18
6.
The setting is only valid if the unit is “On”.
7.
Depending on the operating mode defined (heating or cooling), the relative set-points will be used.
8.
If the start time of “Period 2” is the same as that of “Period 1”, the first will be implemented.
9.
The time bands are based on the timer inside the unit.
10. During hot water production mode, this function is not available.
11. If the relative function is activated (paragraph 8.3), the value of this parameter will be stored in the
memory and automatically reset after any possible voltage failure.
12. The default value for this function is “Off”.
Emergen. mode
On
Off
OK
Cancel
NOTES:
1.
Emergency mode can only be activated when the unit is OFF, or if the compressor displays an error
and, despite a reset, the error resumes and persists for at least 3 minutes.
2.
Emergency mode can only be activated in heating (DHW or Heating, but not simultaneously).
3.
Emergency mode cannot be activated without the installation (and activation) of the electric heater
on the storage tank and/or the additional heat source or electric heater.
4.
The use of Emergency mode (in Heating) will be blocked if the “HP-Water Switch“, “Auxi. heater 1”,
“Auxi. heater 2“, “Temp AHLW“ errors appear.
5.
The use of Emergency mode (in DHW) will be blocked if the “Auxi. WTH“ error appears.
6.
None of the functions linked to the timers will be available during Emergency mode.
7.
The thermostat cannot be used in Emergency mode.
8.
After a voltage failure, Emergency mode returns to the OFF status.
9.
Certain functions are not available in Emergency mode so, if you attempt to activate them, the sys-
tem will tell you to disable Emergency mode first.
10. The default value for this function is “Off”.
4.13.
Enabling emergency operation for heating or DHW (Emergen. mode)
If the compatible Aermec accessory tank for this mod-
el (refer to the installation manual for more informa-
tion) - and/or an additional heat source (paragraph
7.7) or electric heater (paragraph 7.8) - is installed and
correctly set on the system, you can enable the “Emer-
gency mode” function which excludes the heat pump
for hot water (domestic or system) production, using
only the electric heater of the storage tank and/or the
additional heat source (or electric heater) to meet the
requests. After accessing the “Emergen. mode” func-
tion, you can enable or disable this program; you must
then press “OK” to confirm.