VELTRON DPT-
plus
Air Monitor Corporation
116-010-91.P65 (09/18/09)
VELTRON DPT-
plus
- IO&M Manual
13
SECTION 4 – INSTALLATION
4.5 – POWER/SIGNAL CONNECTIONS (con't)
ALARM 2/AUTO-purge ACKNOWLEDGMENT (Terminals 6(PURGE ACK) and 7(COM))
. This set of unpowered
relay contacts is used for Alarm 2 status or as AUTO-purge acknowledgment. Contacts are normally open and close
at the existence of an alarm condition or the initiation of an AUTO-purge cycle. Review the Factory Information Set-Up
Sheet (provided separately) to determine which (if any) your unit is configured for.
AUTO-purge "START" SIGNAL (Terminals 9(PURGE START INPUT) and 10(GND))
. Customer to provide momentary
(0.5 to 10 seconds unpowered) dry contact as notification of AUTO-purge cycle initiation. Upon receiving this signal,
transmitter hold will be activated.
TEMPERATURE INPUT (Terminals 2(SIG COM), 11(TEMP INPUT), and 12(LOOP POWER)
. Follow the appropriate
Figure below for connecting a temperature input signal.
Figure 4.8
Figure 4.9
ALARM 1 (Terminals13(PURGE POWER) and 14(NEUT))
. This set of relay contacts is used for Alarm 1 status.
Contacts are normally open and only close at the existence of an alarm condition.