5.2.4.1 Configuring HEATSLOPE Parameter
The
HEATSLOPE
value is configured as shown in the instructions below.
Configuring HEATSLOPE Parameter
1. Ensure ON/OFF switch on front of Modulex boiler is in the ON position.
2. Open controller front panel.
3. Turn the Rotary Knob clockwise to the USER menu.
4. Press Program Key to select the User submenu. The first item (sub-menu) displayed will
be
INSTALLATION
.
5. Continue scrolling clockwise through the
USER
menu until the
HTG CIRCUIT 1
sub-menu
is displayed.
6. With
HTG CIRCUIT 1
displayed, press the Program Key to enter this sub-menu.
7. Using the Rotary Knob, scroll to the
HEATSLOPE
variable. The display will show
“
HEATSLOPE
” and the current value stored in memory (0.00 to 3.00).
8. If the desired value for
HEATSLOPE
is not displayed, press the Program Key once. The
red LED will light.
9. Determine the required value for the
HEATSLOPE
function as explained above. The
value to be entered must be between 0 and 3.00 inclusively.
10. Turn the Rotary Knob until the desired
HEATSLOPE
value is displayed.
11. Press the Program Key to store the
HEATSLOPE
value. The value will flash indicating it
was entered.
Continue scrolling through the
HTG CIRCUIT 1
sub-menu until
RETURN
is displayed.
Press the Program Key to exit the
HTG CIRCUIT 1
sub-menu.