3.2.
Fixing of the fan control unit
It is strictly forbidden to drill the fan control unit.
The cable which links the fan to its control unit must be handled with care. It can not be modified of
lengthened
It is possible to fix the metal protection of the control unit either on a vertical face or on a horizontal face. In both cases the
control unit must be vertical with its cable glands facing downwards, to ensure an effective protection against the penetration
of water.
When installing the control unit on a horizontal face, it is necessary to maintain a distance between 50 mm and 550
mm between the fan housing and the metal protection of the control unit.
To make the VBP+ F400 compliant, every electrical cable linked to the control unit must be 400 °C resistant.