Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
FUNCTION
DESCRIPTION
ENTRY RANGE
DEFAULT
HEAT CIRCUIT 1 & 2 Sub-Menus
(Continued)
B-HEAT SINK
Circuit Enable
00 = OFF
01 = ON
01 (ON)
RETURN
Press Program Key to exit HEAT
CIRCUIT 1 (or 2) Sub-Menu
.
SOLAR M/F Sub-Menu
MF (1-4)
FUNCTION
Multi-Function (MF) Relay Functions.
00 = No Function
01 = Header Pump
02 = Circulation (Time)
03 = Booster Pump
05 = Pump HS1
06 = Pump HS2
20 = Temp-Controlled Circulation Pump
21 = Pulsed Circulation Pump
22 = Solid Fuel Boiler Integration
23 = Solar Integration
24 = Return Flow Temperature Increase
HS1
25 = Return Flow Temperature Increase
HS2
26 = Return Flow Temperature Increase
HS
Via Buffer Storage
00, 01, 02, 03,
05, 06 & 20-26
00
(No
Function)
MF (1-4)
SET TEMP
Multi-Function Relay Set Point
Temperature
indicates switching temperature for relay
86F – 194F
86°F
MF (1-4)
HYST (1-4)
Multi-Function Relay Hysteresis
39°F – 64°F
48°F
F15 FUNCTION
F15 Function
00 = Room Sensor for Heating Circuit 2
01 = 0 – 10V iInput
02 = Light sensor
00 -02
00
RETURN
Press Program Key to exit SOLAR M/F
Sub-Menu.
8.5 GENERAL Menu
The GENERAL Menu contains a DATE/TIME Sub-Menu and a SERVICE Sub-Menu.