24 LIST OF THE RECOMMENDED PERIODIC INTERVENTIONS
GENERAL INTERVENTIONS
DESCRIPTION
FREQUENCY
Note
3 Mths
6 Mths
12 Mths
GENERAL INTERVENTIONS
Refrigerant leak control (this operation must be performed with the frequency suggested by current European regulations)
•
Unit supply voltage control
•
Compressor supply voltage control
•
Fan supply voltage control
•
Solenoid valve control
•
Pressure switch operation and calibration control, if applicable
•
Pressure/temperature probe control and reading
•
Control and replacement, if necessary, of the filter driers
•
Compressor contactor control
•
Fan contactor control, if applicable
•
Heat exchanger coil cleaning (preferably from the inside towards the outside)
•
Heat exchanger electric heater control
•
Check for the presence of rust or signs of corrosion in the components, paying particular attention to pressurised containers. In that case, replace them or use specific products
•
•
General unit cleaning
•
Vent the hydraulic circuit and the heat exchangers, the coexistence of air and water reduces performance and can promote the formation of rust
•
INTERVENTIONS ON THE CIRCUIT
DESCRIPTION
FREQUENCY
Note
3 Mths
6 Mths
12 Mths
INTERVENTIONS ON THE COOLING CIRCUIT OPERATING WITH FULL LOAD
Measurement of the overheating temperature
•
Measurement of the undercooling temperature
•
Measurement of the exhaust gas temperature
•
Measurement of fan input
•
Measurement of compressor input
•
COMPRESSOR CONTROLS
Oil level control
•
Oil acidity control
•
Control of proper operation of the carter heater
•
Control of the oil level sensor, if present
•
HYDRAULIC CIRCUIT CONTROLS
Measurement of pump input
•
Check the rotor seal of the pump(s)
•
Control of flexible joints
•
Control of the proper operation and calibration of the flow switch, if present
•
Control of the proper operation of the differential pressure switch, if present
•
Control the concentration of the glycol solution, if applicable
(1)
•
Cleaning the water filter
•
(1)
If the glycol must be changed, refer to the documentation provided by the supplier.
WARNING The frequency of the operations described here is only approximate, they can vary based on how the unit is used and the type of system where
it is installed. If the unit is installed in aggressive environments, we recommend reducing the intervention times.