3.6 Duct Mounting
Air suction and blow nozzles on the unit should be connected to air ducts with flexible duct elements. While installing
flexible duct elements, make sure that the flanges on the unit and the connection flanges of the air duct are on the
same axis.
The length of the assembled flexible connector should be approximately 75% of the stretched length.
Weights of ducts should never be carried to dampers and flanges. Instead, fixed
headstock supports should be placed on the ceiling or the floor and carried to these holders. Otherwise, the dampers
may not work properly and the unit may be damaged.
Duct connection supports should not be connected to the unit frame. Using the
unit frame as support equipment may cause panel damage! AERA is not responsible for any damages that may occur
in such cases.
ATTENTION
ATTENTION
Air Duct
Air Duct