13
System
Pressure
H1
H2
1500 Pa
150 mm
110 mm
1400 Pa
140 mm
100 mm
1300 Pa
130 mm
90 mm
1200 Pa
120 mm
80 mm
1100 Pa
110 mm
70 mm
1000 Pa
100 mm
60 mm
800 Pa
80 mm
40 mm
600 Pa
60 mm
20 mm
System
Pressure
Elbow Height
(H)
1500 Pa
110 mm
1400 Pa
100 mm
1300 Pa
90 mm
1200 Pa
80 mm
1100 Pa
70 mm
1000 Pa
60 mm
800 Pa
40 mm
600 Pa
20 mm
< 600 Pa
-
3.5 Removing of the Fan Fixing Parts
Fan bases are fixed to the unit frame with spring vibration insulators to prevent noise and vibration. Since this situation
may cause damage to the unit by undesirable vibrations during shipment, the fan bases are fixed to the unit frame via
a fixing sheet at the factory. The sheets must be removed before the fans are operated.
The units may be damaged if operated without the fixing sheet of fan Insulators
removed. AERA is not responsible for any damages that may occur due to the failure to remove the sheets.
ATTENTION
Siphon Connection in Positive Pressure
a. Siphon
b. Elbow / S (Required if pressure is more than 600Pa)
Siphon Connection in Negative Pressure
a. Siphon
b. Elbow / S (Required if the pressure is less than -600Pa.)