Powerware Series

Eaton  5130 Rack/Tower UPS
1000–3000 VA
User's Guide

®

Summary of Contents for Powerware 5130

Page 1: ...Powerware Series Eaton 5130 Rack Tower UPS 1000 3000 VA User s Guide...

Page 2: ...Koskelontie 13 FIN 02920 Espoo Finland Phone 358 9 452 661 Fax 358 9 452 665 68 Eaton Powerware FERRUPS and LanSafe are registered trademarks of Eaton Corporation or its subsidiaries and affiliates Mi...

Page 3: ...e user may be required to take additional measures Class B EMC Statements High Voltage Models FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class B digital...

Page 4: ...ion such as important operating and maintenance instructions This symbol indicates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batterie...

Page 5: ...it 24 Tower Setup 25 Installing the UPS 28 RPO and ROO Installation 31 UPS Rear Panels 33 4 Operation 35 Turning the UPS On 35 Starting the UPS on Battery 36 Turning the UPS Off 36 Operating Modes 37...

Page 6: ...ace Internal Batteries 49 How to Replace Extended Battery Modules 51 Recycling the Used Battery or UPS 52 7 Specifications 53 8 Troubleshooting 61 Audible Alarms and UPS Conditions 61 Service and Supp...

Page 7: ...power quality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost productivity and expensive repairs...

Page 8: ...intenance by allowing you to replace batteries safely without powering down the critical load S Shutdown control through the remote power off RPO and remote on off ROO port S Two standard communicatio...

Page 9: ...s the output receptacles may remain electrically live If the input power source in your application is wired line to neutral as in most European applications the voltage to the output receptacles is 0...

Page 10: ...UPS ens indvendige dele kan repareres af brugeren ADVARSEL S Denne UPS indeholder sin egen energikilde batterier Udgangsstikkene kan endog v re str mf rende n r UPS en ikke er koblet til en vekselstr...

Page 11: ...neemt en bewaar deze handleiding als naslagwerk GEVAAR Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING Alle reparaties en onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uit...

Page 12: ...chriften te voldoen mag de gehele apparatuur die op de uitgang van deze UPS is aangesloten geen aardlekstroom van meer dan 3 5 milliamp re hebben OPGELET S Batterijen leveren gevaar op voor elektrisch...

Page 13: ...aan tulojohdotuksessa l ht vastakkeiden j nnite on 115V mitataan linjasta maahan tai linjasta neutraaliin UPS virtal hteen johdotuksesta riippuen S l poista tai irrota sis ntulojohtoa kun UPS on kytke...

Page 14: ...n CA S En ce qui concerne les mod les 230 V il est possible que les prises de sortie restent sous tension Si la source d alimentation de votre application est c bl e phase et neutre comme dans la majo...

Page 15: ...des Handbuches bevor sie mit dem Ger t arbeiten Bewaren Sie das Handbuch zum Nachlesen auf WARNUNG Die USV f hrt lebensgef hrliche Spannungen Alle Reparatur und Wartungsarbeiten sollten nur von Kunde...

Page 16: ...en Die Wartung muss von qualifiziertem Wartungspersonal durchgef hrt werden das im Umgang mit Batterien ge bt ist und ber gute Kenntnisse der erforderlichen Vorsichtsma nahmen verf gt Nicht autorisier...

Page 17: ...pparecchiatura ad esso collegata S Per ridurre il rischio di incendio o di scossa elettrica installare il gruppo statico di continuit in un ambiente interno a temperatura ed umidit controllata privo d...

Page 18: ...de for 230V modellene Spenningen til utgangsstikkene vil v re 0 V dersom din enhets str mkilde er fase til n ytral som p de fleste europeiske enheter Med ledningsf rt fase til fase inngang vil spennin...

Page 19: ...instru es antes de operar o equipamento e guarde este manual para consult lo futuramente CUIDADO A UPS cont m VOLTAGEM MORTAL Todos os reparos e assist ncia t cnica devem ser executados SOMENTE POR PE...

Page 20: ...ipamento total conectado sa da desta UPS n o deve ter uma corrente de fuga terra maior que 3 5 miliamp res PERIGO S As baterias podem oferecer risco de choque el trico ou queimadura ocasionados por al...

Page 21: ...SAFETY WARNINGS Eaton 5130 Rack Tower UPS 1000 3000 VA User s Guide S 164201730 Rev 4 www eaton com powerquality 15 S S 230 0 115 S S 40 95 S 3 5 S S S...

Page 22: ...230V es posible que los recept culos de salida permanezcan el ctricamente activos Si la fuente de energ a de entrada de su aplicaci n est cableada de l nea a neutro como la mayor a de las aplicaciones...

Page 23: ...tion och underh ll av UPS enheten och batterierna L s alla instruktioner innan du anv nder utrustningen och spara den h r anvisningen f r framtida referens FARA Denna UPS enhet inneh ller LIVSFARLIG S...

Page 24: ...verensst mma med internationell standard och installationsf reskrifter f r inte den totala utrustning som anslutits till uttagen p denna UPS enhet ha l cksstr m som verstiger 3 5 milliampere VIKTIGT...

Page 25: ...ged during shipment keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for c...

Page 26: ...ccessory Kit Verify that the following additional items are included with the UPS Table 1 UPS Accessory Kit Item Description UPS user s guide or CD UPS front cover USB cable RS 232 serial cable Rackmo...

Page 27: ...age Model Accessory Items Item Description Two cord retention brackets Two equipment power cords 2500 3000 VA models only Power cord If you ordered an optional EBM verify that the following items are...

Page 28: ...e internal battery connectors by firmly pressing the connectors together see Figure 2 1 2 Figure 2 Connecting the Internal Battery Connectors NOTE A small amount of arcing may occur when connecting th...

Page 29: ...in a rack continue to the following section Rackmount Setup otherwise continue to Tower Setup on page 25 Rackmount Setup The rail kit can be mounted in 19 inch panel 48 cm racks from 24 to 30 inches 6...

Page 30: ...ing rails are not already installed in your rack contact your local distributor to order rail kits To install the rail kit 1 Adjust the rail size for the depth of your rack 2 Select the proper holes i...

Page 31: ...t the bottom of the rack If placed in a rack with existing equipment the rack must be reconfigured to allow the UPS installation at the bottom of the rack NOTE The EBMs must be installed below the UPS...

Page 32: ...Step 3 For one 3U cabinet continue to Installing the UPS on page 28 For two or more cabinets the joining brackets must be installed Skip to Step 5 3 Align the pedestals with the screw holes on the sid...

Page 33: ...with the adjacent cabinet screw holes and secure with the supplied screws see Figure 7 NOTE Joining brackets are required for installations with two or more cabinets Joining Bracket Figure 7 Installi...

Page 34: ...your warranty See UPS Rear Panels on page 33 for the rear panel of each model To install the UPS and optional EBMs 1 If installing an optional EBM continue to Step 2 otherwise continue to Step 3 2 Plu...

Page 35: ...connect your computer to the USB port or RS 232 communication port using the supplied communication cable OR Figure 9 Installing a Communication Cable 4 For rackmount installations only If your rack...

Page 36: ...ements of the heating elements 6 High voltage models only Install the cord retention bracket to secure the cords and provide strain relief see Figure 10 Plug a 10A power cord into the input connector...

Page 37: ...130 includes a two position terminal see Figure 11 that can be either left closed or configured one of two ways S RPO Allows a remote contact to be used to disconnect all equipment connected to the UP...

Page 38: ...ctivate the remote external contact and restart the UPS by pressing the button UPS starts up UPS connected to AC power and AC power is available NOTE The local button overrides the ROO function 4 Conn...

Page 39: ...ROO Connector Receptacles 6 5 15R 1000 1500 VA 8 5 15 5 20R 2200 VA Communication Bay Ground Bonding Screw EBM RJ 11 Connector Site Fault Indicator Figure 12 1000 2200 VA Low Voltage Rear Panel 1000 1...

Page 40: ...ure 14 208V Rear Panel USB Port RS 232 Port EBM Battery Connector RPO ROO Connector 8 10A IEC 320 C13 Receptacles Communication Bay 10A IEC C14 Input Connector EBM RJ 11 Connector Ground Bonding Screw...

Page 41: ...inate Conditions permitting the UPS runs a battery test and the bar graph indicators cycle through The load segment indicators 1 and 2 show that power is available to the output receptacles The bar gr...

Page 42: ...button for two seconds The UPS starts up in Battery mode and supplies battery power to your equipment Turning the UPS Off NOTE Pressing the button while the UPS is in Battery mode causes the UPS to sh...

Page 43: ...Indicator Lit Flashing Unlit Indicator Legend Load Level Indicators Figure 17 UPS Front Panel Normal Mode During Normal mode the button and the indicator illuminate and the front panel displays the p...

Page 44: ...ree seconds Immediately complete and save your work to prevent data loss and similar difficulties When utility power is restored after the UPS shuts down the UPS automatically restarts 1 2 0 25 26 50...

Page 45: ...y USB Port The UPS can communicate with a USB compliant computer using LanSafe Power Management Software or other HID compliant power management software compatible with Microsoft Windows 2000 and XP...

Page 46: ...Tower UPS 1000 3000 VA User s Guide S 164201730 Rev 4 www eaton com powerquality 40 Figure 20 The USB Port 2 Install the LanSafe Power Management Software and USB drivers according to the instructions...

Page 47: ...d the pin for the corresponding signal Contact characteristics optocoupler S Voltage 48 V DC max S Current 25 mA max S Power 1 2W Figure 21 identifies the cable pins and Table 4 describes the pin func...

Page 48: ...ty loads to the programmable receptacles 1 and 2 This feature allows you to save battery power See your power management software manual for details refer to www eaton com powerquality for the latest...

Page 49: ...creen instructions for the Eaton 5130 It is possible to modify the settings listed below detailed comments are available in the UPS Configuration tool Table 5 Main Output Options Function Factory Sett...

Page 50: ...nsfer to battery 294 Vac 271 294 Vac Low threshold for transfer to battery 160 Vac 160 180 Vac Fader activation threshold 265 Vac 244 265 Vac Booster activation threshold 184 Vac 184 207 Vac Maximum i...

Page 51: ...bled Energy savings mode Disabled Enabled UPS ON OFF controlled by software Enabled Disabled Battery level before restart 0 0 100 Table 9 Battery Options Function Factory Setting Other Available Setti...

Page 52: ...ADDITIONAL UPS FEATURES Eaton 5130 Rack Tower UPS 1000 3000 VA User s Guide S 164201730 Rev 4 www eaton com powerquality 46...

Page 53: ...For full battery life keep the UPS at an ambient temperature of 25 C 77 F NOTE The batteries in the UPS are rated for a 3 5 year service life The length of service life varies depending on the freque...

Page 54: ...re on the batteries may need replacing Contact your service representative to order new batteries Replacing Batteries NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode With the hot...

Page 55: ...ted when you pull it out of the UPS S To ensure safety and high performance use only batteries supplied by Eaton To replace the UPS internal batteries 1 Remove the UPS front cover Press the button on...

Page 56: ...see Figure 27 1 2 Figure 27 Removing the Battery Cover 4 Pull the battery block out onto a flat stable surface see Figure 28 See Recycling the Used Battery or UPS on page 52 for proper disposal 1 2 F...

Page 57: ...Ms 1 Unplug the EBM cable from the UPS If additional EBMs are installed unplug the EBM cable from the battery connector on each EBM 2 Unplug the EBM communication cable from the RJ 11 port Repeat for...

Page 58: ...aste center for information on proper disposal of the used battery or UPS WARNING S Do not dispose of the battery or batteries in a fire Batteries may explode Proper disposal of batteries is required...

Page 59: ...Nominal Voltage Voltage Range1 Frequency Range2 Voltage3 Frequency PW5130L1000 XL2U 1000 VA 1000W 120V 89 151V 47 70 Hz 50 Hz system 56 5 70 Hz 60 Hz system 120V 6 10 50 60 Hz 0 1 PW5130L1500 XL2U 150...

Page 60: ...the UPS Configuration tool see page 43 2 Up to 40 Hz in low sensitivity mode programmable using the UPS Configuration tool 3 Adjustable to 100V 10 derating of output power 120 127V Table 12 Weights a...

Page 61: ...5 2 19 0 39 9 kg 88 0 lb Table 13 Power Connections Model Input Connection Output Receptacles PW5130L1000 XL2U 8 ft 15A 5 15P power cord 6 5 15R PW5130L1500 XL2U PW5130L2200 XL2U 8 ft 20A L5 20P powe...

Page 62: ...ry B IEC 61000 4 5 Safety Conformance UL 1778 UL 497A CSA C22 2 No 107 1 NOM 019 SCFI UL 1778 UL 497A data line only CSA C22 2 No 107 1 EN 62040 1 1 IEC 60950 1 IEC 50091 1 1 Agency Markings cULus cUL...

Page 63: ...56 100 150 192 1000 VA 1000W 7 36 66 97 128 PW5130L1500 XL2U with PW5130N1750 EBM2U 150 VA 105W 90 302 495 710 920 375 VA 262W 45 150 270 410 530 750 VA 525W 19 61 121 185 250 1125 VA 787W 10 45 70 11...

Page 64: ...00 VA 1050W 16 62 117 160 210 2250 VA 1575W 8 35 59 85 105 3000 VA 2100W 5 24 40 59 82 3000 VA 2700W 3 17 32 47 62 PW5130i1250 XL2U with PW5130N1750 EBM2U 125 VA 115W 119 430 741 1052 1363 313 VA 288W...

Page 65: ...W 28 122 207 309 412 1250 VA 1125W 11 55 100 150 206 2153 VA 1938W 6 31 59 90 120 2500 VA 2250W 3 23 42 63 85 PW5130i3000 XL2U PW5130i3000 XL3U with PW5130N3000 EBM2U or PW5130N3000 EBM3U depending on...

Page 66: ...SPECIFICATIONS Eaton 5130 Rack Tower UPS 1000 3000 VA User s Guide S 164201730 Rev 4 www eaton com powerquality 60...

Page 67: ...Audible Alarms and UPS Conditions The UPS has an audible alarm feature to alert you of potential power problems Use Table 17 to determine and resolve the UPS alarms and conditions Battery Charge Leve...

Page 68: ...percent load is greater than the set overload level or UPS capacity Check the power drawn by the connected devices and disconnect any non priority devices Check the overload setting The button and in...

Page 69: ...Serial number S Version number if available S Date of failure or problem S Symptoms of failure or problem S Customer return address and contact information If repair is required you will be given a Re...

Page 70: ...TROUBLESHOOTING Eaton 5130 Rack Tower UPS 1000 3000 VA User s Guide S 164201730 Rev 4 www eaton com powerquality 64...

Page 71: ...e option of Company PROCEDURES FOR REPAIR OR REPLACEMENT OF WARRANTED ITEMS The Warranted Item will be repaired or replaced at a Company site or such other location as determined by Company If the War...

Page 72: ...OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY TITLE NON INFRINGEMENT AND FITNESS FOR A PARTICULAR PURPOSE CORRECTION OF NON CONFORMITIES IN THE MANNER AND FOR...

Page 73: ...uaranty applies only to the original End User the End User of any Eaton 3105 5110 5115 5125 and 5130 Products individually and collectively the Product and cannot be transferred This Guaranty applies...

Page 74: ...E FOR DAMAGE TO PROPERTY OR EQUIPMENT OTHER THAN THE PRODUCTS INCLUDING LOSS OF PROFITS OR REVENUE LOSS OF USE OF PRODUCTS LOSS OF DATA COST OF CAPITAL CLAIMS OF CUSTOMERS OF THE END USER OR ANY SPECI...