I-35
F-084392_EN • B
P
roduct
I
nstallatIon
Safety Instructions for the Chimney Con-
nections
î
Do not install the appliance
into a common fl ue pipe
with other gas or oil appli-
ances. This will cause fl ue
gas spillage or appliance
malfunction. Please contact
your AIC Technical Support
for more information.
î
A condensation outlet connected to the
sewer must be fi tted close to the appli-
ance.
î
Verify installed combustion air and
fl ue gas piping are tight and meet
all provided instructions and appli-
cable codes and standards.
î
Failure to properly support the fl ue
system can cause failure, resulting
in fl ue gases contaminating the
ambient air.
î
The appliance must be equipped
with fl ue system components from
the same manufacturer and be
approved by the appliance manu-
facturer. Ensure that the pipe and
connection diameters all match to
prevent any leaks from occurring.
î
Any gas-fi red appliance generates
carbon monoxide. Failure to install
carbon monoxide detectors with
alarm in the boiler room can result
in serious injury, or death. Refer to
applicable local regulations.
î
A condensate neutralisation sys-
tem needs to be installed accord-
ing to the applicable local regu-
lations and standards. It must be
cleaned and serviced regularly.
î
Make sure to secure the fl ue
piping to a solid structure.
î
Exclusively use the provid-
ed brackets to support the
fl ue system.
î
When assembling the pipes, make
sure not to put any stress on the com-
ponents.
î
Install the horizontal fl ue pipes with a
slight slope of 5 cm per meter (3°) back
towards the appliance.
î
It is mandatory to ventilate the boiler
room. The high or low air vent opening
dimensions depend on the appliance
power and the boiler room size. Refer
to the local regulations in force.
î
If the combustion air inlet is located
in an area likely to cause or contain
contamination, or if products which
could contaminate the air cannot be
removed, the combustion air must be
repiped and terminated at another lo-
cation.
î
If the appliance is used on professional
premises such as hairdresser’s, clean-
ing company, painter’s, etc. where
chloride products, solvents, paints,
dust etc. are likely to contaminate the
air, make sure to install the appliance
in a dedicated boiler room so that the
appliance is supplied with clean com-
bustion air.
î
In the case of parallel fl ue systems,
make sure to maintain suffi cient dis-
tance (at least 40 mm) between the
appliance fl ue piping and combustible
materials, and between the fl ue pipe
and air inlet pipe if the latter is made of
plastic material.