I-36
F-084392_EN • B
P
roduct
I
nstallatIon
General Instructions for the Installation of AIC-approved Chimney Components
î
Make sure to insulate the
fl ue piping in damp rooms
to avoid condensation water
from forming and dripping.
î
Cut the pipes squarely and deburr the
edges. This will ensure correct sealing
and prevent seals from being damaged.
î
To ease the assembly of pipes, use exclu-
sively a mixture of water and soap (1%)
on the extremity of the pipe to be fi t in.
î
Metal fl ue pipes should always be fi t-
ted into the sleeve to the end stop.
i
Installing the pipes - General principles
î
Flue pipe elements or PP air
inlet elements should not be
screwed together.
î
Piping elements should not be bond-
ed together using glue (e.g. silicone) or
foam (e.g. PUR).
î
Plastic fl ue pipes should be
allowed to expand under the
eff ect of heat. Leave about
10 mm between the pipe and
the sleeve end stop.
î
T
he fl ue system should be fi tted with an
inspection opening.
î
Do not exceed the maximum length rec-
ommended for the product when con-
necting the fl ue pipes, or the system pow-
er might decrease.
î
F
or C-type appliances, the fl ue gas exhaust
pipes must at least comply with the cate-
gory T120 H1 W1/2 O30 LI E U when using
parallel piping and T120 H1 W1/2 O00 LI/
LE E U0 when using concentric piping (EN
14471). Metallic piping must comply with
the requirements of standard EN 18
56.
î
The maximum length of duct must be
calculated according to the permissible
diff erence in pressure indicated in the
technical specifi cations.
i
Component
Characteristics
Recommendation
Elbow
Clamped at the sleeve
Straight element
Clamped at the sleeve
î
< 25 cm
î
located before or after fi rst elbow
Clamped with a bracket after elbow
Horizontal > 1m
(with 3° slope)
î
Clamped in pipe center for support
î
Allow free movement of pipe
Vertical > 2m
î
Clamped every 2 meters,
î
Even distribution of clamps
î
Allow free movement of pipe
L>
500 mm
L>
250 mm
L>
25
0 m
m
L> 250 mm
L>
250 mm
or
or
L
>
500 mm
L
>
250 mm
L >
250
mm
L >250 mm
L
>
250 mm
or
or
3°
!
max.
1000 mm
max.
1000 mm
max.
2000 mm