5.1 General notes
5 Assembly
26
Actuators NK and VK, Position Controller ESR-NK
5.1 General notes
Important information!
In order to ensure safe operation of the actuator, the device should have a
rated torque that is 15-20% higher than the torque required for adjusting
the valve (for rated torques see section
“3.4.5 Functional data”
).
−
Inspect the actuator for possible damage (e.g. transport damage) before
installing it.
−
If an anti-corrosive agent was applied for storing the actuator, it must be
removed and replaced by grease before the device is installed.
−
Protect the actuator against strong vibrations such as may occur when the
actuator is dropped.
−
It is forbidden to attach hooks, ropes or the like directly to the actuator.
−
The actuator may not be lifted by the handwheel.
−
Adhere to the installation instructions of the valve manufacturer.
−
The valve must be able to move freely during the installation.
−
Where possible, avoid installing the actuator on an operating valve.
−
If it is necessary to install the actuator in an operating system, all precau-
tions must be taken to ensure that the system is in a safe condition (see
operating instructions of the system and regulations provided by the sys-
tem owner/lessor).
−
If the actuator is attached to a freely accessible valve, the crushing and
pinching hazards from rotating valve parts must be observed.
−
If the actuator is to be attached to a valve not yet installed into a system,
make sure that the valve is secured so that its stability is maintained dur-
ing the installation of the actuator.
−
Check the cable glands and filler plugs (if fitted) for tightness before put-
ting the actuator into service.
−
Do not put the actuator into service unless the limit switches have been
set.
−
Protect the actuator sufficiently against climatic influences – e.g. by fitting
a protective cover.
−
Spark-quenching capacitors within the customer's power supply may in-
fluence the rotational stability of the actuator and cause damages to it.
Summary of Contents for ESR-NK Series
Page 6: ......
Page 28: ......
Page 58: ......
Page 78: ......
Page 86: ......
Page 92: ...11 1 Certificates 11 Appendix 86 Actuators NK and VK Position Controller ESR NK...
Page 93: ...11 Appendix 11 1 Certificates Actuators NK and VK Position Controller ESR NK 87...
Page 94: ...11 1 Certificates 11 Appendix 88 Actuators NK and VK Position Controller ESR NK...
Page 95: ...11 Appendix 11 1 Certificates Actuators NK and VK Position Controller ESR NK 89...
Page 96: ......