APPENDIX E
BOILER DEFAULT SETTINGS
MENU & OPTION
FACTORY DEFAULT
Setup Menu
Password 0
Language English
Unit of Temp
Fahrenheit
Comm Address
0
Baud Rate
9600
Configuration Menu
Internal Setpt
130°F
Unit Type
Boiler
Unit Size
1.5 MBTU
Boiler Mode
Constant Setpoint
Remote Signal
(If Mode = Remote Setpoint, Direct Drive or
Combination)
4 – 20 mA / 1-5V
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
70°F
Reset Ratio
(If Boiler Mode = Outdoor Reset)
1.2
Outdoor Sensor
Disabled
System Start Tmp
(If Outdoor Sensor = Enabled)
60°F
Setpt Lo Limit
60°F
Setpt Hi Limit
200°F
Temp Hi Limit
215°F
Max Fire Rate
100%
Pump Delay Timer
0 min
Aux Start On Dly
0 sec
Failsafe Mode
Shutdown
mA Output
Fire Rate Out
CAUTION:
DO NOT Change
Lo Fire Timer
2 sec
Setpt Limit Band (If Setpt Limiting = Enabled)
5°F
Tuning Menu
Prop Band
70°F
Integral Gain
1.00
Derivative Time
0.0 min
E-1