3 Installation
UPS IST7 Series (60K-200K)
User Manual
62
IST7-60, IST7-100, IST7-120 equip the mains and bypass in one source. When customers need wiring
that mains and bypass in different source, they need to remove the three copper bars (as shown in
Figure3-31) that are short circuited the mains and bypass, and then connect the mains and the bypass
respectively.
Figure3-31
Short circuit bars position of mains and bypass
It is suggested to select DC switch for battery DC input, the detail wiring is as shown in Figure3-32.
Figure3-32
Battery wiring diagram
Step 3
Lead the communication wires go through the wiring hole and connect them to corresponding ports
and ensure reliable connection.
Step 4
Reinstall the bottom wire seal plate, the wiring is finished.
----End
3.5.2 IST7-160, IST7-200
Step 1
Open the door and remove the front and rear wiring cover plate. The position of cover plate of IST7-
200 as shown in Figure3-33.