TROUBLESHOOTING
Table 8-4. VFD Parameter Settings
VFD Parameter
Parameter Value
1 0.0
2 100.0
5
AI.AV
10 L3
19
Between -70.0 & 100.0
59 1
61
Between -150 & 250
62
Between 200 & 500
63
Between 250 & 600
64
Between 250 & 700
65
Between 400 & 850
71 18.20
72 18.21
73 18.22
74 18.23
75 18.24
•
If a parameter value differs from the one shown in Table 8-4, reset the parameter to the value
shown in the Table.
•
If a parameter value differs from the one shown in Table 8-4, reset the parameter to the value
shown in the Table
•
If a parameter value differs from the one shown in Table 8-4, reset the parameter to the value
shown in Table 8-4, reset the parameter to the value shown in the Table.
•
If parameters 61, 62, 63, 64, and 65 are skipped and do not appear, perform the following
procedure:
1. Set Pr. 28 to USA
2. Set Pr. 1 to 0.0
3. Set Pr. 2 to 100.0
4. Set Pr. 10 to L3
5. Set Pr. 19 to 82.0
6. Set Pr. 71 to 18.20
7. Set Pr. 72 to 18.21
8. Set Pr. 73 to 18.22
9. Set Pr. 74 to 18.23
10. Set Pr. 75 to 18.24
11. Set Pr. 61 to 50
12. Set Pr. 62 to 300
13. Set Pr. 63 to 400
14. Set Pr. 64 to 450
15. Set Pr. 65 to 600
8-14
Summary of Contents for GF-123
Page 4: ......
Page 8: ......
Page 36: ......
Page 42: ......
Page 68: ......
Page 76: ......
Page 78: ......
Page 84: ......
Page 89: ...APPENDIX F F 5 ...
Page 92: ...APPENDIX F F 8 ...
Page 94: ...APPENDIX F F 10 ...
Page 96: ...APPENDIX F F 12 ...
Page 100: ...APPENDIX G G 4 ...
Page 106: ......
Page 107: ...APPENDIX J BENCHMARK CONTROL PANEL EXPLODED VIEW J 1 ...
Page 108: ...APPENDIX J J 2 P1 P2 P3 P4 P5 P6 BENCHMARK CONTROL PANEL REAR VIEW ...