the Heating set point by a value equal 
to the dead band, there is an automatic 
swap to Cooling operation. 

If the actual ambient temperature falls 

below the Cooling set point by a value 
equal to the dead band, there is an 
automatic swap to Heating operation.

Heater switch-on and switch-off depends 

solely on the thermostat operation 
request.

In this case, a fixed correction of the 

ambient probe is envisaged, and is 
determined on the basis of the type of 
thermostat configured.

• Behaviour with a faulty ambient 

temperature probe

-

 2-pipe system:

With the selector in the OFF/Aux 

position, ventilation switched off and 
the valve is closed.

With the selector in the AUTO, V1, 

V2, V3 position, the Heating mode is 
fixed and the valve is always open. 
The ventilation makes on-off cycles 
of variable duration depending on the 
position of the temperature selector.

- 4-pipe system:

With the selector in the OFF/Aux 

position, ventilation switched off and 
the valve is closed

With the selector in the AUTO, V1, V2, 

V3 position, the Heating/Cooling mode 
is decided on the basis of the position 
of the temperature selector, activating 
the respective valve. The ventilation 
makes on-off cycles of variable duration 
depending on the position of the 
temperature selector.

• Behaviour with a faulty ambient 

temperature probe on a Slave fan coil

The board automatically assumes the 

reading of the ambient probe of the 
Master fan coil. 

• Heating mode with electric heater 

(if present)

The electric heater must be enabled by 

configuring the dip-switches on the 
thermostat again. Activate the heater-
operated heating by positioning the 
control panel selector on AUX.

Standard operation is of the ON-OFF 

type. 

The electric heater intervenes when there 

is a thermostat operation request and 
the water temperature is sufficiently 
low. 

It should be noted that when the 

thermostat starts up, the heater is OFF, 
so it will only be activated if the water 
temperature is below the enabling 
threshold (35°C with normal band and 
31°C with reduced band).

In any case, the activation of the electric 

heater involves a similar ventilation 
management to that in Automatic mode. 

If the fan coil is operated with continuous 

ventilation, then the electric heater will 
switch off when the set point is reached. 
Following the post-ventilation phase 
(described below), ventilation continues 
at speed Vmin (Vmin can be selected 
using Dip.8).

Electric heater operation involves 

pre-ventilation and post-ventilation 
phases in relation to its activation and 
deactivation. 

It should be noted that the pre-ventilation 

phase (20” at Vmin) always corresponds 
to the activation of the electric heater, 
while the post-ventilation phase always 
corresponds to the deactivation of the 
electric heater (60” at Vmin).

Example: the thermostat requests fan 

operation with the heater activated (i.e. 
the water temperature is sufficiently 
low), so we will have 20” of ventilation 
at speed Vmin (pre-ventilation) after 

which the thermostat will operate at 
the ventilation speed determined by 
the microprocessor on the basis of the 
difference between the actual ambient 
temperature and the set temperature. 
Once the set temperature has been 
reached, if the heater is still active (i.e. 
the water temperature is sufficiently 
low), we will have post-ventilation for 
1min at speed Vmin.

It should be noted that when the heater is 

switched off during operation because 
the water temperature is sufficiently high, 
then after reaching the set temperature, 
ventilation continues at speed Vmin for 
the remaining time needed to terminate 
the post-ventilation cycle.

Finally, please note that the heater is 

never enabled if the thermostat is in 
anti-freeze or emergency mode, due to 
the ambient probe.

• Operation with purifying devices (if 

present)

If purifying devices are installed 

(Plasmacluster or bactericidal lamp), 
they must be enabled by configuring the 
dip-switches on the thermostat again. 

With the selector on “Aux”, the ambient 

is purified regardless of the thermostat 
operation requests.

Unlike the electric heater however, this 

type of accessory is even activated 
if the operation speed selector is not 
positioned on “Aux”. 

On “Aux”, the fan will always operate 

at minimum speed, closing any shutoff 
element whose use is recommended 
with this function and thereby avoiding 
any ambient alterations (overheating / 
under-cooling). 

Summary of Contents for VMF-E18

Page 1: ...t extensible pour ventilo convecteurs Inverter VMF System Erweiterbare Thermostatplatine für Inverter Gebläsekonvektoren Sistema VMF Tarjeta termostato expansible para fan coils Inverter M A N UA L E D U S O E I N S TA L L A Z I O N E U S E A N D I N S T A L L A T I O N M A N U A L MANUEL D UTILISATION ET D INSTALLATION BEDIENUNGS UND INSTALLATIONSANLEITUNG MANUAL DE INSTRUCCIONES E INSTALACIÓN ...

Page 2: ...ct Only touch the element exposed to electrostatic risk when absolutely essential e g for maintenance Touch the element without coming into contact with either the con tact pins or the wire guides If you follow this rule the energy of the electrostatic charges cannot reach or damage the sensitive parts Before taking measurements on the unit it is necessary to discharge all electrostatic charges fr...

Page 3: ...rolled with the dip switches it is possible to choose between two temperature bands Air side changeover If the actual ambient temperature is lower than the set point by a value equal to the Dead Band there is an automatic swap to Heating operation If the actual ambient temperature is higher than the set point by a value Description of the functions DESCRIPTION The VMF E18 accessory is an advanced ...

Page 4: ... selected speed With the VMF E4 panel you can select one of the 20 speed steps between 0 and 20 maximum speed Automatic with the selector on AUTO The fan speed is managed by the ther mostat on the basis of the ambient con ditions and the fan coil configuration Thermostat settings Ventilation management Ventilation settings Continuous ventilation Ventilation is always active The temperature is con ...

Page 5: ...ectric heater involves a similar ventilation management to that in Automatic mode If the fan coil is operated with continuous ventilation then the electric heater will switch off when the set point is reached Following the post ventilation phase described below ventilation continues at speed Vmin Vmin can be selected using Dip 8 Electric heater operation involves pre ventilation and post ventilati...

Page 6: ...r pre heating Minimum temperature check activated Heating Minimum temperature check deactivated Heating Minimum temperature check activated Heating Minimum temperature check deactivated Heating Maximum check activated if probe is present Cooling Maximum check activated if probe is present Cooling Maximum check activated if probe is present Cooling Maximum check activated if probe is present Coolin...

Page 7: ...lectrical mains Any intervention by unqualified and untrained personnel could cause injury to the worker and damage to the equipment and surrounding environment Check the mains voltage complies with the one requested for the device to be installed The electrical wiring measurements must be carried out according to the regulations in force taking into account the system load For the power supply us...

Page 8: ...he air temperature sensor SA Connect the electric cables of the water temperature sensor SW Connect the electric cables of the sec ondary water temperature sensor SW1 in 4 pipe hydronic systems Connect the cables for the external contact if envisaged Connect the cables for the presence sensor if envisaged Connect the cables for the microswitch if envisaged Connect the mains and RS485 power supply ...

Page 9: ...Digital input Screw clamps Minimum cable section 0 2mm2 Maximum cable section 1 0mm2 Maximum cable length 30m CE External contact Digital input Screw clamps Minimum cable section 0 2mm2 Maximum cable section 1 0mm2 Maximum cable length 100m MS Microswitch Sliding contact Maximum cable length 3m RS485 E5 Supervision serial Power supply VMF E5 5 Poles Removable type connector Shielded cable size AWG...

Page 10: ... system with electric heater OFF ON four pipe system ON OFF Two pipe system with Plasmacluster Bactericide lamp ON ON Two pipe system with bactericide lamp always on Position Functions Dip 1 Default OFF Check water valve Thermostat in centralised network See table OFF No shut off valve ON Shutoff valve present Thermostat in centralised network Dip 2 Default OFF Position water temperature sensor Th...

Page 11: ...m pitch Cable section min 0 2mm2 max 1 0mm2 Maximum cable length 100m MS digital input Sliding contact Maximum cable length 3m SP digital input Screw terminals 3 81mm pitch Cable section min 0 2mm2 max 1 0mm2 Maximum cable length 100m Analogue inputs SA SW Quick plug in connections Maximum cable length 3m Analogue input SC Quick plug in connection Maximum cable length 30m TTL local serial Screw te...

Page 12: ...o comandi Connection to the control panel Raccordement au panneau de commande Anschluss an die Bedientafel Conexión al tablero de mandos TTL Seriale locale TTL Local serial TTL Liaison série locale TTL Lokale serielle Schnittstelle TTL Serial Local Y1 Comando valvola VC VF Y2 Comando accessorio Y1 VC VF control Y2 Accessory control Y1 Commande VC VF Y2 Commande accessoire Y1 Steuerung VC VF Y2 Ste...

Page 13: ...ontatto esterno SP Presence sensor CE External contact SP Capteur de présence CE Contact extérieur SP Anwesenheitssensor CE Außenkontakt SP Sensor de presencia CE Contacto externo Sonda acqua su scambiatore raffrescamento 4tubi Water probe on cooling exchanger 4 pipes Sonde d eau sur échangeur de refroidissement 4 tubes Wassertemperaturfühler auf Wärmetauscher für Kühlbetrieb Sonda de agua en inte...

Page 14: ...isione Alimentazione esterna VMF E5 RS485 Supervision serial VMF E5 external power supply RS485 Liaison série de supervision Alimentation externe VMF E5 RS485 Serielle Überwachungsschnittstelle Externe Stromversorgung VMF E5 RS485 Serial supervisión Alimentación externa VMF E5 La schermatura di ogni cavo deve essere collegata a terra in un solo punto Every shield cable must be connected to the gro...

Page 15: ...e supervisione RS485 VMF_E18 MODU_485A Supervision serial RS485 VMF_E18 MODU_485A Liaison série de supervision RS485 VMF_E18 MODU_485A Serielle Überwachungsschnittstelle E18 MODU_485A Serial supervisión RS485 VMF_E18 MODU_485A 22AWG 3 VMF MCR VMF MCR VMF E18 VMF E18 22AWG 3 22AWG 3 22AWG 3 Seriale supervisione RS485 VMF_E18 VMF_MCR Supervision serial RS485 VMF_E18 VMF_MCR Liaison série de supervis...

Page 16: ...ruttore Dip switch Microrupteur Mikroschalter Microinterruptor MV Motore ventilatore Fan motor Moteur du ventilateur Ventilatormotor Motor ventilador PE Collegamento di terra Earth connection Mise à la terre Erdung Toma de tierra SA Sonda ambiente Ambient probe Sonde ambiante Raumtemperaturfühler Sonda ambiente SC Sonda ambiente Control card carte de contrôle Steuerplatine Tarjeta de control SW So...

Page 17: ...squemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriques étant constamment mis à jour il faut absolument se référer à ceux fou...

Page 18: ... 1 1 C37 ROS ROSA SW1 PE VMF E18 MS MS VC Y2 VC F Y1 VC Y2 SW SW VMF E18 master slave VMF E5 VMF E2 E4 Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h...

Page 19: ...A 485 4 V Pan 3 GND 485 5 GND Pan CN16 C2 SW SLOT EXPANSION ROS 1 1 C37 ROS ROSA SW1 PE VMF E18 MS VMF E1 VMF E5 MAX 30m CN17 1 TX RX 2 GND 2 B 485 1 A 485 4 V Pan 3 GND 485 5 GND Pan CN16 RS485 12V TTL MS VC Y2 VC F Y1 VC Y2 SW SW 22AWG VMF E18 master slave VMF E5 VMF E2 E4 Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que ...

Page 20: ...ICI WIRINGDIAGRAMS SCHEMASELECTRIQUES ELEKTRISCHESCHALTPLÄNE ESQUEMASELECTRICOS TTL Seriale locale TTL Local serial TTL Liaison série locale TTL Lokale serielle Schnittstelle TTL Serial Local Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s ...

Page 21: ...MF E2 VMF E4 Master VMF E5 MAX 30m Power Supply Power Supply 12Vdc 24Vac Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas éle...

Page 22: ...VMF E1 VMF E1 VMF E5 Only Master 4 3 2 1 VMF E2 VMF E4 Master 22AWG Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos schémas électriq...

Page 23: ...MF E1 VMF E1 22AWG VMF E1 VMF E5 VMF E5 Only Master 4 3 2 1 VMF E2 VMF E4 Master MAX 30m MODU 485A Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h...

Page 24: ...VMF E1 VMF MCR 22AWG VMF E1 VMF E5 VMF E5 Only Master 4 3 2 1 VMF E2 VMF E4 Master MAX 30m VMF MCR Los esquemas eléctricos están sujetos a modificaciones continuas por lo tanto es obligatorio tomar la referencia de los que se encuentran a bordo de la máquina A l l w i r i n g d i a g r a m s a r e c o n s t a n t l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h...

Page 25: ...rve le droit de modifier à tous moments les données considérées nécessaires à l amelioration du produit Technical data shown in this booklet are not binding Aermec S p A shall have the right to introduce at any time whatever modifications deemed necessary to the improvement of the product Im Sinne des technischen Fortsschrittes behält sich Aermec S p A vor in der Produktion Änderungen und Verbesse...

Reviews: