background image

 

 

4.4.1  Standby 

The UPS output is off, but the batteries are charging, see 3.3.6 step 5 
 

4.4.2  Normal operation 

See 4.3.1. 
 

4.4.3  On bypass 

The UPS is equipped with an automatic bypass switch. This switch automatically transfers the load to 
the mains if the UPS is unable to deliver the demanded output power due to overload or 
overtemperature.  
If all 4 load LEDs illuminate, bypass operation is caused by an overload. If only green load LEDs 
illuminate (the red load LED is off), bypass operation is caused by overtemperature. Take appropriate 
measures: reduce load and/or temperature. 
The UPS will switch back to normal operation when the overload has been removed or the temperature 
has dropped below alarm level. 
If a power failure occurs during bypass operation, the UPS will switch to battery operation and 
eventually, when the batteries are depleted, 

output power is lost

The bypass function can be disabled - see 4.4.6 and 4.5 for further details. 
 

Fail safe bypass operation:

 if the UPS becomes defective, the load may be switched to bypass 

(provided that the bypass function was not disabled). As the status of the UPS is unknown in this 
situation the indications on the operating panel may differ. 
 

4.4.4  On battery 

The UPS uses the energy stored in the batteries: see chapter 9 ‘Batteries - runtime’. 
The runtime capacity LED bar will show the remaining runtime. The UPS will shutdown: 

 

after the batteries have been discharged (automatic restart), or 

 

if keypad 'O' is pressed (restart via front panel required) or 

 

if a 'UPS shutdown' command is given by the computer. Restart depends on the setting of the 
‘auto restart’ function: 

 

-  if set ‘on’ the UPS will automatically restart when the mains returns 

 

-  if set ‘off’ a manual restart is required, either as in 4.2.1 step 1 or via the UPS management 
software. 

 
As default the ‘auto restart’ function is ‘on’. The setting can be changed using the UPS monitoring 
software. For more information please refer to the manual that came with the software. 
 

4.4.5  Battery low (end of runtime) 

If during ‘on battery’ operation the 25% LED starts blinking, the batteries are nearly discharged: the 
remaining runtime is less than 2 minutes (default setting, adjustable via the UPS monitoring software). 
Controlled shutdown of any computer equipment is absolutely necessary at this point. 
If the UPS operates at 100% load, the shutdown procedure should be completed within 2 minutes after 
the 'battery low' alarm started. If only part of the output capacity of the UPS is used this period can be 
longer, with aged batteries this period can be shorter. 
When the batteries are fully discharged, the UPS is no longer able to power the connected equipment. 
 

4.4.6  Bypass out of limits 

The mains voltage or mains frequency are outside bypass input tolerance but inside UPS input tolerance 
(see chapter 9). Bypass operation is inhibited: if for whatever reason the UPS is not able to deliver the 
required output, output power is lost. If the input frequency is often out of tolerance – during which 
bypass operation is inhibited and an alarm is generated – it may be useful to disable the bypass 
function after which the unit operates as a UPS without automatic bypass switch. See 4.5. 

Summary of Contents for 1000 VA VH Series

Page 1: ...User manual VH Series Uninterruptible Power Supply 700 1000 1500 2000 3000 VA...

Page 2: ...ower of the VH Series UPS the rear panel of the UPS shows the model chapter 9 the ratings 3 2 Installation rules The UPS is intended to be used in normal domestic and office situations Protect the UPS...

Page 3: ...ect the DC connector of the internal batteries 5 Assemble the front panel insert the two metal clamps at the rear of the panel into the holes at the right side of the UPS then click the front panel in...

Page 4: ...max rating 10A To connect the loads to the UPS 700 VA 2 outlets 1000 1500 VA 4 outlets 2000 3000 VA 6 outlets 3a Appliance outlet max rating 16A VH Series 3000 VA only To connect a heavy load to the...

Page 5: ...not exceed the VA output rating of the UPS This way you ensure that the UPS is able to supply the required output and prevent that an overload situation will happen 4 Using the output cords provided...

Page 6: ...power fails and the internal batteries supply the required power until either they are depleted or mains power returns 6 LED alarm blinks in case of an alarm 7 LED bar runtime capacity the remaining a...

Page 7: ...this function is activated the UPS will switch off during a mains failure when the load is less than 5 of the maximum load In this way unnecessary discharging of the batteries is avoided The unit will...

Page 8: ...bypass 4 4 3 0 4 0 4 hi o On battery 4 4 4 0 4 0 4 lo Battery low 4 4 5 25 0 4 hi Bypass out of limits 4 4 6 0 4 0 4 lo Overload 4 4 7 0 4 4 hi Replace battery 4 4 8 0 4 0 4 lo General alarm 4 4 9 0 4...

Page 9: ...panel required or if a UPS shutdown command is given by the computer Restart depends on the setting of the auto restart function if set on the UPS will automatically restart when the mains returns if...

Page 10: ...ower failure Allow the UPS to recharge the batteries See also 4 6 4 4 9 General alarm General alarm comprises a group of alarms the buzzer behaviour indicates which alarm is active 1 2 secs General fa...

Page 11: ...the setting of the selected function by pressing switch O The LEDs on the LEDbar runtime capacity shows the setting 4 Store the new settings and leave the setup mode press keypad 1 and keep it presse...

Page 12: ...tery test A deep battery test to be initiated through the UPS software via the USB communication port checks the actual battery capacity in order to ensure accurate runtime prediction During a deep ba...

Page 13: ...al alarm 1 3 Battery low 4 On bypass 5 Remote UPS shutdown RxD 6 GND 1 Active if the output voltage of the UPS is no longer guaranteed due to other circumstances than already indicated by pin 1 3 4 Th...

Page 14: ...the same for all VH Series models NOTE During battery replacement the UPS will not be able to support the load if a mains failure occurs It is recommended to switch off the load before disconnecting...

Page 15: ...lso 4 3 3 Line cord not connected Read 3 3 6 Connect line cord Dead wall socket outlet or mains voltage out of limits Contact qualified electrician Tripped Thermal Circuit Breaker See above UPS switch...

Reviews: