39
18.01._5280107_02
NRL 0280-0750 °-L / A-E
EN
L1
L2
L3
N
TERRA (PE)
FASE
NEUTRO
Alimentazione:
0280
400V/3N/50Hz
2
6
49,41
158
3+N
1
16
16
4
1,5
16
63
0300
400V/3N/50Hz
2
6
56,41
187
3+N
1
16
16
4
1,5
16
63
0330
400V/3N/50Hz
2
8
64,41
193
3+N
1
25
16
4
1,5
16
80
0350
400V/3N/50Hz
2
8
66,41
203
3+N
1
25
16
4
1,5
16
80
0500
400V/3N/50Hz
2
2
80,53
219
3+N
1
50
25
4
1,5
25
125
0550
400V/3N/50Hz
3
2
85,53
225
3+N
1
50
25
4
1,5
25
125
0600
400V/3N/50Hz
4
2
105,86
238
3+N
1
5
25
4
1,5
25
125
0650
400V/3N/50Hz
4
2
117,86
249
3+N
1
70
35
4
1,5
35
160
0700
400V/3N/50Hz
4
3
127,86
267
3+N
1
70
35
4
1,5
35
160
0750
400V/3N/50Hz
4
3
144
320
3+N
1
95
35
4
1,5
50
200
NRL A - E
NRL
SIZE
Po
w
er supply
Compr
essor
s [n°]
Fans [n°] A
-E
TOTAL
ABSORPTION
RECOMMENDED CABLE CROSS-SECTION
F.L.A.
L.R.A.
SEZ. A
SEC. B
TERRA
IL
[A]
[A]
Phases
[n°]
Cables
for single
phase [n°]
Cable
cross-
section
[mm2]
Neutral
cross-
section
[mm2]
Total
cables
[n°]
[mm
2
]
[mm
2
]
[A]
KEY
L.R.A.:
Initial starting current
F.L.A.:
Maximum input current
Sec A:
Power supply
Sec B:
Controls and safety device connection
EARTH
: Earth wire to connect to unit
IL:
Master switch