BOARD INSTALLATION AND CONNECTIONS 

• The VMF-E18 Kit includes the 

system with connection cables 
to the Inverter Control Module.
The cables are wired with connectors 
for quick connection.

The installation of the VMF-E18 kit 

requires that standard control board 
and connection cables to the Inverter 
Control Module (Signal and Supply) are 
removed from the fan coil. 

• Mount the thermostat housing to the 

side of the fan coil units, on the con-
nections that were of the control board.

• Remove the cover of the thermostat 

housing. 

• Connect the inverter control module 

VMF-E18 to the thermostat using 
the system with connection cables 
supplied with the VMF-E18 kit.
Check the connection with the wiring 
diagram.

• WARNING: make an earth connection 

for the thermostat board. 

 

DANGER: it is compulsory to tighten the 
screw on the side of the fan coil, as this 
is what allows the earth connection of 
the entire system. 

• Connect the power supply cables. Warn-

ing: respect the L and N polarities.

• Connect the electric cables of the air 

temperature sensor (SA). 

• Connect the electric cables of the water 

temperature sensor (SW). 

• Connect the electric cables of the sec-

ondary water temperature sensor (SW1), 
in 4-pipe hydronic systems.

• Connect the cables for the external 

contact (if envisaged). 

• Connect the cables for the presence 

sensor (if envisaged). 

• Connect the cables for the microswitch 

(if envisaged). 

• Connect the mains and RS485 power 

supply cables (if connected to the 
mains). 

DANGER: must be connected 

to the earth.

• Connect the TTL mains cables (if con-

nected to the mains). 

• Connect the cables of the control panel 

(if envisaged). 

• Check that all the connections and rela-

tive cables are well fixed. 

• Arrange the cables so there is no risk 

of them being cut, crushed, jerked, 
scraped, or generally damaged.

• Check that the board fuse is undamaged 

and possesses the necessary features.

• Close the housing with the cover.
• Fix the power supply cables and valve 

cables using the cable clamp.

DANGER: 

it is compulsory to tighten the screw on the side of the fan coil, as this is 

what allows the earth connection of the entire system. 

WARNING: Keep separate electri-

cal connections from water con-
nections. Water connections and 
drain should be on the side oppo-
site of the electrical connections.

Summary of Contents for VMF-E18

Page 1: ...t extensible pour ventilo convecteurs Inverter VMF System Erweiterbare Thermostatplatine für Inverter Gebläsekonvektoren Sistema VMF Tarjeta termostato expansible para fan coils Inverter M A N UA L E D U S O E I N S TA L L A Z I O N E U S E A N D I N S T A L L A T I O N M A N U A L MANUEL D UTILISATION ET D INSTALLATION BEDIENUNGS UND INSTALLATIONSANLEITUNG MANUAL DE INSTRUCCIONES E INSTALACIÓN ...

Page 2: ...ct Only touch the element exposed to electrostatic risk when absolutely essential e g for maintenance Touch the element without coming into contact with either the con tact pins or the wire guides If you follow this rule the energy of the electrostatic charges cannot reach or damage the sensitive parts Before taking measurements on the unit it is necessary to discharge all electrostatic charges fr...

Page 3: ...rolled with the dip switches it is possible to choose between two temperature bands Air side changeover If the actual ambient temperature is lower than the set point by a value equal to the Dead Band there is an automatic swap to Heating operation If the actual ambient temperature is higher than the set point by a value Description of the functions DESCRIPTION The VMF E18 accessory is an advanced ...

Page 4: ... selected speed With the VMF E4 panel you can select one of the 20 speed steps between 0 and 20 maximum speed Automatic with the selector on AUTO The fan speed is managed by the ther mostat on the basis of the ambient con ditions and the fan coil configuration Thermostat settings Ventilation management Ventilation settings Continuous ventilation Ventilation is always active The temperature is con ...

Page 5: ...ectric heater involves a similar ventilation management to that in Automatic mode If the fan coil is operated with continuous ventilation then the electric heater will switch off when the set point is reached Following the post ventilation phase described below ventilation continues at speed Vmin Vmin can be selected using Dip 8 Electric heater operation involves pre ventilation and post ventilati...

Page 6: ...r pre heating Minimum temperature check activated Heating Minimum temperature check deactivated Heating Minimum temperature check activated Heating Minimum temperature check deactivated Heating Maximum check activated if probe is present Cooling Maximum check activated if probe is present Cooling Maximum check activated if probe is present Cooling Maximum check activated if probe is present Coolin...

Page 7: ...lectrical mains Any intervention by unqualified and untrained personnel could cause injury to the worker and damage to the equipment and surrounding environment Check the mains voltage complies with the one requested for the device to be installed The electrical wiring measurements must be carried out according to the regulations in force taking into account the system load For the power supply us...

Page 8: ...he air temperature sensor SA Connect the electric cables of the water temperature sensor SW Connect the electric cables of the sec ondary water temperature sensor SW1 in 4 pipe hydronic systems Connect the cables for the external contact if envisaged Connect the cables for the presence sensor if envisaged Connect the cables for the microswitch if envisaged Connect the mains and RS485 power supply ...

Page 9: ...Digital input Screw clamps Minimum cable section 0 2mm2 Maximum cable section 1 0mm2 Maximum cable length 30m CE External contact Digital input Screw clamps Minimum cable section 0 2mm2 Maximum cable section 1 0mm2 Maximum cable length 100m MS Microswitch Sliding contact Maximum cable length 3m RS485 E5 Supervision serial Power supply VMF E5 5 Poles Removable type connector Shielded cable size AWG...

Page 10: ... system with electric heater OFF ON four pipe system ON OFF Two pipe system with Plasmacluster Bactericide lamp ON ON Two pipe system with bactericide lamp always on Position Functions Dip 1 Default OFF Check water valve Thermostat in centralised network See table OFF No shut off valve ON Shutoff valve present Thermostat in centralised network Dip 2 Default OFF Position water temperature sensor Th...

Page 11: ...m pitch Cable section min 0 2mm2 max 1 0mm2 Maximum cable length 100m MS digital input Sliding contact Maximum cable length 3m SP digital input Screw terminals 3 81mm pitch Cable section min 0 2mm2 max 1 0mm2 Maximum cable length 100m Analogue inputs SA SW Quick plug in connections Maximum cable length 3m Analogue input SC Quick plug in connection Maximum cable length 30m TTL local serial Screw te...

Page 12: ...o comandi Connection to the control panel Raccordement au panneau de commande Anschluss an die Bedientafel Conexión al tablero de mandos TTL Seriale locale TTL Local serial TTL Liaison série locale TTL Lokale serielle Schnittstelle TTL Serial Local Y1 Comando valvola VC VF Y2 Comando accessorio Y1 VC VF control Y2 Accessory control Y1 Commande VC VF Y2 Commande accessoire Y1 Steuerung VC VF Y2 Ste...

Page 13: ...ontatto esterno SP Presence sensor CE External contact SP Capteur de présence CE Contact extérieur SP Anwesenheitssensor CE Außenkontakt SP Sensor de presencia CE Contacto externo Sonda acqua su scambiatore raffrescamento 4tubi Water probe on cooling exchanger 4 pipes Sonde d eau sur échangeur de refroidissement 4 tubes Wassertemperaturfühler auf Wärmetauscher für Kühlbetrieb Sonda de agua en inte...

Page 14: ...isione Alimentazione esterna VMF E5 RS485 Supervision serial VMF E5 external power supply RS485 Liaison série de supervision Alimentation externe VMF E5 RS485 Serielle Überwachungsschnittstelle Externe Stromversorgung VMF E5 RS485 Serial supervisión Alimentación externa VMF E5 La schermatura di ogni cavo deve essere collegata a terra in un solo punto Every shield cable must be connected to the gro...

Page 15: ...e supervisione RS485 VMF_E18 MODU_485A Supervision serial RS485 VMF_E18 MODU_485A Liaison série de supervision RS485 VMF_E18 MODU_485A Serielle Überwachungsschnittstelle E18 MODU_485A Serial supervisión RS485 VMF_E18 MODU_485A 22AWG 3 VMF MCR VMF MCR VMF E18 VMF E18 22AWG 3 22AWG 3 22AWG 3 Seriale supervisione RS485 VMF_E18 VMF_MCR Supervision serial RS485 VMF_E18 VMF_MCR Liaison série de supervis...

Page 16: ...ruttore Dip switch Microrupteur Mikroschalter Microinterruptor MV Motore ventilatore Fan motor Moteur du ventilateur Ventilatormotor Motor ventilador PE Collegamento di terra Earth connection Mise à la terre Erdung Toma de tierra SA Sonda ambiente Ambient probe Sonde ambiante Raumtemperaturfühler Sonda ambiente SC Sonda ambiente Control card carte de contrôle Steuerplatine Tarjeta de control SW So...

Page 17: ...squemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriques étant constamment mis à jour il faut absolument se référer à ceux fou...

Page 18: ... 1 1 C37 ROS ROSA SW1 PE VMF E18 MS MS VC Y2 VC F Y1 VC Y2 SW SW VMF E18 master slave VMF E5 VMF E2 E4 Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h...

Page 19: ...A 485 4 V Pan 3 GND 485 5 GND Pan CN16 C2 SW SLOT EXPANSION ROS 1 1 C37 ROS ROSA SW1 PE VMF E18 MS VMF E1 VMF E5 MAX 30m CN17 1 TX RX 2 GND 2 B 485 1 A 485 4 V Pan 3 GND 485 5 GND Pan CN16 RS485 12V TTL MS VC Y2 VC F Y1 VC Y2 SW SW 22AWG VMF E18 master slave VMF E5 VMF E2 E4 Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que ...

Page 20: ...ICI WIRINGDIAGRAMS SCHEMASELECTRIQUES ELEKTRISCHESCHALTPLÄNE ESQUEMASELECTRICOS TTL Seriale locale TTL Local serial TTL Liaison série locale TTL Lokale serielle Schnittstelle TTL Serial Local Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s ...

Page 21: ...MF E2 VMF E4 Master VMF E5 MAX 30m Power Supply Power Supply 12Vdc 24Vac Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas éle...

Page 22: ...VMF E1 VMF E1 VMF E5 Only Master 4 3 2 1 VMF E2 VMF E4 Master 22AWG Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriq...

Page 23: ...MF E1 VMF E1 22AWG VMF E1 VMF E5 VMF E5 Only Master 4 3 2 1 VMF E2 VMF E4 Master MAX 30m MODU 485A Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h...

Page 24: ...VMF E1 VMF MCR 22AWG VMF E1 VMF E5 VMF E5 Only Master 4 3 2 1 VMF E2 VMF E4 Master MAX 30m VMF MCR Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h...

Page 25: ...rve le droit de modifier à tous moments les données considérées nécessaires à l amelioration du produit Technical data shown in this booklet are not binding Aermec S p A shall have the right to introduce at any time whatever modifications deemed necessary to the improvement of the product Im Sinne des technischen Fortsschrittes behält sich Aermec S p A vor in der Produktion Änderungen und Verbesse...

Reviews: