Technical Data SR C0C0 Units
Mechanical and Electrical Data
Mechanical
SR09D020-C0C0
SR09D025-C0C0
SR12D030-C0C0
SR12D035-C0C0
SR15D040-C0C0
SR15D045-C0C0
SR18D050-C0C0
SR18D060-C0C0
Capacity
Nom Cooling (Gross)
(1) kW
25.3
30.5
36.5
43.1
50.5
54.7
61.0
70.1
Fan Power Input (Fan Gain)
(2) kW
0.81
1.47
1.26
2.36
2.15
2.82
2.25
3.86
Dimensions
- D(600) x H(1980)
Width
mm
963
1242
1521
1800
Weight - Machine
(3)
kg
320
320
380
380
464
464
540
540
- Operating
kg
351
351
424
424
518
518
609
609
Cooling Coil
Water volume
l
16
16
22
22
27
27
35
35
Water flow rate
l/s
1.2
1.45
1.74
2.05
2.4
2.6
2.9
3.34
Pressure drop
kPa
18.7
26.6
21.5
29.0
30.5
35.3
26.2
33.1
Fan & Motor
Quantity x Motor Size
(4) kW 1 x 1.96 1 x 1.96 1 x 2.9 1 x 2.9 2 x 1.96 2 x 1.96 2 x 2.9 2 x 2.9
Speed @25Pa ESP
rpm 1178
1444
1316
1595
1281
1404
1231
1460
Speed @maximum ESP
rpm 1560
1560
1660
1660
1560
1560
1660
1660
Maximum ESP
Pa
459
197
504
124
349
221
551
318
Nominal Airflow
m³/s 1.85
2.30
2.70
3.30
3.80
4.20
4.60
5.50
Connections
Water Inlet / Outlet
mm
35.0
35.0
42.0
42.0
42.0
42.0
54
54
Filtration
Quantity
9
9
12
12
15
15
18
18
Electric Heating
Rating
kW
7.5
7.5
7.5
7.5
15.0
15.0
15
15
Stage of Reheat
1
1
1
1
2
2
2
2
Humidifier
Capacity
kg/hr
3
3
3
3
8
8
8
8
Electrical
Unit Data - Full Function
(5)
Nominal Run Amps
A
21.0
21.0
19.63
19.63
43
43
40.3
40.3
Recommended Mains Fuse Size
A
25
25
25
25
50
50
50
50
Unit Data - Cooling Only
Nominal Run Amps
A
4
4
5.43
5.43
7
7
9.86
9.86
Recommended Mains Fuse Size
A
10
10
10
10
10
10
16
16
Max Mains Incoming Cable Size
mm²
16
16
16
16
35
35
35
35
Fan and motor
Full Load Amps
A
3
3
4.5
4.5
3
3
4.5
4.5
Electric heat
Current Per Phase
A
10.9
10.9
10.9
10.9
21.7
21.7
21.7
21.7
Humidifier
Rating
kW
2.25
2.25
2.25
2.25
6
6
6
6
Full Load Amps
A
3.3
3.3
3.3
3.3
8.7
8.7
8.7
8.7
(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, these values may change with different ESP.
(3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.
(5) Values given for full function units with standard selections for heating, humidification, supply air fans.
Other fans are available, please contact Airedale.
Precision Air Conditioning
SmartCool™ 6 - 200kW
59
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018