![AIC N 150 WH Installation And Maintenance Manual Download Page 15](http://html1.mh-extra.com/html/aic/n-150-wh/n-150-wh_installation-and-maintenance-manual_2870755015.webp)
G-15
F-084392_EN • B
T
echnical
S
pecificaTionS
Combustion and Gas Data
N 150 WH
(min. - max.)
chimney type(s)
B23, B23P, C13(x), C33(x), C43(x), C53(x), C63(x), C83(x),
C93(x)
flue gas temperature at 80/60°C
°C
60.0 - 74.9
flue gas temperature at 50/30°C
°C
30.0 - 44.5
overheat flue gas temperature
°C
110
max. flue gas pressure
(incl. max wind condition)
Pa
300
Max. chimney length (100/150)
m
16
mass flow rate of flue gases
g/s
57.5
max. condensate volume
kg/h
15.1
CO emissions
mg/kWh
68.7
CO
2
contents (G20) (± 0.1)
%
8.2 - 9.0
CO
2
contents (G31) (LF± 0.2 / HF +
0 )
%
10.0 - 10.7
O
2
contents (G20) (± 0.15)
%
6.3 - 4.8
O
2
contents (G31) (LF± 0.3 / HF +
0
)
%
5,7 - 4,6
NOx level (weighted)
mg/kWh
46.9
NOx class
6
gas type(s)
G20 - G31
gas categories
I2E, II2E3P, II2H3P
gas pressure
G20 (20 mbar)
mbar
17 - 25
G31 (30/37/50 mbar)
mbar
25.0-35.0 / 25.0-45.0 / 42.5-57.5
gas flow rate (G20)*
m
3
/h
1.28 - 14.80
gas flow rate (G31)*
m
3
/h
0.590 - 5.88
*
15°C, 1013.25 mbar, dry gas
-
0.2
-
0.3