SECTION 4 – INSTALLATION
4.5 – POWER/SIGNAL CONNECTIONS
All electrical connections are done at the terminal strips located under the Terminal Side enclosure cover. All wiring
should be routed through one or both 3/4"-14 NPT conduit connections. See Figure 4.4.
Figure 4.4 represents the terminal strip and the connections for input power and the various inputs/outputs available.
Figure 4.4
WIRING
. It is recommended that all wiring be 14 to 22 AWG. 14 AWG is the maximum gauge that the terminal strip
can accommodate. No more than two wires should be connected to any one terminal. 18 AWG is the maximum gauge
wire that can be doubled up in one terminal.
Note: It is recommended that an ON/OFF switch be placed in line of the incoming power to allow turning power on
and off. Power should be OFF when connecting power wiring to the VELTRON DPT-
plus
.
POWER SUPPLY (Terminals LINE and NEUT)
. Power required by the VELTRON DPT-
plus
must be connected to the
two terminals labeled LINE and NEUT. Earth ground should be connected to the terminal lug provided on the upper left
mounting stud (see Figure 4.4). Power supply must be 20-28VAC or 20-32VDC. When powering multiple units from
one power source, polarity must be maintained.