**NOTE**
The numbers in the parenthesis are for 24V and 48V models. In the case of
over voltage, under voltage and thermal protection, the inverter will shut down. When
the inverter is in the OFF position, the inverter doesn't consume battery current.
HI-POT TESTING OF DC to AC Inverter
Most of our AC inverters are Listed by Intertek to conform to UL 458
standards.
One of
the requirements of UL 458 is that all AC inverters pass a High Voltage Dielectric
Withstand Test, commonly called the Hi-Pot Test. The voltage applied to the control is
usually equal to 1,000 volts, plus two times the line voltage rating of the inverter.
Therefore, the standard hi-pot voltage for 115 VAC inverter is 1,250 VAC. For 230 VAC
or dual voltage inverters, the hi-pot voltage is 1,500 VAC. This A
IMS
P
ower inverter is
hi-pot tested before it leaves the factory, with a UL Certified hi-pot tester, set to the
voltages shown above.
(CAN/CSA-C22.2 No. 107.1) and are identified with the cETL Listed Mark.
7