background image

 

INST APD0344 A090630

 

INST APD0344 A090630

LOCATiON PReReqUiSiTeS

This  guideline  contains  general  information  on 

duct smoke detector installation, but does not 
preclude the NFPA and/or ICC documents listed 

on page 1.  Air Products and Controls assumes 
no  responsibility  for  improperly  installed 

duct  detectors.  To  determine  the  correct 

installation position for an RT-3000 Series duct 
smoke  detector,  the  following  factors  must  be 

considered:

1)  A uniform non-turbulent (laminar) airflow 
between  100  ft/min.  to  4,000  ft/min.  must 
be  present  in  the  HVAC  duct.  To  determine 
duct  velocities,  examine  the  engineering 
specifications that define the expected velocities 
or use an Alnor model 6000AP velocity meter 

(or equivalent).
2)  To  minimize  the  impact  of  air  turbulence 

and stratification on performance, a duct smoke 
detector  should  be  located  as  far  as  possible 
downstream from any obstruction (i.e. deflector 

plates,  elbows,  dampers,  etc.).  In  all  situations, 
confirmation of velocity and pressure differential 
within specifications is required. 
The  pressure  differential  between  the  input 
sampling (high pressure) tube and exhaust (low 
pressure)  tube  for  the  RT-3000  Series  smoke 
duct  detector  should  be  greater  than  0.01 
inches of water and less than 1.8 inches of water. 
See page 4 for detailed information on pressure 

differential gauges.
3)  Identify a code compliant location (supply 
or  return  side,  or  both)  for  the  installation  of 
the  duct  unit  that  will  permit  easy  access  for 

viewing and serviceability.
4)  When installing on the return side, install 

duct units prior to the air being exhausted from 
the building or diluted with outside “fresh” air.
5)  When  installing  duct  smoke  units 

downstream  of  filters,  fires  occurring  in  the 
filters will be detected, but if the filters become 
blocked,  insufficient  air  flow  through  the  duct 
unit  will  prevent  the  correct  operation  of  the 
duct detector. Duct units installed in the supply 
air side may monitor upstream equipment and/
or filters.

6)  Where  possible,  install  duct  detectors 

upstream of air humidifiers and downstream of 
dehumidifiers.
7)  To prevent false alarms, the duct detector 
should  not  be  mounted  in  areas  of  extreme 

high or low temperatures, in areas where high 
humidity exists, or in areas where the duct may 
contain gases or excessive dust.

SAMPLiNG TUBe ASSeMBLy

The  RT-3000  Series  duct  smoke  detectors 
employ a specially notched sampling tube, which 
must  be  ordered  separately  in  one  of  four 

standard lengths.

 

STN-1.0

    For duct widths of 6" to 1.0'

 

STN-2.5

    For duct widths of 1.0' to 3.0'

 

STN-5.0

    For duct widths of 3.0' to 5.0'

 

STN-10.0

  For duct widths of 5.0' to 10.0'

Standard  sampling  tubes  are  steel  tubes  with 

air  intake  holes  punched  the  entire  length  of 
the tube. These tubes can be cut to length and 
must  span  at  least  80%  the  width  of  the  duct. 
Sampling tubes over 3.0’ must be supported on 

the opposite side of the duct. For custom duct 
widths, always use the next longest standard size 
and cut down to the exact requirement. 

To ensure the correct operation of the exhaust 
tube, the red end cap (red stopper in installation 

kit) must be inserted in the end of the air intake 
sampling tube. 

NO-TOOLS

 TUBe iNSTALLATiON

The  RT-3000  Series  duct  smoke  detector 
provides  a  unique,  patented  mechanism  for 
installation and/or removal of the sampling and 

exhaust tubes from either the front or rear of 
the detector housing.

Once the airflow direction has been determined, 

insert the inlet and exhaust tubes into the duct 
smoke detector.  If the cover is in place, the tubes 
may be inserted into the back of the detector 
via the key-slots provided.  Simply push the tube 

into place against the spring loaded retainer, and 
turn to the correct position, allowing the key to 

MeCHANiCAL iNSTALLATiON

“lock” the tube in the desired orientation. 

For front side installation, simply rotate the tube 
retainer  so  that  the  tube  may  be  inserted  and 

oriented  properly.    Once  the  tube  is  installed, 
rotate  the  retainer  back  into  place  to  lock 
down  the  tube.  Ensure  air  intake  sampling  tube 

is positioned so that the inlet holes are directly 
facing  the  airflow  (the  air  sampling  holes  are 

aligned with the notch in the tube).

DUCT PRePARATiON

Remove mounting template from the installation 

kit.    Remove  paper  backing  from  the  mounting 
template  and  affix  it  to  the  duct  at  the  desired 

location.  Using the template as a guide, drill (2) mounting holes, 3/32" (2.5mm) for the #12 X ½" 
sheet metal screws packaged in the installation kit.  Drill or punch (2) 1¼" (32mm) holes for inlet 
sampling and exhaust tubes, using the template as a guide.  Clean all holes.

MOUNTiNG

To maintain the Type 4X watertight, corrosion resistant properties of this duct smoke detector, and 
in accordance with NFPA 70 / the National Electric Code, Listed watertight (outdoor) conduit and 
fittings must be used.  Preferably, mount the product with the conduit holes facing downwards. If 

vertical mounting is required based on the application, simply orient the sampling tube so it is on the 
upstream side of the exhaust tube.

After securing the sampling and exhaust tubes to the duct smoke unit, (or initially placing the tubes 

through  the  1¼"  holes  drilled  or  punched  in  the  HVAC  duct  to  accept  the  inlet  sampling  and 
exhaust tubes and then attaching them to the duct unit), hold the duct unit assembly in position and 
use (2) # 12 X ½" sheet metal screws (packaged in the installation kit) to secure the duct smoke 

detector to the HVAC duct sheet metal.

AiR SAMPLiNG veRiFiCATiON

To ensure correct operation of the duct unit use a Magnehelic differential pressure gauge,  Dwyer 
2000 or 4000 Series (or equivalent) to determine the differential pressure between the inlet (high 
side)  and  exhaust  (low  side)  tubes.   The  differential  pressure  between  the  two  tubes  should  be 

greater than 0.01 inches of water and less than 1.8 inches of water.
This  duct  smoke  detector  is  shipped  with  a  velocity  adapter  insert,  either  factory  installed  

(RT-3000-P), or found in the installation kit (RT-3000-N).  When installed, this adapter will allow 
the duct detector to operate at extremely low air velocities.  To install the adapter, simply insert it 
into the slots provided inside the detector housing so that the adapter fits snugly over the smoke 
detector head.  Unless your system is consistently operating in the slower velocity range (where 

the adapter is specifically required, RT-3000-N), we recommend that the adapter not be inserted.  
If you experience false alarms at higher velocities with the adapter in place, the adapter should be 
removed.  Please use the following chart for guidance on when the velocity adapter should be used.  
For reference, the speeds indicated are intended to represent the velocity of air within the duct 

under normal operational conditions.

100 ft/min

300 ft/min

500 ft/min

1,000 ft/min 2,000 ft/min

3.000 ft/min

4,000 ft/min

RT-3000-N

UL Listed 

without

 insert installed (500-4,000 ft/min)

UL Listed 

with

 insert installed (100-4,000 ft/min)

RT-3000-P

UL Listed 

without

 insert installed (500-4,000 ft/min)

UL Listed 

with

 insert installed (100-4,000 ft/min)

INLET TUBE
HOLES FACE
AIR FLOW

DUCT WIDTH

AIR FLOW DIRECTION

INSERT RED STOPPER 
THIS END OF INLET TUBE

EXHAUST TUBE INSTALLED 
DOWNSTREAM OF AIRFLOW
DO NOT INSERT RED STOPPER

NOTE: Mountings shown 
are typical.   Detectors can 
be installed side, bottom 
or top of duct as long as 
proper tube operation and 
flow/pressure performance 
is maintained

Tube Support Hole only for Ducts Greater than 3 Feet Wide

Summary of Contents for RT-3000-N

Page 1: ...t Any example applications shown are subject to the most current enforced local national codes standards approvals certifications and or the authority having jurisdic tion All of these resources as well as the specific manufacturer of any shown or mentioned related equipment should be consulted prior to any implementation For further information or assistance concerning this product contact Air Pr...

Page 2: ...d into the HVAC duct Air flowing through the duct is forced into the air intake inlet tube via the air intake holes facing the airflow and passes over the detector head The air will be drawn out via the exhaust tube back into the HVAC duct A 7 exhaust tube is provided in the installation kit When the concentration of smoke particles suspended in the air stream reach the alarm threshold of the dete...

Page 3: ...be into place against the spring loaded retainer and turn to the correct position allowing the key to Mechanical Installation lock the tube in the desired orientation For front side installation simply rotate the tube retainer so that the tube may be inserted and oriented properly Once the tube is installed rotate the retainer back into place to lock down the tube Ensure air intake sampling tube i...

Page 4: ...VER REMOVAL and the unit will be energized The green pilot LED will be illuminated and when pressing the test reset button TEST RESET the red alarm LED will be illuminated This test confirms the correct basic operation of the duct smoke unit excluding the detector head see functional testing Shut down WIRING Example In alarm NC and COM will open interrupting voltage supply to fan NC COM NO ALARM 1...

Page 5: ...nly no tools single point cover assembly when the unit cover is on and the latch is in closed position the RT 3000 is secure and weathertight Patented Maintenance Mode offers 3 minute interval for test and maintenance functions with no extra trouble reports to the system automatically shuts off when cover latch engages Patented tether holds cover to unit and allows hands free reference to wiring d...

Page 6: ...ACU Alarm COM NO COM NO COM NO COM NO facu alarm trouble NO com nc com NO C NC C form A Alarm form b trouble 30vdc 1 0a 30vdc 7 0a SAMPLE CONTROL unit WIRING STYLE d CLASS A IDC Supervised A fault condition will not inhibit an alarm response Trouble contacts are shown in energized condition Under normal operation contacts will be held as shown msr remote accessory wiring ms remote accessory wiring...

Page 7: ...interconnect al1 al2 t r s h common alarm link common link reference common test reset in alarm out alarm out common alarm horn strobe options The following diagrams show interconnection of the RT 3000 Series to other duct smoke detectors manufactured by Air Products and Controls specifically the SL 2000 Series the HS 100 Special Application Series and the SM 501 Series Up to 30 Air Products units...

Page 8: ...afe to perform test maintenance functions without extra reports to the system Determine Correct Operation ofthe Head MagnetTest 1 Place the square short sided end of the magnet provided with the installation kit on the grey section of the housing inline with the area designated Test Magnet Allow at least five seconds for alarm initiation 2 Upon alarm initiation both the detector head LED and redAL...

Page 9: ...combination Strobe Visual and Sounder Audible MSR 50SA X C Module Clear Lens with color Double Gang Cover Plate MSR 50SA X O Module Opaque Lens with color Double Gang Cover Plate MS and SHP SERIES REMOTE ACCESSORIES MS RA Remote Alarm MS RA R Remote Alarm push button Test Reset Switch MS RA P R Remote Alarm Pilot push button Test Reset Switch MS KA R Remote Alarm key operated Test Switch MS KA P R...

Reviews: