7
Installation and Assembly
Installation and Assembly
You will find information regarding the assembly and installation of the unit.
This may only be carried out by specialists with the necessary knowledge of relevant accident
prevention regulations and other standard regulations relevant to health and safety in the workplace,
based on their training and experience.
The unit should be installed in such a way that it is accessible only to technical personnel with the
appropriate authorisation and training. The unit may only be assembled in accordance with the
application shown in the technical information supplied with the unit.
The units must not be stacked with other components that are not part of the unit.
This is only permissible if the necessary load-bearing capacity has been specially incorporated into
the units delivered from AERA
When connecting the duct it must be ensured that no foreign materials can enter the unit. If necessary,
a suitable wire mesh guard can be installed by the third party at the opening on the discharge/intake
side of the unit.
DAMAGE TO THE UNIT!
During installation of EVO-M units special care must be taken to ensure that no loads are applied to
the floor panels. During assembly work suitable measures should be taken to ensure that any loads
are spread across the bottom profiles (e.g. using grid walkways).
Installation
Installation location
The unit must be installed at a location that fulfils the following requirements:
– The substructure must be level and stable.
– The maximum deflection of the substructure may not exceed 4 mm per metre.
– In units where a condensate drain is installed, the height of the substructure must be at least the
same as to the required siphon height (see siphon).
– Make sure that no damage to the installation location or the environment can be caused by loose
components.
- In order to be able to remove fans, heat exchangers, droplet eliminators, etc. and also perform
servicing and maintenance, a minimum clearance of one unit width must be maintained on the
operating side.
- A minimum clearance of 600 mm between the rear of the unit and the wall must be maintained if
the internal dividing joint connectors cannot be used due to the unit configuration.
Heigh adjustment
Figure 5: Installation location