12
22.11 – 6755532_06
VERSION P
Water filter:
Installation in the immediate vicinity of the heat exchanger is mandatory,.
1
Plate heat exchanger
2
In the versions without a hy-
dronic kit, the water filter is sup-
plied with a connection point for
making the connection. In the
versions with a hydronic kit, it is
supplied ready-mounted
3
Flow switch
4
Air drain valve
5
Water temperature sensor (IN/
OUT)
6
Anti-vibration joints
7
Flow shut-off valves
8
Pressure relief valve
9
Expansion vessel
10 System buffer tank
11 Pressure gauge
12 Pump
13 Resistance
14 Drain valve
5
5
2
4
4
4
10
14
1
13
7
6
6
11
11
3
8
12
9
Water characteristics
System: Chiller with plate heat exchanger
PH
7,5 - 9
Total hardness
4,5 - 8,5 °dH
Temperature
< 65 °C
Oxygen content
< 0,1 ppm
Max. glycol amount
50 %
Phosphates (PO₄)
< 2ppm
Manganese (Mn)
< 0,05 ppm
Iron (Fe)
< 0,3 ppm
Alkalinity (HCO₃)
70 - 300 ppm
Chloride ions (Cl-)
< 50 ppm
Sulphate ions (SO₄)
< 50 ppm
Sulphide ion (S)
None
Ammonium ions (NH₄)
None
Silica (SiO₂)
< 30 ppm
NOTICE under no circumstances does the unit have to be operated with water circulating on the heat exchanger whose characteristics are different from
those indicated in the table WATER CHARACTERISTICS, under penalty of the warranty expiration. Aermec cannot be held responsible for any malfunction
of the units which are operated with water whose characteristics are outside the limits in the table WATER CHARACTERISTICS and for their consequences.
It is of fundamental importance to keep the oxygen concentration in the water under control, especially in open vessel systems. This type of system, in
fact, is very sensitive to the phenomenon of extra-oxygenation of the water (an event that can be encouraged by the incorrect positioning of some com-
ponents). This phenomenon can trigger corrosion processes and subsequent drilling of the heat exchanger and pipes.