background image

 

13 

INST APD0344 A090630

 

14 

INST APD0344 A090630

Test the Trouble Contacts:

With  detector  in  Maintenance  Mode  and 

cover removed/hanging from tether:

1.  Remove  the  detector  head  by  twisting  it 

counter-clockwise.  The  trouble  contacts  will 
change  state,  the  yellow  TROUBLE  LED  will 

change to steady illumination, the green PILOT 
LED will remain flashing.
2. Twist the detector head back into place, the 

trouble  contacts  will  change  back,  the  yellow 
and green LEDs will resume flashing alternately.
Replace the unit’s front cover and fully depress 

the latch lever to verify proper unit and system 
stand-by (or normal) mode.
Upon  proper  replacement  of  the  unit’s  front 
cover, the Maintenance Mode will automatically 
be  cancelled  and  the  RT-3000  will  revert  to 

normal  operational  (stand-by)  status  where 

failure  to  have  the  cover  properly  in  place 
and  latched  will  immediately  cause  a  trouble 

condition. 
Should  additional  testing  also  be  required  for 
simulated fire conditions, smoke bombs placed 

in the duct may not be suited for the particular 
detector  head  (photoelectric  or  ionization) 
selected and installed. Consult the smoke bomb 
data  for  proper  use  and  compatibility  with 
detector type.
The  S65A  ionization  detector  head  (55000-
225)  utilizes  a  radioactive  source  as  its  means 
of detection and will detect smoke particles of 
between .1 and 1 micron in size.
The S65A photoelectric detector head (55000-
328)  operates  on  the  principle  of  light  scatter 

and  will  detect  smoke  particles  of  between  1 
and 10 microns in size.
When  purchasing  smoke  bombs  for  additional 
required  functional  testing,  ensure  smoke 
particle  sizes  comply  with  the  criteria  as 

described above.

NOTE: 

In  situations  that  require  a  duct  smoke 

detector  to  be  held  in  an  alarm  condition  for 
an extended period of time, the magnet test or 
smoke test methods should be used to ensure 

the detector is locked into alarm.

Each  installation  location  must  be  assessed  on 
its own merits.  If the protected area is of a very 

dirty nature then the RT-3000 duct unit(s) will 
have to be checked and cleaned on a quarterly 

basis or when cleaning is required.
As a guideline the smoke detector head should 
be  cleaned  every  six  months  or  as  required.  

The  best  methods  of  cleaning  are  to  vacuum 

the  detector  head  thoroughly  or  to  blow  the 
detector head out using clean, dry compressed 

air.
Do not use chemicals or non-conforming air to 

clean  the  detector  head  housing  as  this  could 
contaminate the detector head and damage the 
casing.
Sampling tubes must be inspected and cleaned 
in accordance with the schedule as determined 
above, to allow the free flow of air through both 
inlet and exhaust tubes.
Consult your local code and AHJ requirements 
for required maintenance schedules.

1.  Press  the  black  MAINTENANCE  button  on 
the front cover to initiate the RT-3000’s 3-minute 

Maintenance Mode.

-  Pressing  the  MAINTENANCE  button  a 

second time within 30 seconds will return the 
detector to stand-by.
-  Other  than  above,  pressing  the 
MAINTENANCE button a second time while 

in Maintenance Mode will reset the 3 minute 
timer.   The  MAINTENANCE  button  can  be 
accessed  directly  from  the  unit’s  control 
board if the cover is not in place.

2.  The  green  PILOT  LED  will  flash  while  in 
Maintenance Mode and the cover latched.
3.  You  are  safe  to  perform  test/maintenance 

functions without extra reports to the system.

DeTeRMiNe CORReCT 

OPeRATiON OF THe HeAD
Magnet Test

1.  Place  the  square  (short-sided) 
end of the magnet provided with 
the  installation  kit  on  the  grey 

section of the housing, inline  with 
the area designated “Test Magnet”.  
Allow  at  least  five  seconds  for 

alarm initiation.  
2. Upon alarm initiation, both the detector head 
LED and red ALARM LEDs will illuminate.  Alarm 

relays  will  change  state  and  the  alarm  related 
remote accessories, if attached, will function. The 
green PILOT LED will continue to flash.
3.  Remove  magnet  and  reset  the  detector  by 
pressing the red  TEST / RESET button on the 
front cover.

Smoke Test

1.  Using  smoke  canister  with  testing  nozzle 
(available  from  Air  Products,  part  number 
TG-2000),  insert  the  test  gas  nozzle  into  the 

patented test port on the unit cover. 
2. Press can against cover to release gas into the 
chamber.

 

CAUTiON

:    DO  NOT  SPRAY  GAS 

FOR  MORE THAN  ½  SECOND.    OVERUSE 

OF  TEST  GAS  FACILITY  MAY  RESULT  IN 

DETECTOR CONTAMINATION.
After 15 - 20 seconds the detector head will go 
into alarm, illuminating both the detector head 
LED and red ALARM LED on the control board. 
Duct  unit  functions  will  operate,  alarm  relays 

will change state, and the alarm related remote 
accessories, if attached, will function.
3. Lift the cover latch and remove the cover.
4. Clear the smoke from the chamber
5. Press the TEST / RESET button on the control 
board
6. The green PILOT and yellow TROUBLE LEDs 
will  flash  alternately,  indicating  the  unit  is  in 

Maintenance  Mode  while  the  cover  is  not  in 
place.
Alternately, if no test gas is available to conduct 

functional testing:

With detector in Maintenance Mode:

1. Lift the cover latch and remove the cover. The 
green  PILOT  and  yellow TROUBLE  LEDs  will 
flash alternately.
2.  Blow  smoke  from  a  cotton  wick  or  punk 
directly at the head to cause an alarm.  
3. The alarm indicators described above should 

illuminate within one minute. Duct unit functions 
will operate, alarm relays will change state, and 

the alarm related remote accessories, if attached, 
will function.
4. Clear the smoke from the chamber
5. Press the TEST / RESET button on the control 

board
6. The green PILOT and yellow TROUBLE LEDs 
will  flash  alternately,  indicating  the  unit  is  in 
Maintenance  Mode  while  the  cover  is  not  in 
place.

MAiNTeNANCe MODe & OPeRATiONAL TeSTiNG

5

5

Mount/install RT-3000 appropriately to ductwork/check differential pressure (see page 4).

5

5

Connect input power and test (see page 5).

5

5

Connect RT-3000 to FACU / AHU / Remote Accessories (see pages 6-10).

5

5

Replace cover on the RT-3000 and flip the cover latch into locked (down) position.

5

5

Ensure RT-3000 is in normal (stand-by) mode and the green PILOT LED is illuminated.

IMPORTANT NOTE!

Cover Removal and Replacement

The RT-3000 cover seats firmly against a 
high-performance rubber gasket. This gasket 
is durable, requires no maintenance and will 
provide the weathertight endurance that 
outdoor enviornments will require over the 
life of the unit.

To avoid accidental damage to the gasket:

When removing the cover from the unit, lift 
the stainless steel cover latch to its upright 
position and pull/lift uniformly on the corner 
tabs for best leverage.  

When replacing the cover, be sure the stainless 
steel cover latch is in its upright position 
before properly seating the cover straight 
onto the base. Then fully depress the cover 
latch. 

FOR TECHNICAL SUPPORT CALL 

TOLL FREE 888-332-2241 OR 

248-332-3900 

either of  

these ends

Summary of Contents for RT-3000-N

Page 1: ...t Any example applications shown are subject to the most current enforced local national codes standards approvals certifications and or the authority having jurisdic tion All of these resources as well as the specific manufacturer of any shown or mentioned related equipment should be consulted prior to any implementation For further information or assistance concerning this product contact Air Pr...

Page 2: ...d into the HVAC duct Air flowing through the duct is forced into the air intake inlet tube via the air intake holes facing the airflow and passes over the detector head The air will be drawn out via the exhaust tube back into the HVAC duct A 7 exhaust tube is provided in the installation kit When the concentration of smoke particles suspended in the air stream reach the alarm threshold of the dete...

Page 3: ...be into place against the spring loaded retainer and turn to the correct position allowing the key to Mechanical Installation lock the tube in the desired orientation For front side installation simply rotate the tube retainer so that the tube may be inserted and oriented properly Once the tube is installed rotate the retainer back into place to lock down the tube Ensure air intake sampling tube i...

Page 4: ...VER REMOVAL and the unit will be energized The green pilot LED will be illuminated and when pressing the test reset button TEST RESET the red alarm LED will be illuminated This test confirms the correct basic operation of the duct smoke unit excluding the detector head see functional testing Shut down WIRING Example In alarm NC and COM will open interrupting voltage supply to fan NC COM NO ALARM 1...

Page 5: ...nly no tools single point cover assembly when the unit cover is on and the latch is in closed position the RT 3000 is secure and weathertight Patented Maintenance Mode offers 3 minute interval for test and maintenance functions with no extra trouble reports to the system automatically shuts off when cover latch engages Patented tether holds cover to unit and allows hands free reference to wiring d...

Page 6: ...ACU Alarm COM NO COM NO COM NO COM NO facu alarm trouble NO com nc com NO C NC C form A Alarm form b trouble 30vdc 1 0a 30vdc 7 0a SAMPLE CONTROL unit WIRING STYLE d CLASS A IDC Supervised A fault condition will not inhibit an alarm response Trouble contacts are shown in energized condition Under normal operation contacts will be held as shown msr remote accessory wiring ms remote accessory wiring...

Page 7: ...interconnect al1 al2 t r s h common alarm link common link reference common test reset in alarm out alarm out common alarm horn strobe options The following diagrams show interconnection of the RT 3000 Series to other duct smoke detectors manufactured by Air Products and Controls specifically the SL 2000 Series the HS 100 Special Application Series and the SM 501 Series Up to 30 Air Products units...

Page 8: ...afe to perform test maintenance functions without extra reports to the system Determine Correct Operation ofthe Head MagnetTest 1 Place the square short sided end of the magnet provided with the installation kit on the grey section of the housing inline with the area designated Test Magnet Allow at least five seconds for alarm initiation 2 Upon alarm initiation both the detector head LED and redAL...

Page 9: ...combination Strobe Visual and Sounder Audible MSR 50SA X C Module Clear Lens with color Double Gang Cover Plate MSR 50SA X O Module Opaque Lens with color Double Gang Cover Plate MS and SHP SERIES REMOTE ACCESSORIES MS RA Remote Alarm MS RA R Remote Alarm push button Test Reset Switch MS RA P R Remote Alarm Pilot push button Test Reset Switch MS KA R Remote Alarm key operated Test Switch MS KA P R...

Reviews: