection Pin No Wire 1 502 2 583 or 584 3 2 4 N or 3 Pin No Wire 1 502 2 522 3 560 4 561 5 563 6 5...

Page 59: ... 12 12 15 15 18 18 Electric Heating Rating kW 7 5 7 5 7 5 7 5 15 0 15 0 15 15 Stage of Reheat 1 1 1 1 2 2 2 2 Humidifier Capacity kg hr 3 3 3 3 8 8 8 8 Electrical Unit Data Full Function 5 Nominal Run Amps A 21 0 21 0 19 63 19 63 43 43 40 3 40 3 Recommended Mains Fuse Size A 25 25 25 25 50 50 50 50 Unit Data Cooling Only Nominal Run Amps A 4 4 5 43 5 43 7 7 9 86 9 86 Recommended Mains Fuse Size A ...

Page 60: ...sure Drop in kPa Q Water Flow Rate in l s and M 36 Kv Fluid 100 water 8 SR09D020 C0C0 SR09D025 C0C0 9 SR12D030 C0C0 SR12D035 C0C0 10 SR15D040 C0C0 SR15D045 C0C0 11 SR18D050 C0C0 SR 18D060 C0C0 0 0 10 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 0 0 00 1 00 2 00 3 00 4 00 5 00 6 00 Pressure Drop kPa Flow Rate l s 8 9 10 11 SmartCool 6 200kW Precision Air Conditioning 60 SmartCool 6 200kW Chilled Water T...

Page 61: ...8 76 78 78 76 70 61 31 Return Air 78 78 76 76 77 74 69 60 30 Case Breakout 80 82 82 79 77 76 70 61 34 Sound Pressure 3m 65 67 67 65 63 61 55 47 20 SR15D045 C0C0 Discharge Air 82 80 79 80 80 78 72 63 34 Return Air 81 80 79 78 79 77 72 63 33 Case Breakout 82 84 84 82 80 78 72 64 37 Sound Pressure 3m 68 70 70 67 65 64 58 49 22 SR18D050 C0C0 Discharge Air 78 74 77 76 76 74 68 62 38 Return Air 76 74 77...

Page 62: ...lood Detection Tape Probe 610 Flood Detection Tape Probe 810 Supply Air Temperature Sensor 811 Supply Air Temperature Sensor 560 Non Critical Alarm N O 561 Non Critical Alarm Common 563 Critical Alarm N O 564 Critical Alarm Common 565 Critical Alarm N C 881 BMS Connection 882 BMS Connection 883 BMS Connection Pin No Wire 1 502 2 583 or 584 3 2 4 N or 3 Pin No Wire 1 502 2 522 3 560 4 561 5 563 6 5...

Page 63: ...5 0 22 5 30 0 30 0 Stage of Reheat 2 2 3 4 4 Humidifier Capacity kg hr 8 30 30 30 30 Rating kW 6 0 22 5 22 5 22 5 22 5 Full Load Amps A 8 7 32 6 32 6 32 6 32 6 Electrical Unit Data Full Function 5 Nominal Run Amps A 40 3 64 2 79 4 94 7 94 7 Recommended Mains Fuse Size A 50 80 100 125 125 Unit Data Cooling Only Nominal Run Amps A 9 9 9 9 14 3 18 7 18 7 Recommended Mains Fuse Size A 16 16 20 25 25 M...

Page 64: ...v Bypass SD18D110 CH00 40 40 SD22D140 CH00 63 40 SD25D175 CH00 63 40 1 SD18D110 CH00 0 2 SD22D140 CH00 0 3 SD25D175 CH00 0 0 0 20 0 40 0 60 0 80 0 100 0 120 0 140 0 160 0 180 0 200 0 0 00 2 00 4 00 6 00 8 00 10 00 12 00 Pressure Drop kPa Flow Rate l s SD18D110 CH00 0 SD22D140 CH00 0 SD25D175 CH00 0 1 and 2 3 SmartCool 6 200kW Precision Air Conditioning 64 SmartCool 6 200kW Chilled Water Technical ...

Page 65: ...uid 100 water Kv Cooling Kv Bypass SD31D215 CH00 63 63 SD35D255 CH00 63 63 0 0 20 0 40 0 60 0 80 0 100 0 120 0 140 0 160 0 180 0 0 00 2 00 4 00 6 00 8 00 10 00 12 00 14 00 16 00 Pressure Drop kPa Flow Rate l s SD31D215 CH00 0 SD35D225 CH00 0 4 5 4 SD31D215 CH00 0 5 SD35D255 CH00 0 Precision Air Conditioning SmartCool 6 200kW 65 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_20...

Page 66: ...Sound Pressure 3m 50 57 62 52 46 39 36 32 23 SD22D140 CH00 Discharge Air 66 69 80 67 59 53 51 43 36 Return Air 61 67 74 62 55 50 51 43 35 Case Breakout 67 75 79 70 63 57 54 50 41 Sound Pressure 3m 53 60 65 55 49 43 39 35 27 SD25D175 CH00 Discharge Air 66 69 80 67 59 53 51 43 35 Return Air 61 67 74 62 56 50 50 43 35 Case Breakout 67 75 79 70 63 57 54 50 41 Sound Pressure 3m 53 60 65 55 49 43 39 35 ...

Page 67: ...ondensate Pump Supply 230V 534 Condensate Pump High Level Alarm 535 Condensate Pump High Level Alarm 609 Flood Detection Tape Probe 610 Flood Detection Tape Probe 810 Supply Air Temperature Sensor 811 Supply Air Temperature Sensor 560 Non Critical Alarm N O 561 Non Critical Alarm Common 563 Critical Alarm N O 564 Critical Alarm Common 565 Critical Alarm N C 881 BMS Connection 882 BMS Connection 88...

Page 68: ...ifier Capacity kg hr 8 30 30 30 30 Rating kW 6 0 22 5 22 5 22 5 22 5 Full Load Amps A 8 7 32 6 32 6 32 6 32 6 Electrical Unit Data Full Function 5 Nominal Run Amps A 40 3 64 2 79 4 94 7 94 7 Recommended Mains Fuse Size A 50 80 100 125 125 Unit Data Cooling Only Nominal Run Amps A 9 9 9 9 14 3 18 7 18 7 Recommended Mains Fuse Size A 16 16 20 25 25 Max Mains Incoming Cable Size mm 35 70 70 70 70 Fan...

Page 69: ...15 CL00 40 40 SD22D145 CL00 63 40 SD25D180 CL00 63 40 0 0 20 0 40 0 60 0 80 0 100 0 120 0 140 0 160 0 180 0 200 0 220 0 240 0 260 0 280 0 300 0 0 00 2 00 4 00 6 00 8 00 10 00 12 00 Pressure Drop kPa Flow Rate l s SD18D115 CL00 0 SD22D145 CL00 0 SD25D180 CL00 0 2 1 and 3 1 SD18D115 CL00 0 2 SD22D145 CL00 0 3 SD25D180 CL00 0 Precision Air Conditioning SmartCool 6 200kW 69 SmartCool 6 200kW Chilled W...

Page 70: ...Kv Fluid 100 water Kv Cooling Kv Bypass SD31D235 CL00 63 63 SD35D270 CL00 63 63 4 SD31D235 CL00 0 5 SD35D270 CL00 0 0 00 50 00 100 00 150 00 200 00 250 00 300 00 0 00 2 00 4 00 6 00 8 00 10 00 12 00 14 00 16 00 Pressure Drop kPa Flow Rate l s SD31D235 CL00 0 SD35D270 CL00 0 5 4 SmartCool 6 200kW Precision Air Conditioning 70 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_2018 ...

Page 71: ...6 50 50 43 35 Case Breakout 67 75 79 70 63 57 54 50 41 Sound Pressure 3m 53 60 65 55 49 43 39 35 26 SD31D235 CL00 Discharge Air 67 70 81 68 60 54 51 44 36 Return Air 62 68 75 63 56 50 51 43 36 Case Breakout 68 75 80 70 64 58 54 50 42 Sound Pressure 3m 53 61 66 56 49 43 40 36 27 SD35D270 CL00 Discharge Air 70 73 84 70 62 57 54 47 39 Return Air 65 71 78 66 59 54 54 47 39 Case Breakout 71 78 83 73 67...

Page 72: ... 3 Condensate Pump Supply 230V 534 Condensate Pump High Level Alarm 535 Condensate Pump High Level Alarm 609 Flood Detection Tape Probe 610 Flood Detection Tape Probe 810 Supply Air Temperature Sensor 811 Supply Air Temperature Sensor 560 Non Critical Alarm N O 561 Non Critical Alarm Common 563 Critical Alarm N O 564 Critical Alarm Common 565 Critical Alarm N C 881 BMS Connection 882 BMS Connectio...

Page 73: ... 22 5 30 0 30 0 Stage of Reheat 2 2 3 4 4 Humidifier Capacity kg hr 8 30 30 30 30 Rating kW 6 0 22 5 22 5 22 5 22 5 Full Load Amps A 8 7 32 6 32 6 32 6 32 6 Electrical Unit Data Full Function 5 Nominal Run Amps A 40 3 64 2 79 4 94 7 94 7 Recommended Mains Fuse Size A 50 80 100 125 125 Unit Data Cooling Only Nominal Run Amps A 9 9 9 9 14 3 18 7 18 7 Recommended Mains Fuse Size A 16 16 20 25 25 Max ...

Page 74: ...ng Kv Bypass SD18D085 CHCH 40 40 SD22D105 CHCH 63 40 SD25D135 CHCH 63 40 0 0 20 0 40 0 60 0 80 0 100 0 120 0 140 0 0 00 1 00 2 00 3 00 4 00 5 00 6 00 7 00 8 00 9 00 Pressure Drop kPa Flow Rate l s SD18D085 CHCH 0 SD22D105 CHCH 0 SD25D135 CHCH 0 1 2 3 1 SD18D085 CHCH 0 2 SD22D105 CHCH 0 3 SD25D135 CHCH 0 SmartCool 6 200kW Precision Air Conditioning 74 SmartCool 6 200kW Chilled Water Technical Manua...

Page 75: ...6 Kv Fluid 100 water Kv Cooling Kv Bypass SD31D165 CHCH 63 63 SD35D195 CHCH 63 63 0 00 20 00 40 00 60 00 80 00 100 00 120 00 0 00 2 00 4 00 6 00 8 00 10 00 12 00 14 00 Pressure Drop kPa Flow Rate l s SD31D165 CHCH 0 SD35D195 CHCH 0 4 and 5 4 SD31D165 CHCH 0 5 SD35D195 CHCH 0 Precision Air Conditioning SmartCool 6 200kW 75 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_2018 Tec...

Page 76: ...63 57 54 50 41 Sound Pressure 3m 53 60 65 55 48 42 39 35 26 SD25D135 CHCH Discharge Air 65 68 79 66 58 52 49 42 34 Return Air 60 66 73 61 54 49 49 41 34 Case Breakout 66 73 78 68 62 56 52 48 40 Sound Pressure 3m 52 59 64 54 48 41 38 34 25 SD31D165 CHCH Discharge Air 66 69 80 67 59 53 50 43 35 Return Air 61 67 74 62 55 50 50 42 35 Case Breakout 67 74 79 69 63 57 53 49 41 Sound Pressure 3m 53 60 65 ...

Page 77: ...ondensate Pump Supply 230V 534 Condensate Pump High Level Alarm 535 Condensate Pump High Level Alarm 609 Flood Detection Tape Probe 610 Flood Detection Tape Probe 810 Supply Air Temperature Sensor 811 Supply Air Temperature Sensor 560 Non Critical Alarm N O 561 Non Critical Alarm Common 563 Critical Alarm N O 564 Critical Alarm Common 565 Critical Alarm N C 881 BMS Connection 882 BMS Connection 88...

Page 78: ...fier Capacity kg hr 8 30 30 30 30 Rating kW 6 0 22 5 22 5 22 5 22 5 Full Load Amps A 8 7 32 6 32 6 32 6 32 6 Electrical Unit Data Full Function 5 Nominal Run Amps A 40 3 64 2 79 4 94 7 94 7 Recommended Mains Fuse Size A 50 80 100 125 125 Unit Data Cooling Only Nominal Run Amps A 9 9 9 9 14 3 18 7 18 7 Recommended Mains Fuse Size A 16 16 20 25 25 Max Mains Incoming Cable Size mm 35 70 70 70 70 Fan ...

Page 79: ...ling Kv Bypass SD18D090 CLCL 40 40 SD22D120 CLCL 40 40 SD25D140 CLCL 63 63 1 SD18D090 CLCL 0 2 SD22D120 CLCL 0 3 SD25D140 CLCL 0 0 00 50 00 100 00 150 00 200 00 250 00 0 00 1 00 2 00 3 00 4 00 5 00 6 00 7 00 8 00 9 00 Pressure Drop kPa Flow Rate l s SD18D090 CLCL 0 SD22D120 CLCL 0 SD25D140 CLCL 0 2 1 3 Precision Air Conditioning SmartCool 6 200kW 79 SmartCool 6 200kW Chilled Water Technical Manual...

Page 80: ... M 36 Kv Fluid 100 water Kv Cooling Kv Bypass SD31D190 CLCL 63 63 SD35D225 CLCL 63 63 4 SD31D190 CLCL 0 5 SD35D225 CLCL 0 0 00 50 00 100 00 150 00 200 00 250 00 0 00 2 00 4 00 6 00 8 00 10 00 12 00 14 00 Pressure Drop kPa Flow Rate l s SD31D190 CLCL 0 SD35D225 CLCL 0 5 4 SmartCool 6 200kW Precision Air Conditioning 80 SmartCool 6 200kW Chilled Water Technical Manual 7674716 V1 10 0_10_2018 Technic...

Page 81: ...4 49 49 41 34 Case Breakout 66 73 78 68 62 56 52 48 40 Sound Pressure 3m 52 59 64 54 48 41 38 34 25 SD31D190 CLCL Discharge Air 66 69 80 67 59 53 50 43 35 Return Air 61 67 74 62 55 50 50 42 35 Case Breakout 67 74 79 69 63 57 53 49 41 Sound Pressure 3m 53 60 65 55 49 42 39 35 26 SD35D225 CLCL Discharge Air 69 72 83 69 61 56 53 46 38 Return Air 64 70 77 65 58 52 53 46 38 Case Breakout 70 77 82 72 66...

Page 82: ...ondensate Pump Supply 230V 534 Condensate Pump High Level Alarm 535 Condensate Pump High Level Alarm 609 Flood Detection Tape Probe 610 Flood Detection Tape Probe 810 Supply Air Temperature Sensor 811 Supply Air Temperature Sensor 560 Non Critical Alarm N O 561 Non Critical Alarm Common 563 Critical Alarm N O 564 Critical Alarm Common 565 Critical Alarm N C 881 BMS Connection 882 BMS Connection 88...

Page 83: ...e Conditions of Sale Warranty and Warranty Procedure available upon request Procedure When a component part fails a replacement part should be obtained through our Spares department If the part is considered to be under warranty the following details are required to process this requirement Full description of part required including Airedale s part number if known The original equipment serial nu...

Page 84: ...Airedale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY Tel 44 0 113 2391000 Fax 44 0 113 2507219 E mail enquiries airedale com Web www airedale com TM_SMARTCOOL_6_200kW_7674716_1 10 0_10_2018 ...