• Operation in TTL network

The E18 thermostat is designed to com-

municate with other E18 and/or E1 
and/or E0 thermostats via a dedicated 
serial based on the TTL logic standards. 
This serial communication is essential 
for the exchange of information within 
small fan coil networks (up to 6) with a 
maximum network length of 30 metres. 
It was designed, in fact, for small areas 
where the fan coils (more than one) 
need to be controlled from a single 
control point. 

More specifically, this network always 

contains a Master (to which a user 
interface VMF-E2, VMF-E4  is  con-
nected) which controls the operation of 
the Slaves connected to it, according to 
the settings made on its user interface. 

You are advised to confi gure as the 

Master an Inverter fan coil with an 
E18-type electronic board (VMF-E18 
or fan coils with E18 board as stand-
ard). WARNING: if the Master is an 
On-Off fan coil with an E1 (VMF-E1) 
or E0 (VMF-E0) type board, the Inverter 
Slave fan coil with the VMF-E18 board 
will lose the continuous control of the 
20 steps in manual mode. 

The fan coil acting as Slave (of an 

Inverter Master fan coil with VMF-E18 
thermostat) must be fi tted with an E18-
type electronic board (VMF-E18), or 
(if On/Off) with an E1 (VMF-E1) / E0 
(VMF-E0) type board. 

All the fan coils of the TTL network must 

have the same type of confi guration. 
Example: all standard, all with puri-
fi ers (Plasmacluster and/or germicidal 
lamps), or all with an additional coil 
(electric or with water).

On the basis of the settings received 

from the network and the ambient 
conditions detected by the probes, the 
electronic board on each single Slave 
fan coil acts (independently from the 
other fan coils) to switch the ventila-
tion on and off in order to create the 
conditions requested by the user for 
that specifi c room. 

• Cooling operation

Cooling operation requires a water cir-

cuit with chiller.

• Heating operation 

Heating operation requires a water 

circuit with boiler, heat pump or solar 
system.

• Changeover (seasonal change)

The thermostat automatically selects the 

operating mode (Heating/Cooling), if 
that mode is permitted (water probe 
and settings).

Normal band

: Heating at 39°C; 

Cooling at 17°C.

Reduced band

: Heating at 35°C; 

Cooling at 22°C.

Dead band

: can be selected at 5°C 

or 2°C. 

Water side changeover

Water temperature checks

Enabling of water side ventilation (only 

active with water temperature probe). 
The thermostat identifies the ventilation 
enabling threshold in Heating mode 
(minimum controlled) and Cooling 
mode (maximum controlled); with the 
dip-switches it is possible to choose 
between two temperature bands. 

Air side changeover

If the actual ambient temperature is 

lower than the set point by a value 
equal to the Dead Band, there is an 
automatic swap to Heating operation.

If the actual ambient temperature is 

higher than the set point 

by a value 

Description of the functions

DESCRIPTION

The VMF-E18 accessory is an advanced 

electronic thermostat kit for use with 
Inverter fan coils. It requires an interface 
inside the fan coil (VMF-E2) or on the 
wall (VMF-E4).

The VMF-E18 kit consists of:

• An E18-type thermostat board inserted 
in a protective box and easily applied to 
the side of the fan coil. 
• System with connection cables to the 
Inverter Command Module. The cables are 
wired with connectors for quick connection.
The E18-type thermostat board has a pro-

tective fuse, a dip-switch for configura-
tion, and connectors for connection with:
- the power supply, 
- the earthing,
- the valve control,
- the Inverter command module power 
supply,
- ambient air temperature sensor,
- water temperature sensor,
- auxiliary water temperature sensor,
- the control panel (user interface),
- presence sensor,
- the external contact,
- microswitch contact connected to the 
fan coil fin,

- the central supervisor system serial 
(VMF-E5),
- the fan coil network serial (TTL).

With the VMF-E18, you can manage:

 Three fan coil speeds in manual mode

 Continuous ventilation and thermostat 
control by controlling the valves

 Automatic fan mode with BRUSHLESS 
motor depending on the load

 Season display

 Display of alarms and ventilation request

 Up to two ON/OFF two or three-way valves

 Ignition of an electric resistor

 Germicidal lamp

 Plasmacluster filter

 A water temperature sensor, with mini-
mum and maximum temperature and 
changeover functions.

 An additional water sensor (accessory) to 

control the second coil (4-pipe systems)

 Season change according to the water 
or air temperature (4-pipe systems).

 Input for “external contact”. This is a 
digital input with the following logic: 
When open, the thermostat works 
normally; When closed, the fan coil is 
switched off.

 Microswitch for fin contact.

 Anti-freeze function.

 Presence sensor to enable the “sleep” 
function from an external contact 
(reduction of ambient setpoint by 2 or 
5 degrees, depending on the settings, if 
a room is unoccupied)

 Input for supervision serial. In networks 
made up of several fan coils subdivided 
into independent temperature areas, the 
VMF-E18 area regulator allows commu-
nication with a central system supervisor 
(VMF-E5)

• 

Input for local serial. Communication 
with other thermostats, via a dedicated 
serial based on the TTL logic standards. 

VMF-E18
KIT containing an ELECTRONIC EXPANDABLE THERMOSTAT BOARD FOR INVERTER FAN COILS

Summary of Contents for VMF-E18

Page 1: ...t extensible pour ventilo convecteurs Inverter VMF System Erweiterbare Thermostatplatine für Inverter Gebläsekonvektoren Sistema VMF Tarjeta termostato expansible para fan coils Inverter M A N UA L E D U S O E I N S TA L L A Z I O N E U S E A N D I N S T A L L A T I O N M A N U A L MANUEL D UTILISATION ET D INSTALLATION BEDIENUNGS UND INSTALLATIONSANLEITUNG MANUAL DE INSTRUCCIONES E INSTALACIÓN ...

Page 2: ...ct Only touch the element exposed to electrostatic risk when absolutely essential e g for maintenance Touch the element without coming into contact with either the con tact pins or the wire guides If you follow this rule the energy of the electrostatic charges cannot reach or damage the sensitive parts Before taking measurements on the unit it is necessary to discharge all electrostatic charges fr...

Page 3: ...rolled with the dip switches it is possible to choose between two temperature bands Air side changeover If the actual ambient temperature is lower than the set point by a value equal to the Dead Band there is an automatic swap to Heating operation If the actual ambient temperature is higher than the set point by a value Description of the functions DESCRIPTION The VMF E18 accessory is an advanced ...

Page 4: ... selected speed With the VMF E4 panel you can select one of the 20 speed steps between 0 and 20 maximum speed Automatic with the selector on AUTO The fan speed is managed by the ther mostat on the basis of the ambient con ditions and the fan coil configuration Thermostat settings Ventilation management Ventilation settings Continuous ventilation Ventilation is always active The temperature is con ...

Page 5: ...ectric heater involves a similar ventilation management to that in Automatic mode If the fan coil is operated with continuous ventilation then the electric heater will switch off when the set point is reached Following the post ventilation phase described below ventilation continues at speed Vmin Vmin can be selected using Dip 8 Electric heater operation involves pre ventilation and post ventilati...

Page 6: ...r pre heating Minimum temperature check activated Heating Minimum temperature check deactivated Heating Minimum temperature check activated Heating Minimum temperature check deactivated Heating Maximum check activated if probe is present Cooling Maximum check activated if probe is present Cooling Maximum check activated if probe is present Cooling Maximum check activated if probe is present Coolin...

Page 7: ...lectrical mains Any intervention by unqualified and untrained personnel could cause injury to the worker and damage to the equipment and surrounding environment Check the mains voltage complies with the one requested for the device to be installed The electrical wiring measurements must be carried out according to the regulations in force taking into account the system load For the power supply us...

Page 8: ...he air temperature sensor SA Connect the electric cables of the water temperature sensor SW Connect the electric cables of the sec ondary water temperature sensor SW1 in 4 pipe hydronic systems Connect the cables for the external contact if envisaged Connect the cables for the presence sensor if envisaged Connect the cables for the microswitch if envisaged Connect the mains and RS485 power supply ...

Page 9: ...Digital input Screw clamps Minimum cable section 0 2mm2 Maximum cable section 1 0mm2 Maximum cable length 30m CE External contact Digital input Screw clamps Minimum cable section 0 2mm2 Maximum cable section 1 0mm2 Maximum cable length 100m MS Microswitch Sliding contact Maximum cable length 3m RS485 E5 Supervision serial Power supply VMF E5 5 Poles Removable type connector Shielded cable size AWG...

Page 10: ... system with electric heater OFF ON four pipe system ON OFF Two pipe system with Plasmacluster Bactericide lamp ON ON Two pipe system with bactericide lamp always on Position Functions Dip 1 Default OFF Check water valve Thermostat in centralised network See table OFF No shut off valve ON Shutoff valve present Thermostat in centralised network Dip 2 Default OFF Position water temperature sensor Th...

Page 11: ...m pitch Cable section min 0 2mm2 max 1 0mm2 Maximum cable length 100m MS digital input Sliding contact Maximum cable length 3m SP digital input Screw terminals 3 81mm pitch Cable section min 0 2mm2 max 1 0mm2 Maximum cable length 100m Analogue inputs SA SW Quick plug in connections Maximum cable length 3m Analogue input SC Quick plug in connection Maximum cable length 30m TTL local serial Screw te...

Page 12: ...o comandi Connection to the control panel Raccordement au panneau de commande Anschluss an die Bedientafel Conexión al tablero de mandos TTL Seriale locale TTL Local serial TTL Liaison série locale TTL Lokale serielle Schnittstelle TTL Serial Local Y1 Comando valvola VC VF Y2 Comando accessorio Y1 VC VF control Y2 Accessory control Y1 Commande VC VF Y2 Commande accessoire Y1 Steuerung VC VF Y2 Ste...

Page 13: ...ontatto esterno SP Presence sensor CE External contact SP Capteur de présence CE Contact extérieur SP Anwesenheitssensor CE Außenkontakt SP Sensor de presencia CE Contacto externo Sonda acqua su scambiatore raffrescamento 4tubi Water probe on cooling exchanger 4 pipes Sonde d eau sur échangeur de refroidissement 4 tubes Wassertemperaturfühler auf Wärmetauscher für Kühlbetrieb Sonda de agua en inte...

Page 14: ...isione Alimentazione esterna VMF E5 RS485 Supervision serial VMF E5 external power supply RS485 Liaison série de supervision Alimentation externe VMF E5 RS485 Serielle Überwachungsschnittstelle Externe Stromversorgung VMF E5 RS485 Serial supervisión Alimentación externa VMF E5 La schermatura di ogni cavo deve essere collegata a terra in un solo punto Every shield cable must be connected to the gro...

Page 15: ...e supervisione RS485 VMF_E18 MODU_485A Supervision serial RS485 VMF_E18 MODU_485A Liaison série de supervision RS485 VMF_E18 MODU_485A Serielle Überwachungsschnittstelle E18 MODU_485A Serial supervisión RS485 VMF_E18 MODU_485A 22AWG 3 VMF MCR VMF MCR VMF E18 VMF E18 22AWG 3 22AWG 3 22AWG 3 Seriale supervisione RS485 VMF_E18 VMF_MCR Supervision serial RS485 VMF_E18 VMF_MCR Liaison série de supervis...

Page 16: ...ruttore Dip switch Microrupteur Mikroschalter Microinterruptor MV Motore ventilatore Fan motor Moteur du ventilateur Ventilatormotor Motor ventilador PE Collegamento di terra Earth connection Mise à la terre Erdung Toma de tierra SA Sonda ambiente Ambient probe Sonde ambiante Raumtemperaturfühler Sonda ambiente SC Sonda ambiente Control card carte de contrôle Steuerplatine Tarjeta de control SW So...

Page 17: ...squemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriques étant constamment mis à jour il faut absolument se référer à ceux fou...

Page 18: ... 1 1 C37 ROS ROSA SW1 PE VMF E18 MS MS VC Y2 VC F Y1 VC Y2 SW SW VMF E18 master slave VMF E5 VMF E2 E4 Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h...

Page 19: ...A 485 4 V Pan 3 GND 485 5 GND Pan CN16 C2 SW SLOT EXPANSION ROS 1 1 C37 ROS ROSA SW1 PE VMF E18 MS VMF E1 VMF E5 MAX 30m CN17 1 TX RX 2 GND 2 B 485 1 A 485 4 V Pan 3 GND 485 5 GND Pan CN16 RS485 12V TTL MS VC Y2 VC F Y1 VC Y2 SW SW 22AWG VMF E18 master slave VMF E5 VMF E2 E4 Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que ...

Page 20: ...ICI WIRINGDIAGRAMS SCHEMASELECTRIQUES ELEKTRISCHESCHALTPLÄNE ESQUEMASELECTRICOS TTL Seriale locale TTL Local serial TTL Liaison série locale TTL Lokale serielle Schnittstelle TTL Serial Local Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s ...

Page 21: ...MF E2 VMF E4 Master VMF E5 MAX 30m Power Supply Power Supply 12Vdc 24Vac Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas éle...

Page 22: ...VMF E1 VMF E1 VMF E5 Only Master 4 3 2 1 VMF E2 VMF E4 Master 22AWG Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriq...

Page 23: ...MF E1 VMF E1 22AWG VMF E1 VMF E5 VMF E5 Only Master 4 3 2 1 VMF E2 VMF E4 Master MAX 30m MODU 485A Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h...

Page 24: ...VMF E1 VMF MCR 22AWG VMF E1 VMF E5 VMF E5 Only Master 4 3 2 1 VMF E2 VMF E4 Master MAX 30m VMF MCR Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h...

Page 25: ...rve le droit de modifier à tous moments les données considérées nécessaires à l amelioration du produit Technical data shown in this booklet are not binding Aermec S p A shall have the right to introduce at any time whatever modifications deemed necessary to the improvement of the product Im Sinne des technischen Fortsschrittes behält sich Aermec S p A vor in der Produktion Änderungen und Verbesse...

Reviews: