VELTRON DPT-
plus
Air Monitor Corporation
116-010-91.P65 (09/18/09)
VELTRON DPT-
plus
- IO&M Manual
39
5.13 – DISPLAY CONFIGURATION (con't)
SECTION 5 – OPERATION
8. Press and display will indicate:
LINE 2
PARAMETER
9. Press and display will indicate current parameter selected to display on Line 2 (see Parameter List at the
end of this section for available selections).
10. Use or to scroll to desired parameter. Press and parameter will be stored in memory and display
will indicate as in Step 8.
Note: If user desires not to change the setting and return to Setup menu, press . Unit will remain
programmed as it was originally.
11. If CUSTOM TEXT was selected and pressed in Step 10, proceed to Step 20. For other parameters, continue
with Step 12.
12. Press and display will indicate:
LINE 2
FILTER
Note: This selection is available only if Parameter selected is Temperature or Diff Pressure.
13. Press and display will indicate current Filter setting selected for Line 1 [1 (None), 2 (Minimum), 3, 4, or 5
(Maximum)].
14. Use or to scroll to desired filter setting. Press and filter setting will be stored in memory and
display will indicate as in Step 12.
15. Press and display will indicate:
LINE 2
EXIT
16. Press then and display will indicate:
LINE 3
17. Repeat Steps 8 through 16 for Line 3. The only differences being the change of Line # in the display.
18. After Line 3 has been set, Step 16 will yield a display:
Return to
MAIN MENU
19. Press to return to Main Menu.
20. If Custom Text was selected and pressed in Step 10 (for line 2 or 3), press and display will indicate:
LINE 2
SET CUSTOM TEXT
X