4. Commissioning
EVO-M series air handling units are set at the desired values in the project at the factory and shipped to the user as
plug and play. However, before the air handling unit is commissioned, the list below should be filled in and in case of a
problem, AERA Technical Service should be contacted.
PRE-COMMISSIONING CHECK LIST
NO Control Point
NOPE YES NO
1.
Is the personnel will commission the device qualified?
2.
Have the device's user manual been read / understood?
3.
Is the place the device is assembled in accordance with the user manual?
4.
Is the device module number and type correct?
5.
Is there any visible defect / damage on the device?
6.
Is the device level?
7.
Are the device modules combined correctly?
8.
Do the unit’s doors close properly?
9.
If available , is the roof sheet installed correctly
10. If available, Are the siphon connections of the device in accordance with the user manual
11. Is the drain pan clean and able to drain water?
12. If available , Are the fan insulator sheets removed?
13. Are the fan connection equipment undamaged?
14. Can the fan rotate freely
15. Are channel connections of unit correct ?
16. If available , Is there any damage to the batteries of the unit?
17. If available , Are the battery connections of the unit correct?
18. If available, Is the internal mixing damper closed?
19. If available Are there any damage to the internal silencers?
20. If available , Are the humidifier connections of the unit correct?
21. If available , Are the external sensors of the device connected correctly?
22. Are electrical connections between modules made correctly?
23. Is the control panel connected?
24. If available , Is the BMS connected?
25. If available , Are the unit filters type, airflow direction correct, and are the filters clean?
26. If available, Is there any damage to the heat recovery exchanger of the unit ?
27. If available, Is device heat exchanger bypass damper closed
28. Are the unit power supplies correct?
29. Are there any tools or objects inside the unit?
30. Has the inside of the unit been cleaned after assembly?
31. Is there water in the batteries of the unit ?
If there is a problem with even one of the above items, the unit should not be operated !
If the error cannot be resolved by the user, AERA Technical Service should be contacted!
If all the items in the list above are suitable, the device can be powered for the first time.
The items to be checked after the first run are as follows.