background image

 

 

4.4.7  Overload 

The demanded power exceeds the normal capacity of the UPS. The alarm occurs when the load is > 
100%. If the load exceeds 150% the UPS will immediately switch to bypass, assuming that the conditions 
for a transfer to bypass are fulfilled.  
If an overload condition between 110-150% persists, the UPS will also switch to bypass operation. 
During an overload the UPS may automatically switch off within a few minutes (load dependent) and 
output power is lost: 

 

if a transfer to bypass is inhibited (see 4.4.6), or  

 

if the bypass function has been disabled (see 4.5), or  

 

if the UPS operates on battery (see 4.4.4). 

To avoid these problems, be absolutely certain that the power demands of the protected equipment 
are within the limits of the UPS. 
 

4.4.8  Replace battery 

Either the batteries are almost chemically worn out or the battery wiring, including the battery fuse, is 
faulty. If the batteries are aged, they must be replaced as soon as possible to ensure full protection for 
your equipment (see 7.4). Perhaps the 'replace battery' alarm occurs after a test which you started 
immediately after installation or after a power failure. In this case the alarm may be incorrect as the 
batteries have been (partly) discharged during transport or storage or during the power failure. Allow 
the UPS to recharge the batteries. See also 4.6. 
 

4.4.9  General alarm 

‘General alarm’ comprises a group of alarms; the buzzer behaviour indicates which alarm is active: 
 
1 / 2 secs: 

General fault 
Overload (see 4.4.7) 

 

 

Overtemperature 
Output out of tolerance 

 
1 / 5 secs: 

Charger failure 
Bypass out of limits (see 4.4.6) 
Replace battery (see 4.4.8) 

 

4.4.10 Shutdown pending 

The UPS monitoring software allows you to switch the UPS into standby mode after a programmable 
delay time. During countdown the ‘operation’ LED will blink 2x per second and the buzzer will beep 
every 5 seconds. 
 

4.4.11 Startup pending 

The UPS monitoring software allows you to start up UPS after a programmable delay time. During this 
delay time the ‘operation’ LED will blink 2x per second. 
 

4.4.12 P-N (Phase-Neutral) reversal indication 

If the P-N reversal indication is enabled, the UPS will indicate whether the voltage between Neutral 
and Earth (Ground) at the UPS input exceeds a certain voltage (i.e. Phase and Neutral at the UPS input 
are reversed in an earthed/grounded Neutral system). In this potentially unsafe situation both LEDs 
‘operation’ and ‘alarm’ will blink fast and the buzzer will sound. Reversing the mains plug will prevent 
this unsafe situation and will cancel the alarm. In case of non-earthed/grounded Neutral system this 
indication should be disabled.  
The default setting of the P-N reversal indication is: 

enabled

. Changing of the setting is described in 

section 4.5. 
 
 

Summary of Contents for 1000 VA VH Series

Page 1: ...User manual VH Series Uninterruptible Power Supply 700 1000 1500 2000 3000 VA...

Page 2: ...ower of the VH Series UPS the rear panel of the UPS shows the model chapter 9 the ratings 3 2 Installation rules The UPS is intended to be used in normal domestic and office situations Protect the UPS...

Page 3: ...ect the DC connector of the internal batteries 5 Assemble the front panel insert the two metal clamps at the rear of the panel into the holes at the right side of the UPS then click the front panel in...

Page 4: ...max rating 10A To connect the loads to the UPS 700 VA 2 outlets 1000 1500 VA 4 outlets 2000 3000 VA 6 outlets 3a Appliance outlet max rating 16A VH Series 3000 VA only To connect a heavy load to the...

Page 5: ...not exceed the VA output rating of the UPS This way you ensure that the UPS is able to supply the required output and prevent that an overload situation will happen 4 Using the output cords provided...

Page 6: ...power fails and the internal batteries supply the required power until either they are depleted or mains power returns 6 LED alarm blinks in case of an alarm 7 LED bar runtime capacity the remaining a...

Page 7: ...this function is activated the UPS will switch off during a mains failure when the load is less than 5 of the maximum load In this way unnecessary discharging of the batteries is avoided The unit will...

Page 8: ...bypass 4 4 3 0 4 0 4 hi o On battery 4 4 4 0 4 0 4 lo Battery low 4 4 5 25 0 4 hi Bypass out of limits 4 4 6 0 4 0 4 lo Overload 4 4 7 0 4 4 hi Replace battery 4 4 8 0 4 0 4 lo General alarm 4 4 9 0 4...

Page 9: ...panel required or if a UPS shutdown command is given by the computer Restart depends on the setting of the auto restart function if set on the UPS will automatically restart when the mains returns if...

Page 10: ...ower failure Allow the UPS to recharge the batteries See also 4 6 4 4 9 General alarm General alarm comprises a group of alarms the buzzer behaviour indicates which alarm is active 1 2 secs General fa...

Page 11: ...the setting of the selected function by pressing switch O The LEDs on the LEDbar runtime capacity shows the setting 4 Store the new settings and leave the setup mode press keypad 1 and keep it presse...

Page 12: ...tery test A deep battery test to be initiated through the UPS software via the USB communication port checks the actual battery capacity in order to ensure accurate runtime prediction During a deep ba...

Page 13: ...al alarm 1 3 Battery low 4 On bypass 5 Remote UPS shutdown RxD 6 GND 1 Active if the output voltage of the UPS is no longer guaranteed due to other circumstances than already indicated by pin 1 3 4 Th...

Page 14: ...the same for all VH Series models NOTE During battery replacement the UPS will not be able to support the load if a mains failure occurs It is recommended to switch off the load before disconnecting...

Page 15: ...lso 4 3 3 Line cord not connected Read 3 3 6 Connect line cord Dead wall socket outlet or mains voltage out of limits Contact qualified electrician Tripped Thermal Circuit Breaker See above UPS switch...

Reviews: