53
APPENDIX D. Relative length of straight runs
Table D.1 shows the minimum values of the relative length of straight pipe
sections for the various types of local hydraulic resistances required for in-
stallation of the flow meters.
Table D.1
Type of local hydraulic resistance
Relative length of a straight run, L,
minimum
1
2
10·DN
3·DN
10·DN
10·DN
Regulating valve
30·DN
Regulating valve
3·DN