48
FAULT
SYMPTOM
POSSIBLE CAUSE
SOLUTION
There is a water leak
from the air handling
unit.
The drain pan
is full.
The drain pan inside the air
handling unit is clogged.
Check the pan and pipe, clean if
necessary.
There may be water leakage
in the water coils inside the air
handling unit.
Turn off the water connections,
check the coil. Contact AERA
Technical Team in case of damage
detection.
The siphon is not working.
Check siphon, clean, or replace if
necessary.
The drainage pipe outside the
switchboard may be clogged.
Contact your plumber.
Coil connections
are dripping/
leaking.
The unions are loose / cracked
or leaking from the welds.
Contact your plumber.
The heating
coil is dripping/
leaking.
The heating coil damaged/
burst.
Contact the AERA Technical Team.
There are water
drops after the
cooling coil.
Drip tray installed incorrectly /
broken
Check the drip tray, correct if nec-
essary, or request a new one.
Water accumu-
lation in the unit
Storage shortage
The unit got water while it was
waiting at the construction site.
Please clean.
The unit is not installed cor-
rectly.
Check, install according to the
manual.
The unit is damaged
Contact the AERA Technical Team.
Weather protection assembly
does not correct
Check, install according to the
manual.
Positioning the indoor unit
outdoors
Attach the appropriate weather
protection to the unit.