Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
Table 8-2: USER Menu Sub-Menus and Parameters
(Continued)
FUNCTION
DESCRIPTION
ENTRY RANGE
DEFAULT
HTG CIRCUIT 1 Sub-Menu
MODE
Displays Timer Mode for Boiler
- - - -, Standby,
Auto 1, Auto 2,
Day, Night
- - - -
T-ROOM DES 1
Room temperature setting for first
enable tiime.
41.0°F – 104.0°F
68.0° F
T-ROOM DES 2
Room temperature setting for second
enable tiime.
41.0°F – 104.0°F
68.0° F
T-ROOM DES 3
Room temperature setting for third
enable tiime.
41.0°F – 104.0°F
68.0° F
T-REDUCED
Reduced night-time room temperature
setting.
41.0°F – 104.0°F
50.0° F
T-ABSENCE
Required room temperatures during
holidays (vacations).
41.0°F – 104.0°F
59.0° F
T-LIMIT DAY
Applies during day-time heating periods
- - - -,
-23.0°F–104.0°F
66.0°F
T-LIMIT N
Applies during reduced night-time
periods.
- - - -,
-23.0°F–104.0°F
50.0°F
HEATSLOPE
Indicate number of degrees that that the
flow temperature changes if the outside
temperature increases or decreases by 1°F.
0.00 – 3.00
1.20
OPTIM HEAT
Heating optimization
00, 01, 02
00
MAX OPT-TIME
Only active if OPTIM HEAT is set to 01 or
02.
0:00 – 3:00 [h]
2:00 [h]
ECONO OPTI
Reduction optimization
0:00 – 2:00 [h]
0:00 [h]
PC-ENABLE
Code Number for enabling access to
heating circuit data from a Personal
Computer.
0000 – 9999
0000
RETURN
Press Program Key to exit HTG CIRCUIT 1
(or 2) sub-menu.
HTG CIRCUIT 2 Sub-Menu
Functions for HTG Circuit 2 are identical to HTG Circuit 1 Functions listed above.
SOLAR M / F Sub-Menu
(No Functions Currently In This Sub-Menu)
RETURN
Pressing the Program Key with SOLAR M/F
displayed will change display to RETURN.
Press Program Key again to redisplay
SOLAR M/F. Turning the Rotary Knob
clockwise will advance thd display to the
TIME PROGRAM Menu.
N/A