Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
F11
Flow temperature heating circuit 1
or temperature multifunction 1
F12
Hot water temperature lower or
temperature
multifunction 2
F13
Solid fuel boiler temperature or collector 2
or temperature multifunction 3
F14
Collector 1 temperature or
temperature multifunction 4
F15;
Light;
0-10V I
Room temperature heating circuit 2 or
measured value of the light sensor or
voltage value 0-10V input
OTHER ENTRIES
(General -> Service level)
Additional items and functions in the SERVICE Sub-Menu include the following:
SW NO XXX-
XX
Specifies the Software Version and Index
number currently installed in the
Controller
CASCADE
MANU
(1-8)
Starting different burner stages of the
cascade.
See GF-115-H, Section 6, Paragraph 6.5
for additional startup instructions using
these sub-menu functions.
BURNER TIME
(1-8)
Program Key - Burner time for all stages
BURNER
START (1-8)
Program Key - Burner start for all stages
LIMITER TEST
(1-8)
Safety temperature limiter test with heat
generator temperature display
Start with Program Key (hold down)!
SERVICE
(only with code
no.)
Input of date or operating hours for
service messages
WARNING: NEVER ATTEMPT TO USE THE FOLLOWING RESET
FUNCTIONS:
RESET USER 00
DO NOT USE
RESET EXPERT
00
DO NOT USE
RESET T-PRG 00
DO NOT USE
RETURN
Exit level using Program Key